ESIE16-03B
|
Part 5. Appendix
5.1. Field setting
SA R32 Sky-Air RZAG-L
Page 104
22/08/16
|
Version 1.1
•
Current operating condition (normal/test operation/line inspection and normal/error)
•
Night time quiet operation condition (normal/low noise level 1, 2, and)
•
Demand operating condition (normal/30% demand/40% demand/50% demand)
These conditions above can be checked by performing the following steps:
Setting Mode 2
In this mode, settings for the following items can be made.
H1P H2P H3P H4P H5P H6P H7P
HWL
L.N.O.P
h
h
h
h
h
h
h
The system is normally “Setting
mode 1”. Press the MODE (BS1)
button once to set the system to
“Setting mode 1”.
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
During “Setting mode 1”, the lamp is always OFF.
Test operation display
h
In normal operation
k
In test operation
l
In line inspection operation
Error display
h
Normal
k
Error
Night time quiet operation display
hh
Normal operation
hk
Low noise level 1
kh
Low noise level 2
kk
Low noise level 3
Demand level display
hh
30% Normal operation
hk
40% Demand
kh
50% Demand
kk
Demand
h
: BLINK
MODE TEST
DEMAND
k
: ON
l
: OFF
<Selection of setting conditions>
<Selection of setting conditions>
Press the SET (BS2) button and set to
the setting condition you want.
Press the RETURN (BS3) button and
decide the condition.
Press the MODE (BS1) button for 5
seconds and set to “Setting mode 2”.
* If you become unsure of how to proceed, push the MODE (BS1) button and return to setting mode 1.
Press the SET (BS2) button and set the
LED display to a setting item (*1).
Press the RETURN (BS3) button and
decide the item.
Press the RETURN (BS3) button and
set to the initial status of “Setting mode
2”.