background image

12

English

7-8 Air tight test and vacuum drying

After doing the piping, perform the following inspections.

Be sure to use nitrogen gas. (See the figure (“Stop valve operation pro-
cedure”) for the location of the service port.)

[Procedure]
Pressurize from the liquid pipes and gas pipes to 550psi(3.8MPa) (and 
not above 550psi(3.8MPa)). If there is not pressure drop over the next 
24 hours, the equipment has passed the test.
If the pressure drops, check for leakage positions. (Confirm that there is 
no leakage, then release nitrogen.)
If a FXTQ indoor unit and a CXTQ unit are used, only pressurize to 
450psi(3.1MPa).

Use a vacuum pump that can create a vacuum down to at least 

500 microns

.

[Procedure]
Operate the vacuum pump for 

at least 2 hours

 from 

both the liquid  and 

gas pipes

 and decrease the pressure to at least 500 microns. 

Leave at below 500 microns for at least 1 hour and make sure that the 
vacuum gauge does not rise. (If it does rise, there is either still moisture 
in the system or a leak.)

Cases where moisture might enter the piping 

(i.e., if doing work dur-

ing the rainy season, if the actual work takes long enough that conden-
sation may form on the inside of the pipes, if rain might enter the pipes 
during work, etc.)
After performing the vacuum drying for 2 hours, pressurize to 
7.2psi(0.05MPa) (i.e., vacuum breakdown) with nitrogen gas, then 
depressurize down to at least 500 microns a for an hour using the vac-
uum pump (vacuum drying). (If the pressure does not reach at least 500 
microns even after depressurizing for at least 2 hours, repeat the vacuum 
breakdown - vacuum drying process.) Leave as a vacuum for 1 hour after 
that, and make sure the vacuum gauge does not rise.

(Refer to figure 27)

1.

Decompression valve

2.

Nitrogen

3.

Vacuum pump

4.

Valve (Open)

5.

Charge hose

6.

Stop valve service port

7.

Indoor unit

8.

Gas line stop valve (Close)

9.

Liquid line stop valve (Close)

10.

Indicates local procurement

11.

Outdoor unit

NOTE

The stop valve must always be turned to “closed”. 
Otherwise the refrigerant in the outdoor unit will pour out.

• The names of parts needed to operate the stop valve are shown in 

the figure below. The unit is shipped from the factory with the stop 
valve turned to the “closed” position.

• Since the side boards may be deformed if only a torque wrench is 

used when loosening or tightening flare nuts, always lock the stop 
valve with a wrench and then use a torque wrench.

• In cases where the unit is run in heating mode when the outside tem-

perature is low or in other situations where the operating pressure 
might drop, seal the gas-side flare nut on the stop valve with silicon 
sealant or the like to prevent it from freezing.

Stop valve operation procedure

Have a hex wrench ready (size: 0.2in.(4mm) and 0.3in.(6mm)).

Opening the valve

1.

Place the hex wrench on the valve stem and turn counter-clockwise.

2.

Stop when the valve stem no longer turns. It is now open.

Close the valve

1.

Place the hex wrench on the valve stem and turn clockwise.

2.

Stop when the valve stem no longer turns. It is now closed.

• A seal is attached to the point indicated by the arrow.

Take care not to damage it.

• Be sure to tighten the valve cap securely after operating the valves.

• Use a push-rod-provided charging hose for operation.
• Be sure to tighten the valve cap securely after operation.

Tightening torque ................. 8.5 ~ 10.3 ft·lbf (10.8 ~ 14.7 N·m)

Air tight test

Vacuum drying

Stop valve operation procedure

Precautions when handling the stop valve

Servicing port

Valve stem

Flare nut

Valve cap

Field piping connection

Precautions for handling valve cap

Liquid-side tightening torque

Gas-side tightening torque

10.0 ~ 12.2 ft·lbf
13.5 ~ 16.5 N·m

16.6 ~ 20.3 ft·lbf
22.5 ~ 27.5 N·m

Precautions for handling servicing port

Silicon sealing pad

(Make sure that there is no gap)

Direction to open

Direction to open

<Gas pipe>

<Liquid pipe>

Valve cap

Stop valve 
(cap attachment)

01_EN_3P591321-3B.fm  Page 12  Tuesday, December 24, 2019  10:28 AM

Summary of Contents for RXSQ60TAVJUA

Page 1: ...nual Residential VRV System air conditioner Manuel d installation Climatiseur syst me VRV r sidentiel Espa ol Manual de instalaci n Acondicionador residencial de aire sistema VRV Residential VRV INSTA...

Page 2: ...s inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or more 40 1000 or more...

Page 3: ...4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure...

Page 4: ...1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2 3 4 5 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 25 figure 26 figure 27 1 2 3 4 5 6 7 8 figure 28 figure 29 Maximum a...

Page 5: ...lt in serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or dea...

Page 6: ...scent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install the air conditioner...

Page 7: ...y accessories and parts which are of the designated specifica tion when installing 4 SELECTING INSTALLATION SITE 1 Select an installation site where the following conditions are satisfied and that mee...

Page 8: ...ance lev els especially in small rooms so steps need to be taken to prevent refrigerant leakage See the equipment design reference for details 6 Inverter type air conditioners sometimes cause static i...

Page 9: ...MULTIPLE ROW INSTALLATION FOR ROOF TOP USE ETC 1 In case of installing one unit per row Refer to figure 10 1 2 In case of installing multiple units 2 units or more in lateral connec tion per row Refe...

Page 10: ...n a wiring pipe or plastic tube to protect it Secure the wiring with the included clamp so that it does not come in contact with the piping or stop valve See 6 3 How to connect the power supply wiring...

Page 11: ...with no polarity 3 Indoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malf...

Page 12: ...performing nitrogen replacement or releasing nitro gen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrig...

Page 13: ...insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure that the interunit piping does not touch the mounting bolt of the compressor Refe...

Page 14: ...0 5m Pipe length from rst refrigerant branch kit either refnet joint or refnet header to indoor unit 100ft 30 5m Example unit 8 i 100ft 30 5m Example unit 6 b h 131ft 40m unit 8 i k 100ft 30 5m Refrig...

Page 15: ...94 Put connected indoor unit Qty based on table below 2 49 Indoor type table 3 44 A coil 3 75 FXMQ FXEQ FXUQ FXFQ FXZQ FXHQ FXLQ FXDQ FXTQ FXAQ CXTQ 4 78 A Total G2 G3 24 36 G4 B 2 40 G5 G6 A B G7 A B...

Page 16: ...p valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed t...

Page 17: ...All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to perform the check o...

Page 18: ...see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control ch...

Page 19: ...refrigerant temperature to match the required load which is also related to the outdoor ambient conditions E g when your system is operating in cooling you do not need as much cooling under low outdoo...

Page 20: ...ing on the situation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above To activate...

Page 21: ...Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout i...

Page 22: ...ilure related to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 H...

Page 23: ...damage due to sweating and cause compressor damage and void warranty Standard pipe connection Gas side Standard diameter Existing pipe connection Gas side Larger pipe Liquid side No inslated Existing...

Page 24: ...unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve defau...

Page 25: ...action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant sy...

Page 26: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 3B EM19A006A HT 00_CV_3P591321 3B fm Page 5 Friday December 20 2019 4 17 PM...

Reviews: