background image

English

5

When something is obstructing the top

1.

Installation of single unit 

(Refer to figure 8-[3])

Relation of dimensions of H, A, and L are shown in the table below.

inch(mm)

Note
Get the lower part of the frame sealed so that air from the outlet does 
not bypass.

2.

Series installation (up to two units) 

(Refer to figure 8-[4])

Relation of dimensions of H, A, and L are shown in the table below.

inch(mm)

Note) 
1. Get the lower part of the frame sealed so that air from the outlet 

does not bypass.

2. Only two units at most can be installed in series.

Pattern 2:

Where obstacles in front of the air outlet is lower than the 
unit.
(There is no height limit for obstructions on the intake side.)

When nothing is obstructing the top

1.

Installation of single unit 

(Refer to figure 8-[5])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row 

(Refer to figure 8-[6])

Relation of dimensions of H, A, and L are shown in the table below.

inch(mm)

When something is obstructing the top

1.

Installation of single unit 

(Refer to figure 8-[7])

Relation of dimensions of H, A, and L are shown in the table below.

inch(mm)

Note)
Get the lower part of the frame sealed so that air from the outlet does 
not bypass.

2.

Series installation (up to two units) 

(Refer to figure 8-[8])

Relation of dimensions of H, A, and L are shown in the table below.

inch(mm)

Note)
1. Get the lower part of the frame sealed so that air from the outlet 

does not bypass.

2. Only two units at most can be installed in series.

(7)-4 IN CASE OF STACKED INSTALLATION

1.

In case obstacles exist in front of the outlet side 

(Refer to figure 9-[1])

Note)
1. No more than two units should be stacked.

2. About 4in.(100mm) is required as the dimension for laying the 

upper outdoor unit’s drain pipe.

3. Shut off the Z part (the area between the upper outdoor unit and 

the lower outdoor unit) so that outlet air does not bypass.

2.

In case obstacles exist in front of the air inlet 

(Refer to figure 9-[2])

Note)
1. No more than two units should be stacked.
2. About 4in.(100mm) is required as the dimension for laying the 

upper outdoor unit’s drain pipe.

3. Shut off the Z part (the area between the upper outdoor unit and 

the lower outdoor unit) so that outlet air does not bypass.

(7)-5 IN CASE OF MULTIPLE-ROW INSTALLATION (FOR ROOF 

TOP USE, ETC.)

1.

In case of installing one unit per row 

(Refer to figure 10-[1])

2.

In case of installing multiple units (2 units or more) in lateral connec-
tion per row 

(Refer to figure 10-[2])

Relation of dimensions of H, A, and L are shown in the table below.

inch(mm)

5.

PRECAUTIONS ON INSTALLATION

• Before installation, make sure the unit is level and the foundation is 

sturdy enough to prevent vibration and noise.

• Fasten the unit in place using 4 foundation bolts M12 or equivalent. 

It is best to screw in the foundation bolt until their length remains 
13/16in.(20mm) above the foundation surface.

(Refer to figure 11)

1.

Diagram of lower surface

<Drain pipe installation>

• Locations where drain water from the outdoor unit might be a prob-

lem.
In such locations, for example, where the drain water might drip onto 
passersby, lay the drain pipe using the separately sold drain plug and 
seal up the drain holes in the bottom frame. For details, please con-
tact your dealer.
In case of installing the outdoor unit in cold climates, do not take this 
centralized drainage way. Otherwise, drain pipe freeze-up and ice 
build-up on the bottom frame way occur.

• When laying the drain pipe, at least 4in.(100mm) from the bottom of 

the outdoor unit is needed.

• Make sure the drainage works properly. 

(Watch out for water leaks if piping is brought out the bottom.)

(Refer to figure 12)

1.

Drain plug

2.

4 tabs

3.

Drain receiver

4.

Insert the drain receiver into the drain plug and hook the 
tabs.

5.

Bottom frame drain hole

6.

(1) Insert the drain plug through the drain hole in the 

bottom frame shown in figure 13.

(2) Turn the drain plug along the guides until it stops 

(approx. 40°).

7.

Guide

(Refer to figure 13)

1.

Air outlet side

2.

Diagram of lower surface 

3.

Drain hole (For plug)

4.

