ESIE16-03B
|
Part 2. Troubleshooting
2.4. Component checklist
Page 56
22/08/16
|
Version 1.1
SA R32 Sky-Air RZAG-L
15. Power the Daikin unit.
16. Activate the inverter test (refer to
"Component checklist" on page 121
).
17. Check that all LED’s on the Inverter Analyzer are lit; if not, replace the inverter board (refer to
"Replacing inverter PCB" on
page 87
).
18. Switch off the Daikin unit with the field supplied circuit breaker.
19. Wait a few minutes and confirm that the LED's on the Inverter Analyzer are off.
20. Disconnect the Inverter Analyzer from the U V W wiring.
21. Reconnect the U V W leads to the compressor.
W
ARNING
Electrical shock hazard. Do not touch life wires.
C
AUTION
When wiring the compressor, observe UV W as indicated on the compressor.