![background image](http://html1.mh-extra.com/html/daikin/rzag100l7v1b/rzag100l7v1b_service-manual_2460000077.webp)
ESIE16-03B
|
Part 3. Repair
3.3. Unit specific repair procedures
22/08/16
|
Version 1.1
Page 77
SA R32 Sky-Air RZAG-L
18. Loosen and remove the 3 bolts (5) that fix the compressor (7).
19. Remove the compressor (7).
20. Remove the dampers (4) from the compressor (7).
21. Supply nitrogen to the piping circuit.
22. Heat the 2 compressor pipes (1) using an oxygen acetylene torch.
23. When the solder is liquid, remove the 2 compressor pipes (1).
24. Cut the nitrogen supply when the piping has cooled down.
Figure 3-14: Removing compressor
1. Compressor pipe
5. Bolt
2. R2T thermistor
6. Rubber grommet
3. Compressor wiring
7. Compressor
4. Dampers
2
1
7
5
6
3
3
4