Outdoor Unit Functional Concept
ESIE04-01
2–46
Part 2 – Functional Description
3
1
2
4
5
3.3.4
High Pressure Protection Control
Outline
In order to prevent abnormal high pressures in the system and hence avoiding activation of the high
pressure safety device the below control function will be activated.
Details
The high pressure value will be calculated from the low pressure, power input and compressor
frequency.
P
HPS opens at : 40 bar (tolerance: +0 / -0.15)
P
HPS closes at : 30 bar (tolerance : +/- 0.15)
Flow chart
Parameters
Normal operation
OR
Hp > 3.53 MPa
15 times or
less stop-
ping in 200
minutes
Normal operation
Compressor operation
frequency B Hz
Compressor stop
Malfunction stop (E3 indication)
Malfunction stop (E3 indication)
Compressor stop
Compressor operation
frequency A Hz
Compressor operation
frequency –1 step/10 sec
Compressor operation
fre1 step/1 min
Compressor operation
fre1 step/5 min
Hp > 3.58 MPa
Hp > 3.43 MPa
OR
OR
&
&
Hp < 3.38 MPa
• Hp > 3.82Mpa
• HPS activates
• HPS activates
• Stopped 16 times in
200 minutes
Hp < 3.48 MPa
• HPS activates
• Hp > 3.82 MPa
for 1 minute
• HPS activates
• Stopped 16 times
in 200 minutes
(When cooling operation)
(When heating operation)
Hp < 3.29 MPa
• Hp < 3.24Mpa
• 30 sec elapsed
RZQ71B
RZQ100 ~125B
A Hz
79 Hz
62 Hz
B Hz
62 Hz
62 Hz
RZQ - Final.book Page 46 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...