background image

English

15

[Remote controller displays malfunction code]
(Check on a remote controller connected to the indoor unit.)

• When using a central controller, see the installation manual or ser-

vice manual which came with the central controller.

[If nothing is displayed on the remote controller]

• There might be a problem with the connections or communication 

between the indoor unit and the remote controller.
Make sure all the wiring is properly connected.

CAUTION

To the pipe-layer, To the electrician

After the test run, when handing the unit over to the customer, make 
sure the front panel on the unit and all screws are attached.

10-3 Final charge adjustment

It is not necessary to do this final adjustment normally, but perform the 
following operation only when the most adequate refrigerant charge for 
the best performance is required and the piping length between the out-
door and indoor units is less than 50ft.(15m).
The outdoor temperature must be between 65°F and 105°F.

The number of revolutions of the compressor must be greater than or 
equal to the charge mode. (It can be confirmed by LED display on 
printed circuit board)

The number of revolutions of the compressor LED display.

 :Chargeable  

 :Impossible to charge)

In the case of multiple connection with an indoor unit other than 
CXTQ + G / F, the receiver vessel (Optional item) is not attached to the 
liquid piping.

Run the system for 60 minutes in cooling by the forced operation using 
the field setting mode 2, No.20 LED 

:ON, mode 2, No.7 LED 

:ON, 

(Refer to Service Manual.) to allow pressures to stabilize.

Check subcooling of outdoor unit at LSV. Systems should have the 
target subcooling in the table below.

a. If the subcooling is low, add charge to raise subcooling to the target 

value. (The maximum additional charge is 2.2 lbs.(1kg))

b. If the subcooling is high, remove charge to lower the subcooling to 

the target value.

11. ENERGY SAVING AND OPTIMUM 

OPERATION

RXSQ~ units are equipped with advanced energy saving functionality. 
Depending on the priority, emphasis can be put on energy saving or 
comfort level. Several parameters can be selected, resulting
in the optimal balance between energy consumption and comfort for the 
particular application.

Several patterns are available and explained below. Modify the param-
eters to the needs of your building and to realize the best balance 
between energy consumption and comfort.

Refer to Service Manual for changing the field settings.
Setting definition:[A-B]=C;A=mode,B=setting NO.,C=setting value.

11-1 Three main operation methods are available:

Basic

The refrigerant temperature is fixed independent from the situation.
It corresponds to the standard operation which is known and can be 
expected from/under previous VRV systems:

• To activate this operation method under cooling operation:

change field setting [2-8]=2.

• To activate this operation method under heating operation:

change field setting [2-9]=2.

Automatic(default)

The refrigerant temperature is set depending on the outdoor ambient 
conditions. As such adjusting the refrigerant temperature to match the 
required load (which is also related to the outdoor ambient conditions).
E.g., when your system is operating in cooling, you do not need as 
much cooling under low outdoor ambient temperatures (e.g., 
77°F(25°C)) as under high outdoor ambient temperatures (e.g., 
95°F(35°C)).
Using this idea, the system automatically starts increasing its refrig-
erant temperature, automatically reducing the delivered capacity 
and increasing the system’s

 

efficiency.

• To activate this operation method under cooling operation:

change field setting [2-8]=3(default).

E.g., when your system is operating in heating, you do not need as much 
heating under high outdoor ambient temperatures (e.g., 59°F(15°C)) as 
under low outdoor ambient temperatures (e.g., 23°F (-5°C)).

Malfunc-

tion code

Installation error

Remedial action

E3

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

F6

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

E4

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 
has been finished correctly.

Recalculate the required amount of refrig-
erant from the piping length and add an 
adequate amount of refrigerant.

F3

Refrigerant overcharge.

Recalculate the required amount of refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

Insufficient refrigerant.

Check if the additional refrigerant charge 
has been finished correctly.

Recalculate the required amount of refrig-
erant from the piping length and add an 
adequate amount of refrigerant.

U2

Insufficient supply voltage

Check to see if the supply voltage is sup-
plied properly.

U3

If a check operation has not 
been performed.

Perform a check operation.

U4

No power is supplied to an out-
door unit.

Turn the power on for the outdoor 
unit.

UA

If no dedicated indoor unit is 
being used.

Check the indoor unit. If it is not a dedi-
cated unit, replace the indoor unit.

UF

The stop valve of an outdoor 
unit is left closed.

Open the gas-side stop valve and the liq-
uid-side stop valve.

If the right indoor unit piping and 
wiring are not properly con-
nected to the outdoor unit.

Make sure that the right indoor unit piping 
and wiring are properly connected to the 
outdoor unit.

UH

If the transmission wiring has 
not be connected or it has 
shorted.

Make sure the transmission wiring is cor-
rectly attached to terminals (X2M) F1/F2 
(TO IN/D UNIT) on the outdoor unit circuit 
board.

Model

Target subcooling

RXSQ60~

14±1°F (7.78±0.56°C)

01_EN_3P591321-3B.fm  Page 15  Tuesday, December 24, 2019  10:28 AM

Summary of Contents for RXSQ60TAVJUA

Page 1: ...nual Residential VRV System air conditioner Manuel d installation Climatiseur syst me VRV r sidentiel Espa ol Manual de instalaci n Acondicionador residencial de aire sistema VRV Residential VRV INSTA...

Page 2: ...s inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or more 40 1000 or more...

Page 3: ...4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure...

Page 4: ...1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2 3 4 5 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 25 figure 26 figure 27 1 2 3 4 5 6 7 8 figure 28 figure 29 Maximum a...

Page 5: ...lt in serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or dea...

Page 6: ...scent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install the air conditioner...

Page 7: ...y accessories and parts which are of the designated specifica tion when installing 4 SELECTING INSTALLATION SITE 1 Select an installation site where the following conditions are satisfied and that mee...

Page 8: ...ance lev els especially in small rooms so steps need to be taken to prevent refrigerant leakage See the equipment design reference for details 6 Inverter type air conditioners sometimes cause static i...

Page 9: ...MULTIPLE ROW INSTALLATION FOR ROOF TOP USE ETC 1 In case of installing one unit per row Refer to figure 10 1 2 In case of installing multiple units 2 units or more in lateral connec tion per row Refe...

Page 10: ...n a wiring pipe or plastic tube to protect it Secure the wiring with the included clamp so that it does not come in contact with the piping or stop valve See 6 3 How to connect the power supply wiring...

Page 11: ...with no polarity 3 Indoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malf...

Page 12: ...performing nitrogen replacement or releasing nitro gen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrig...

Page 13: ...insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure that the interunit piping does not touch the mounting bolt of the compressor Refe...

Page 14: ...0 5m Pipe length from rst refrigerant branch kit either refnet joint or refnet header to indoor unit 100ft 30 5m Example unit 8 i 100ft 30 5m Example unit 6 b h 131ft 40m unit 8 i k 100ft 30 5m Refrig...

Page 15: ...94 Put connected indoor unit Qty based on table below 2 49 Indoor type table 3 44 A coil 3 75 FXMQ FXEQ FXUQ FXFQ FXZQ FXHQ FXLQ FXDQ FXTQ FXAQ CXTQ 4 78 A Total G2 G3 24 36 G4 B 2 40 G5 G6 A B G7 A B...

Page 16: ...p valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed t...

Page 17: ...All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to perform the check o...

Page 18: ...see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control ch...

Page 19: ...refrigerant temperature to match the required load which is also related to the outdoor ambient conditions E g when your system is operating in cooling you do not need as much cooling under low outdoo...

Page 20: ...ing on the situation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above To activate...

Page 21: ...Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout i...

Page 22: ...ilure related to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 H...

Page 23: ...damage due to sweating and cause compressor damage and void warranty Standard pipe connection Gas side Standard diameter Existing pipe connection Gas side Larger pipe Liquid side No inslated Existing...

Page 24: ...unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve defau...

Page 25: ...action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant sy...

Page 26: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 3B EM19A006A HT 00_CV_3P591321 3B fm Page 5 Friday December 20 2019 4 17 PM...

Reviews: