background image

250B8W1B
Split system air conditioner
4PW25544-1A

Installation manual

2

2. I

NTRODUCTION

2.1.

Combination

The indoor units can be installed in the following range.

Always use appropriate indoor units compatible with R410A.
To  learn which models of indoor units are compatible with
R410A, refer to the product catalogs.

For installation of the indoor unit(s), refer to the installation
manual delivered with the indoor unit(s).

2.2.

Standard supplied accessories

Refer to 

figure 2

.

2.3.

Optional accessories

This outdoor unit requires the pipe branching kit (optional) when
using a twin, triple or double twin application. Refer to catalogues for
details.

2.4.

Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of
specifications.

3. M

AIN

 

COMPONENTS

For main components and function of the main components, refer to
the Engineering Data Book.

4. S

ELECTION

 

OF

 

LOCATION

This is a class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to
take adequate measures.

The inverter units should be installed in a location that meets the
following requirements:

1

The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation. If
not, the unit may fall over and cause injury.

2

The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. (Refer to

figure 1

 and choose one of the possibilities).

In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.

3

Make sure to provide for adequate measures in order to prevent
that the outdoor unit be used as a shelter by small animals.

Small animals making contact with electrical parts can cause
malfunctions, smoke or fire. Please instruct the customer to
keep the area around the unit clean.

4

There is no danger of fire due to leakage of inflammable gas.

5

Ensure that water cannot cause any damage to the location in
case it drips out the unit (e.g. in case of a blocked drain pipe).

6

The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length.

7

Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb
anyone.

8

Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind will
disturb the operation of the unit. If necessary, use a windscreen
to block the wind.

9

Do not install or operate the unit on locations where air contains
high levels of salt, like e.g. in the vicinity of oceans.

10

During installation, avoid the possibility that children can mount
on the unit or place any object on the unit.

Falling or tumble may result in injury.

Precautions for R410A

The refrigerant requires strict cautions for keeping the
system clean, dry and tight.
-

Clean and dry
Foreign materials (including mineral oils or
moisture) should be prevented from getting mixed
into the system.

-

Tight
Read 

"7.6. Precautions on refrigerant piping" on

page 5

  carefully and follow these procedures

correctly.

Since R410A is a mixed refrigerant, the required
additional refrigerant must be charged in its liquid
state. (If the refrigerant is in state of gas, its
composition changes and the system will not work
properly).

The connected indoor units must be indoor units
designed exclusively for R410A.

Read 

"7. Refrigerant piping" on page 4

 carefully and follow

these procedures correctly.

Since design pressure is 4.0 MPa or 40 bar, pipes of larger
wall thickness may be required. Refer to paragraph

"7.1. Selection of piping material" on page 4

.

RZQ200

RZQ250

Gas line piping (1)

1

1

Gas line piping (2)

1

1

Gas line piping (3)

1

1

Installation manual

1

1

Additional refrigerant charge label

1

1

Auxiliary pipe

1

1

Installation manual

2

Accessory pipes

This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment. If installed as a house-hold appliance it could
cause electromagnetic inteference.

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

A B C D

Sides along the installation site with obstacles

Suction side

Summary of Contents for RZQ200B8W1B

Page 1: ...INSTALLATION MANUAL RZQ200B8W1B RZQ250B8W1B Split system air conditioner...

Page 2: ...765 A B 1 2 4 5 6 3 3 15 1 11 3 3 4 6 4 4 2 4 4 5 2 2 2 5 7 2 2 1 1 A B 7 8 9 12 13 H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 1 2 3 3 4 5 6 7 13 14 9 12 12 10 11 8 4 1 2 4 5 3...

Page 3: ...esta declara o se refere 09 10 erkl rer under eneansvar at klimaanl gmodellerne som denne deklaration vedr rer 11 deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som ber rs av...

Page 4: ...R CONDITIONER COMES UNDER THE TERM APPLIANCES NOT ACCESSIBLE TO THE GENERAL PUBLIC WARNING If the warning is not obeyed it may cause serious injuries CAUTION If the caution is not observed it may caus...

Page 5: ...he piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length 7 Select the location of the unit in such a way that neither the discharged air nor the sound g...

Page 6: ...is nontoxic nonflammable and is safe If the refrigerant should leak however its concentration may exceed the allowable limit depending on room size Due to this it could be necessary to take measures a...

Page 7: ...forming nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerat...

Page 8: ...ntion to the following points when re using existing refrigerant piping Perform a visual check on quality of residual oil in existing refrigerant piping This check is extremely important because using...

Page 9: ...ng pipes See the following table for flare part machining dimensions When connecting the flare nuts apply refrigerant oil to the inside and outside of the flares and turn them three or four times at f...

Page 10: ...relative humidity around the cooling pipes might exceed 30 C and RH 80 reinforce the insulation of the cooling pipes at least 20 mm thick Condensation might be formed on the surface of the insulation...

Page 11: ...t is not necessary to charge additionaly if the standard pipe size in pair combination is used and if the total piping length 30 m Additional charging of refrigerant Installations with total piping le...

Page 12: ...L4 10 m 60 type 6 4 Chargeless length 30 m 9 5 30 5 25 m 6 4 25 7 17 10 9 m Additional refrigerant charge 9x0 03 0 27 kg 0 3 kg Example 4 L4 10 m 60 type 6 4 L2 5 m 9 5 L5 7 m 60 type 6 4 250 type L1...

Page 13: ...m is overcharged The refrigerant cannot be charged more than this amount 6 After the refrigerant charge hose is removed make sure to fully open the liquid stop valve Otherwise the piping may burst due...

Page 14: ...onic type main subcool Y1S Solenoid valve 4 way valve Y2S Solenoid valve hotgas bypass Y3S Solenoid valve receiver gas purge Y4S Solenoid valve liquid pipe Z1C Z4C Noise filter ferrite core Z1F Noise...

Page 15: ...uipment will break down Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connection or wires Improper connections or installation may result...

Page 16: ...necting the ground When pulling the ground wire out wire it so that it comes through the cut out section of the cup washer An improper ground connection may prevent a good ground from being achieved 1...

Page 17: ...s When carrying out field settings remove the inspection cover 1 Operate the switches with an insulated stick such as a ball point pen to avoid touching of live parts Make sure to re attach the inspec...

Page 18: ...t with dip switch DS1 3 LOW NOISE OPERATION LEVEL SETTING not installed factory setting 4 HIGH STATIC PRESSURE SETTING 5 AUTOMATIC LOW NOISE OPERATION AT NIGHT TIME 6 POWER CONSUMPTION LIMITATION SETT...

Page 19: ...ion press the button The unit will keep running for 30 seconds and then stops During test operation it is impossible to stop the unit with the remote controller The test operation will be automaticall...

Page 20: ...nsure that air conditioning facilities are installed in a room which is sufficiently large This assures that the maximum concentration level of refrigerant gas is not exceeded in the unlikely event of...

Page 21: ...s in a concentration in excess of the maximum concentration level then it will be necessary to revise the system 5 Please consult your supplier 12 DISPOSAL REQUIREMENTS Dismantling of the unit treatme...

Page 22: ...NOTES NOTES...

Page 23: ...7 9 8 10 11 12 13 15 15 1 2 5 3 3 5 4 4 1 2 3 4 5 DS1 1 2 3 4 OFF ON C O O L H E A T O N O F F 22 21 A 1 2 3 4 4 6 5 6 1 8 4 3 12 8 6 7 9 10 11 2 1 2 3 4 5 T1 T2 1 4 1 2 3 1 2 3 4 X3M X2M X1M 2 4 4 3...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25544 1A...

Reviews: