ESIE16-03B
|
Part 5. Appendix
5.2. Detailed information setting mode
SA R32 Sky-Air RZAG-L
22/08/16
|
Version 1.1
Page 111
Graph 2
Target evaporating temperature control when “low humidity application” is selected. Field setting 16(26)-2-03:
Graph 3
Target evaporating temperature control when “low humidity appli freeze up operation prevention” is selected. Field setting 16(26)-2-04:
In order to increase continuous operation of the unit in low latent heat applications and avoid the rise of temperature after thermostat OFF, the thermostat control will be changed when
using field settings 16(26)-2-03 & 16(26)-2-04.
Thermostat ON
•
∆
Trs
≥
0.5°C (No change from standard setting)
Thermostat OFF
•
∆
Trs
≤
-2.0°C for 5 minutes continuously.
•
∆
Trs
≤
4.5°C
Capacity
When “low humidity application” is selected. Field setting 16(26)-2-03:
Outdoor
Temp.
(°C-DB)
Indoor Temp. (°C-WB)
11
14
16
18
19
20
22
24
Capacity (% of standard point)
-15
0.62
0.76
0.86
0.95
1.00
1.02
1.07
1.11
-10
0.62
0.76
0.86
0.95
1.00
1.02
1.07
1.11
-5
0.62
0.81
0.91
1.01
1.06
1.16
1.21
1.26
0
0.62
0.81
0.91
1.01
1.06
1.16
1.21
1.26
(°C)
Te target acceptable area
Te target
Remote controller setting temp.
Te (see note) target acceptable area
■
Indoor temp. > setting
→
Te target down
■
Indoor temp. < setting
←
Te target up
Te target limited
≥
0°C
Freeze protection
(40 min. integrated coil temp.
≤
-1°C)
Indoor Temp
(°C DB)
Te target limited
≤
20°C
(to protect the comp.)
(°C)
Te (see note) target acceptable area
■
Indoor temp. > setting
→
Te target down
■
Indoor temp. < setting
→
Te target up
Te target limited
≤
20°C
(to protect the comp.)
Freeze protection
(40 min. integrated coil temp.
≤
-1°C)
Indoor Temp
(°C DB)
Remote controller setting temp.
Te target acceptable area
Te target
Te target limited
≥
2°C
(not to freeze)