background image

 

Installation manual

15

250B8W1B

Split system air conditioner

4PW25544-1A

Led state

Throughout the manual the state of the leds is indicated as follows:

x

OFF

w

ON

c

blinking

Setting the dip switches 

(See figure 21)

Setting the push button switch (BS1~5)

Function of the push button switch which is located on the outdoor
unit PCB (A1P):

Setting the mode 2

The set mode can be changed by pressing the 

 button for

5 seconds. The setting mode will change to setting mode 2 and the
H1P led will be ON 

w

.

Exiting mode 2

When all settings are finished and the operation did start according to
the setting, push the 

 button once to exit the mode 2.

9.4.

Test operation

Check the stop valves
Make sure to open the gas and liquid line stop valves.

For details on test operation, refer to the indoor unit installation
manual.

Pre-run checks

1

Make sure the liquid and gas shut-off valves are open.

Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.
-

The refrigerant pressure may not rise, even if the shut-off 
valve is opened after an air purge is performed using a 
vacuum pump.
This is because the indoor unit refrigerant piping is closed off
with electric valves inside. This will not create any problems
during operation.

2

To  protect the compressor, make sure to turn on the power
supply 6 hours before starting operation.

Test operation from remote controller

1

Be sure to set it to cooling and press the operation switch.

2

Press the inspection/test-run switch on the remote control to put
the machine into test-run mode.

What to set with dip switch DS1

3

LOW NOISE OPERATION LEVEL SETTING (

)

(

 = not installed = factory setting)

4

HIGH STATIC PRESSURE SETTING

5

AUTOMATIC LOW NOISE OPERATION AT NIGHT TIME

6

POWER CONSUMPTION LIMITATION SETTING (

)

1, 2, 7, 8

NOT APPLICABLE
DO NOT CHANGE THE FACTORY SETTING.

For changing the set mode

For field setting

For field setting

For test operation

For forced defrost or pump down

NOTE

If you get confused in the middle of the setting
process, push the 

 button once. Then it

returns to setting mode 2 (H1P led is ON 

w

).

L.N.O.P

OFF

DEMAND

BS2

SET

BS1

MODE

BS3

RETURN

BS4

TEST

BS5

FORCED 

DEF

H1P

H2P

H3P

H4P

H5P

H6P

H7P

MODE

TEST:

HWL:

HIGH STATIC

PRESSURE

LN.O.P 

NGHT

L.N.O.P DEMAND

BS1  MODE

BS2  SET

BS3  RETURN

BS4  TEST

BS5  FORCED DEF

BS1  MODE

BS1  MODE

BS1  MODE

NOTE

After turning on the power supply, the unit cannot be
started until the H2P initialisation led goes off
(maximum 12 minutes).

Items to check

Electrical wiring
Inter-unit wiring
Ground wire

Is the wiring as mentioned on the wiring
diagram?
Make sure no wiring has been forgotten
and that there are no missing phases or
reverse phases.

Is the unit properly grounded?

Are any of the wiring attachment screws
loose?

Is the insulation resistance at least 2 M

?

-

Use a 500 V mega-tester when 
measuring insulation.

-

Do not use a mega-tester for circuits 
which are not 230 V.

Refrigerant piping

Is the size of the piping appropriate?

Is the insulation material for the piping
attached securely?
Are both the liquid and gas pipes
insulated?

Are the shut-off valves for both the liquid
side and the gas side open?

Extra refrigerant

Did you write down the extra refrigerant
and the refrigerant piping length?

 Opening direction

A

Liquid side

B

Gas side

Remove the cap and turn 
counterclockwise with a 
hex wrench until it stops

A

B

Summary of Contents for RZQ200B8W1B

Page 1: ...INSTALLATION MANUAL RZQ200B8W1B RZQ250B8W1B Split system air conditioner...

Page 2: ...765 A B 1 2 4 5 6 3 3 15 1 11 3 3 4 6 4 4 2 4 4 5 2 2 2 5 7 2 2 1 1 A B 7 8 9 12 13 H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 1 2 3 3 4 5 6 7 13 14 9 12 12 10 11 8 4 1 2 4 5 3...

Page 3: ...esta declara o se refere 09 10 erkl rer under eneansvar at klimaanl gmodellerne som denne deklaration vedr rer 11 deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som ber rs av...

Page 4: ...R CONDITIONER COMES UNDER THE TERM APPLIANCES NOT ACCESSIBLE TO THE GENERAL PUBLIC WARNING If the warning is not obeyed it may cause serious injuries CAUTION If the caution is not observed it may caus...

Page 5: ...he piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length 7 Select the location of the unit in such a way that neither the discharged air nor the sound g...

Page 6: ...is nontoxic nonflammable and is safe If the refrigerant should leak however its concentration may exceed the allowable limit depending on room size Due to this it could be necessary to take measures a...

Page 7: ...forming nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerat...

Page 8: ...ntion to the following points when re using existing refrigerant piping Perform a visual check on quality of residual oil in existing refrigerant piping This check is extremely important because using...

Page 9: ...ng pipes See the following table for flare part machining dimensions When connecting the flare nuts apply refrigerant oil to the inside and outside of the flares and turn them three or four times at f...

Page 10: ...relative humidity around the cooling pipes might exceed 30 C and RH 80 reinforce the insulation of the cooling pipes at least 20 mm thick Condensation might be formed on the surface of the insulation...

Page 11: ...t is not necessary to charge additionaly if the standard pipe size in pair combination is used and if the total piping length 30 m Additional charging of refrigerant Installations with total piping le...

Page 12: ...L4 10 m 60 type 6 4 Chargeless length 30 m 9 5 30 5 25 m 6 4 25 7 17 10 9 m Additional refrigerant charge 9x0 03 0 27 kg 0 3 kg Example 4 L4 10 m 60 type 6 4 L2 5 m 9 5 L5 7 m 60 type 6 4 250 type L1...

Page 13: ...m is overcharged The refrigerant cannot be charged more than this amount 6 After the refrigerant charge hose is removed make sure to fully open the liquid stop valve Otherwise the piping may burst due...

Page 14: ...onic type main subcool Y1S Solenoid valve 4 way valve Y2S Solenoid valve hotgas bypass Y3S Solenoid valve receiver gas purge Y4S Solenoid valve liquid pipe Z1C Z4C Noise filter ferrite core Z1F Noise...

Page 15: ...uipment will break down Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connection or wires Improper connections or installation may result...

Page 16: ...necting the ground When pulling the ground wire out wire it so that it comes through the cut out section of the cup washer An improper ground connection may prevent a good ground from being achieved 1...

Page 17: ...s When carrying out field settings remove the inspection cover 1 Operate the switches with an insulated stick such as a ball point pen to avoid touching of live parts Make sure to re attach the inspec...

Page 18: ...t with dip switch DS1 3 LOW NOISE OPERATION LEVEL SETTING not installed factory setting 4 HIGH STATIC PRESSURE SETTING 5 AUTOMATIC LOW NOISE OPERATION AT NIGHT TIME 6 POWER CONSUMPTION LIMITATION SETT...

Page 19: ...ion press the button The unit will keep running for 30 seconds and then stops During test operation it is impossible to stop the unit with the remote controller The test operation will be automaticall...

Page 20: ...nsure that air conditioning facilities are installed in a room which is sufficiently large This assures that the maximum concentration level of refrigerant gas is not exceeded in the unlikely event of...

Page 21: ...s in a concentration in excess of the maximum concentration level then it will be necessary to revise the system 5 Please consult your supplier 12 DISPOSAL REQUIREMENTS Dismantling of the unit treatme...

Page 22: ...NOTES NOTES...

Page 23: ...7 9 8 10 11 12 13 15 15 1 2 5 3 3 5 4 4 1 2 3 4 5 DS1 1 2 3 4 OFF ON C O O L H E A T O N O F F 22 21 A 1 2 3 4 4 6 5 6 1 8 4 3 12 8 6 7 9 10 11 2 1 2 3 4 5 T1 T2 1 4 1 2 3 1 2 3 4 X3M X2M X1M 2 4 4 3...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25544 1A...

Reviews: