![Daikin RZAG100L7V1B Service Manual Download Page 39](http://html1.mh-extra.com/html/daikin/rzag100l7v1b/rzag100l7v1b_service-manual_2460000039.webp)
ESIE16-03B
|
Part 2. Troubleshooting
2.2. Error based troubleshooting
22/08/16
|
Version 1.1
Page 39
SA R32 Sky-Air RZAG-L
2.2.2.23. “PJ-00” – Capacity setting abnormality
Possible cause
Check
Corrective action
Faulty radiating fin thermistor.
Check radiating fin thermistor (see
"Refrigerant thermistors" on page 57
).
Replace radiating fin thermistor when
required.
Faulty outdoor unit PCB in which radiating
fin thermistor is connected.
Check if the HAP LED is blinking in regu-
lar intervals (see
"Main PCB" on page 55
).
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Restore the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals
(see
"Replacing main PCB" on page 89
).
Trigger
Effect
Reset
Outdoor main PCB detects a defective
capacity in EEPROM.
Unit will stop operating.
Manual reset via user interface.
Power supply reset.
Possible cause
Check
Corrective action
Position of PCB dip switches are not OK.
Check if dip switches are set to default
(OFF) position.
Faulty outdoor unit main PCB.
Check if the HAP LED is blinking in regu-
lar intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when HAP
LED is not blinking in regular intervals
(see
"Replacing main PCB" on page 89
).
Faulty capacity adapter on outdoor PCB.
Check if the correct adapter is installed.
Check if the correct spare part is installed.
Adjust capacity adapter when required.