Drain hole

[How to remove the transport clasp]

• A yellow transport clasp and washer are attached to the legs of the 

compressor to protect the unit during transportation, so remove 
them as shown in figure 14.

L

A

 H

0 < L 

 1/2H

30(750)

1/2H < L 

 H

40(1000)

H < L

Set the frame to be L 

 H

L

A

 H

0 < L 

 1/2H

40(1000)

1/2H < L 

 H

50(1250)

H < L

Set the frame to be L 

 H

L

A

0 < L 

 1/2H

10(250)

1/2H < L 

 H

12(300)

L

A

 H

0 < L 

 1/2H

4(100)

1/2H < L 

 H

8(200)

H < L

Set the frame to be L 

 H

L

A

 H

0 < L 

 1/2H

10(250)

1/2H < L 

 H

12(300)

H < L

Set the frame to be L 

 H

L

A

 H

0 < L 

 1/2H

10(250)

1/2H < L 

 H

12(300)

H < L

Installation impossible.

01_EN_3P591321-3B.fm  Page 5  Tuesday, December 24, 2019  10:28 AM

Summary of Contents for RXSQ60TAVJUA

Page 1: ...nual Residential VRV System air conditioner Manuel d installation Climatiseur syst me VRV r sidentiel Espa ol Manual de instalaci n Acondicionador residencial de aire sistema VRV Residential VRV INSTA...

Page 2: ...s inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or more 40 1000 or more...

Page 3: ...4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure...

Page 4: ...1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2 3 4 5 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 25 figure 26 figure 27 1 2 3 4 5 6 7 8 figure 28 figure 29 Maximum a...

Page 5: ...lt in serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or dea...

Page 6: ...scent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install the air conditioner...

Page 7: ...y accessories and parts which are of the designated specifica tion when installing 4 SELECTING INSTALLATION SITE 1 Select an installation site where the following conditions are satisfied and that mee...

Page 8: ...ance lev els especially in small rooms so steps need to be taken to prevent refrigerant leakage See the equipment design reference for details 6 Inverter type air conditioners sometimes cause static i...

Page 9: ...MULTIPLE ROW INSTALLATION FOR ROOF TOP USE ETC 1 In case of installing one unit per row Refer to figure 10 1 2 In case of installing multiple units 2 units or more in lateral connec tion per row Refe...

Page 10: ...n a wiring pipe or plastic tube to protect it Secure the wiring with the included clamp so that it does not come in contact with the piping or stop valve See 6 3 How to connect the power supply wiring...

Page 11: ...with no polarity 3 Indoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malf...

Page 12: ...performing nitrogen replacement or releasing nitro gen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrig...

Page 13: ...insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure that the interunit piping does not touch the mounting bolt of the compressor Refe...

Page 14: ...0 5m Pipe length from rst refrigerant branch kit either refnet joint or refnet header to indoor unit 100ft 30 5m Example unit 8 i 100ft 30 5m Example unit 6 b h 131ft 40m unit 8 i k 100ft 30 5m Refrig...

Page 15: ...94 Put connected indoor unit Qty based on table below 2 49 Indoor type table 3 44 A coil 3 75 FXMQ FXEQ FXUQ FXFQ FXZQ FXHQ FXLQ FXDQ FXTQ FXAQ CXTQ 4 78 A Total G2 G3 24 36 G4 B 2 40 G5 G6 A B G7 A B...

Page 16: ...p valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed t...

Page 17: ...All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to perform the check o...

Page 18: ...see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control ch...

Page 19: ...refrigerant temperature to match the required load which is also related to the outdoor ambient conditions E g when your system is operating in cooling you do not need as much cooling under low outdoo...

Page 20: ...ing on the situation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above To activate...

Page 21: ...Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout i...

Page 22: ...ilure related to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 H...

Page 23: ...damage due to sweating and cause compressor damage and void warranty Standard pipe connection Gas side Standard diameter Existing pipe connection Gas side Larger pipe Liquid side No inslated Existing...

Page 24: ...unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve defau...

Page 25: ...action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant sy...

Page 26: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 3B EM19A006A HT 00_CV_3P591321 3B fm Page 5 Friday December 20 2019 4 17 PM...

Reviews: