ESIE04-01
Error Codes: Outdoor Units
Part 3 – Troubleshooting
3–67
3
3
4
5
1
3.10
Malfunctioning HPS System (
H3
)
Remote Controller
Display
H3
Method of
Malfunction
Detection
The protection device circuit checks continuity in the high pressure switch.
Malfunction
Decision
Conditions
When there is no continuity in the high pressure switch during compressor stops operating.
Supposed Causes
P
Incomplete high pressure switch
P
Disconnection in high pressure switch harness
P
Faulty connection of high pressure switch connector
P
Faulty outdoor unit PC board
P
Disconnected lead wire
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Replace HPS with no continuity.
Resistance in normal operation :
10
Ω
or less
Wait for 10 minutes after
the unit stops operating,
then check the following.
Is there
continuity in each
protection HPS?
Replace the outdoor unit PC board.
Replace the lead wire.
NO
Connect correctly.
Is
protection HPS
connector (*1) correctly
connected to outdoor
unit PC board?
NO
YES
YES
YES
Is there continuity
in lead wire?
NO
*1 Connector symbol
RZQ71~125 : X60A
(S2587)
RZQ - Final.book Page 67 Wednesday, September 8, 2004 8:40 AM
Summary of Contents for RZQ71~125B7V3B
Page 1: ...Service Manual ESIE04 01 RZQ71 125B7V3B Sky Air Inverter R 410A B series ...
Page 2: ......
Page 24: ...ESIE04 01 1 2 Part 1 System Outline 3 1 1 5 ...
Page 32: ...General Outline Outdoor Units ESIE04 01 1 10 Part 1 System Outline 3 1 1 4 5 ...
Page 64: ...General Outline Indoor Units ESIE04 01 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 76: ...Specifications ESIE04 01 1 54 Part 1 System Outline 3 1 1 4 5 ...
Page 92: ...Functional Diagrams ESIE04 01 1 70 Part 1 System Outline 3 1 1 4 5 ...
Page 94: ...ESIE04 01 1 72 Part 1 System Outline ...
Page 122: ...Wiring Diagrams ESIE04 01 1 100 Part 1 System Outline 3 1 1 4 5 ...
Page 140: ...ESIE04 01 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 162: ...General Functionality ESIE04 01 2 24 Part 2 Functional Description 3 1 2 4 5 ...
Page 200: ...Outdoor Unit Functional Concept ESIE04 01 2 62 Part 2 Functional Description 3 1 2 4 5 ...
Page 202: ...ESIE04 01 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 288: ...Error Codes Outdoor Units ESIE04 01 3 88 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 312: ...Additional Checks for Troubleshooting ESIE04 01 3 112 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 314: ...ESIE04 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 356: ...ESIE04 01 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Page 484: ...ESIE04 01 viii Index 3 1 4 5 ...