background image

250B8W1B
Split system air conditioner
4PW25544-1A

Installation manual

8

7.10. Checking of unit and installation conditions

Be sure to check the following:

1

Make sure there is no faulty power wiring or loosing of a nut.
See 

"8. Field wiring" on page 10

.

2

Make sure there is no faulty transmission wiring or loosing of a
nut. See 

"8. Field wiring" on page 10

.

3

Make sure there is no faulty refrigerant piping. See

"7. Refrigerant piping" on page 4

.

4

Make sure piping size is correct. See 

"7.1. Selection of piping

material" on page 4

.

5

Make sure insulation work is done. See 

"7.9. Pipe insulation" on

page 7

.

6

Make sure insulation resistance of main power circuit is not
deteriorated.

Using a megatester for 500 

V, check that the insulation

resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring (between outdoor and
indoor unit, outdoor and COOL/HEAT selector, etc.).

7.11. Stop valve operation procedure

Introduction

Confirm the sizes of the stop valves connected to the system
referring to the table below.

Opening stop valve

1.

Remove the cap and turn the valve counterclockwise with the
hexagon wrench.

2.

Turn it until the shaft stops.

Do not apply excessive force to the stop valve. Doing so may break
the valve body, as the valve is not a backseat type. Always use the
special tool.

3.

Make sure to tighten the cap securely.

Closing stop valve

1.

Remove the cap and turn the valve clockwise with the hexagon
wrench.

2.

Securely tighten the valve until the shaft contacts the main body seal.

3.

Make sure to tighten the cap securely.

For the tightening torque, refer to the table below.

(See figure 17)

CAUTION

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant leaks are
present.

7.12. Additional refrigerant charge

Precaution for servicing

This unit requires additional charging of refrigerant according to the
length of pipe connected at the site. Charge the refrigerant to the
liquid pipe in its liquid state through the serviceport of the liquid stop
valve. Since R410A is a mixed refrigerant, its composition changes if
charged in a state of gas and normal system operation would no
longer be assured.

On this model it is not necessary to charge additionaly if the standard
pipe size in pair combination is used and if the total piping length

30 m.

Additional charging of refrigerant

Installations with total piping lengths 

30 m do not require additional

charging of refrigerant.

For total piping lengths over 30 m, calculate the required additional
refrigerant in function of the calculated length and pipe diameters like
explained in the following procedure.

1

Add up the total piping length.

In case the result is 

30 m, your installation does not require any

additional charge.

In case the result is over 30 m, proceed as explained from step 2
onwards.

2

Subtract 30 m from the calculated total piping length. Take note
of this rest value and, starting from the outdoor unit, check the
exact position in the refrigerant flow where you reach this rest
value.

3

Determine the pipe diameter at that position in the refrigerant
flow.

4

From that same position on, add up the remaining pipe lengths
of that same pipe diameter downstream to the indoor unit(s).

5

Determine the required additional refrigerant charge in function
of the calculated pipe length of that pipe diameter by multiplying
that length by the appropriate calculation coefficient.

Take note of the calculated weight.

6

Repeat step 5 for other pipe diameters in function of other pipe
diameter pipe lengths downstream to the indoor units and add
up all calculated weights.

7

The sum of all calculated weights is the total required additional
refrigerant charge for your installation.

The final result must be rounded to 100 g.

Do not open the stop valve until the steps 

1

~

6

  of

"7.10. Checking of unit and installation conditions" on
page 8

 are completed. If the stop valve is left open without

turning on the power, it may cause refrigerant to buildup in
the compressor, leading to insulation degradation.

Model

Liquid line stop valve

Gas line stop valve

RZQ200

Ø9.5

Ø22.2

RZQ250

Ø12.7

Ø22.2

Tightening torque (N•m) (Turn clockwise to close)

stop 

valve 

size

Shaft (valve body)

Cap 

(valve lid)

Service 

port

Flare nut

Gas line 

piping 

attached 

to unit

Ø9.5

5.4~6.6

Hexagonal 

wrench 

4 mm

13.5~16.5

11.5~13.9

33~40

Ø12.7

8.1~9.9

18~22

50~60

Ø15.9

13.5~16.5

Hexagonal 

wrench 

6 mm

23~27

62~75

Ø22.2

27~33

Hexagonal 

wrench 

10 mm

36~44

22~28

Ø25.4

1

Service port

2

Cap

3

Hexagon hole

4

Shaft

5

Seal

When performing service on the unit requiring the
refrigerant system to be opened, refrigerant must be
evacuated according to local regulations.

Summary of Contents for RZQ200B8W1B

Page 1: ...INSTALLATION MANUAL RZQ200B8W1B RZQ250B8W1B Split system air conditioner...

Page 2: ...765 A B 1 2 4 5 6 3 3 15 1 11 3 3 4 6 4 4 2 4 4 5 2 2 2 5 7 2 2 1 1 A B 7 8 9 12 13 H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 1 2 3 3 4 5 6 7 13 14 9 12 12 10 11 8 4 1 2 4 5 3...

Page 3: ...esta declara o se refere 09 10 erkl rer under eneansvar at klimaanl gmodellerne som denne deklaration vedr rer 11 deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som ber rs av...

Page 4: ...R CONDITIONER COMES UNDER THE TERM APPLIANCES NOT ACCESSIBLE TO THE GENERAL PUBLIC WARNING If the warning is not obeyed it may cause serious injuries CAUTION If the caution is not observed it may caus...

Page 5: ...he piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length 7 Select the location of the unit in such a way that neither the discharged air nor the sound g...

Page 6: ...is nontoxic nonflammable and is safe If the refrigerant should leak however its concentration may exceed the allowable limit depending on room size Due to this it could be necessary to take measures a...

Page 7: ...forming nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerat...

Page 8: ...ntion to the following points when re using existing refrigerant piping Perform a visual check on quality of residual oil in existing refrigerant piping This check is extremely important because using...

Page 9: ...ng pipes See the following table for flare part machining dimensions When connecting the flare nuts apply refrigerant oil to the inside and outside of the flares and turn them three or four times at f...

Page 10: ...relative humidity around the cooling pipes might exceed 30 C and RH 80 reinforce the insulation of the cooling pipes at least 20 mm thick Condensation might be formed on the surface of the insulation...

Page 11: ...t is not necessary to charge additionaly if the standard pipe size in pair combination is used and if the total piping length 30 m Additional charging of refrigerant Installations with total piping le...

Page 12: ...L4 10 m 60 type 6 4 Chargeless length 30 m 9 5 30 5 25 m 6 4 25 7 17 10 9 m Additional refrigerant charge 9x0 03 0 27 kg 0 3 kg Example 4 L4 10 m 60 type 6 4 L2 5 m 9 5 L5 7 m 60 type 6 4 250 type L1...

Page 13: ...m is overcharged The refrigerant cannot be charged more than this amount 6 After the refrigerant charge hose is removed make sure to fully open the liquid stop valve Otherwise the piping may burst due...

Page 14: ...onic type main subcool Y1S Solenoid valve 4 way valve Y2S Solenoid valve hotgas bypass Y3S Solenoid valve receiver gas purge Y4S Solenoid valve liquid pipe Z1C Z4C Noise filter ferrite core Z1F Noise...

Page 15: ...uipment will break down Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connection or wires Improper connections or installation may result...

Page 16: ...necting the ground When pulling the ground wire out wire it so that it comes through the cut out section of the cup washer An improper ground connection may prevent a good ground from being achieved 1...

Page 17: ...s When carrying out field settings remove the inspection cover 1 Operate the switches with an insulated stick such as a ball point pen to avoid touching of live parts Make sure to re attach the inspec...

Page 18: ...t with dip switch DS1 3 LOW NOISE OPERATION LEVEL SETTING not installed factory setting 4 HIGH STATIC PRESSURE SETTING 5 AUTOMATIC LOW NOISE OPERATION AT NIGHT TIME 6 POWER CONSUMPTION LIMITATION SETT...

Page 19: ...ion press the button The unit will keep running for 30 seconds and then stops During test operation it is impossible to stop the unit with the remote controller The test operation will be automaticall...

Page 20: ...nsure that air conditioning facilities are installed in a room which is sufficiently large This assures that the maximum concentration level of refrigerant gas is not exceeded in the unlikely event of...

Page 21: ...s in a concentration in excess of the maximum concentration level then it will be necessary to revise the system 5 Please consult your supplier 12 DISPOSAL REQUIREMENTS Dismantling of the unit treatme...

Page 22: ...NOTES NOTES...

Page 23: ...7 9 8 10 11 12 13 15 15 1 2 5 3 3 5 4 4 1 2 3 4 5 DS1 1 2 3 4 OFF ON C O O L H E A T O N O F F 22 21 A 1 2 3 4 4 6 5 6 1 8 4 3 12 8 6 7 9 10 11 2 1 2 3 4 5 T1 T2 1 4 1 2 3 1 2 3 4 X3M X2M X1M 2 4 4 3...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25544 1A...

Reviews: