background image

2

English

additional protection, with the grounding system in North 
America, a dedicated GFCI is not necessary.

Securely fasten the unit terminal cover (panel). If the terminal 
cover/panel is not installed properly, dust or water may enter 
the outdoor unit and could result in fire or electric shock.

When installing or relocating the system, keep the refrigerant 
circuit free from substances other than the specified refrigerant 
(R410A) such as air. Any presence of air or other foreign sub-
stance in the refrigerant circuit could result in abnormal pres-
sure rise or rupture, resulting in injury.

Do not change the setting of the protection devices. If the pres-
sure switch, thermal switch, or other protection device is 
shorted and operated forcibly, or parts other than those speci-
fied by Daikin are used, fire or explosion could result.

CAUTION

Do not touch the switch with wet fingers. Touching a switch 
with wet fingers may result in electric shock.

Do not allow children to play on or around the unit or it may 
result in injury.

The heat exchanger fins are sharp enough to cut, and may 
result in injury if improperly used. To avoid injury wear glove or 
cover the fins when working around them.

Do not touch the refrigerant pipes during and immediately after 
operation as the refrigerant pipes may be hot or cold, depend-
ing on the condition of the refrigerant flowing through the 
refrigerant piping, compressor, and other refrigerant cycle 
parts. It may result in your hands getting burns or frostbite if 
you touch the refrigerant pipes.
To avoid injury, give the pipes time to return to normal temper-
ature or, if you must touch them, be sure to wear proper gloves.

Install drain piping to proper drainage. Improper drain piping 
may result in water leakage and property damage.

Insulate piping to prevent condensation.

Be careful when transporting the product.

Do not turn off the power immediately after stopping operation. 
Always wait for at least 5 minutes before turning off the power. 
Otherwise, water leakage may result.

Do not use a charging cylinder. Using a charging cylinder may 
cause the refrigerant to deteriorate.

Refrigerant R410A in the system must be kept clean, dry, and tight.
(a) Clean and Dry - Foreign materials (including mineral oils such 

as SUNISO oil or moisture) should be prevented from getting 
into the system.

(b) Tight - R410A does not contain any chlorine, does not 

destroy the ozone layer, and does not reduce the earth’s pro-
tection again harmful ultraviolet radiation.
R410A can contribute to the greenhouse effect if it is 
released. Therefore take proper measures to check for the 
tightness of the refrigerant piping installation.
Read the chapter Refrigerant Piping and follow the procedures.

Since R410A is a blend, the required additional refrigerant must 
be charged in its liquid state. If the refrigerant is charged in a 
state of gas, its composition can change and the system will 
not work properly.

The indoor unit is for R410A. See the catalog for indoor models 
that can be connected. Normal operation is not possible when 
connected to other units.

Remote controller (wireless kit) transmitting distance can be 
shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types). Install the indoor unit far 
away from fluorescent lamps as much as possible.

Indoor units are for indoor installation only. Outdoor units can be 
installed either outdoors or indoors. This unit is for outdoor use.

Do not install the air conditioner or heat pump in the following 
locations:
(a) Where a mineral oil mist or oil spray or vapor is produced, 

for example, in a kitchen.

Plastic parts may deteriorate and fall off and thus may result 
in water leakage.

(b) Where corrosive gas, such as sulfurous acid gas, is pro-

duced.
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c) Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of the 
control system and cause the unit to malfunction.

(d) Where flammable gas may leak, where there is carbon fiber, 

or ignitable dust suspension in the air, or where volatile 
flammables such as thinner or gasoline are handled. Operat-
ing the unit in such conditions may result in a fire.

Take adequate measures to prevent the outdoor unit from being 
used as a shelter by small animals. Small animals making con-
tact with electrical parts may result in malfunctions, smoke, or 
fire. Instruct the customer to keep the area around the unit 
clean.

NOTE

Install the power supply and transmission wires for the indoor 
and outdoor units at least 3.5 ft. (1 m) away from televisions or 
radios to prevent image interference or noise.
Depending on the radio waves, a distance of 3.5 ft. (1 m) may 
not be sufficient to eliminate the noise.

Dismantling the unit, treatment of the refrigerant, oil and addi-
tional parts must be done in accordance with the relevant local, 
state, and national regulations.

Do not use the following tools that are used with conventional 
refrigerants: gauge manifold, charge hose, gas leak detector, 
reverse flow check valve, refrigerant charge base, vacuum 
gauge, or refrigerant recovery equipment.

If the conventional refrigerant and refrigerator oil are mixed in 
R410A, the refrigerant result in deterioration.

This air conditioner or heat pump is an appliance that should 
not be accessible to the general public.

As design pressure is 478 psi (3.3 MPa), the wall thickness of 
field-installed pipes should be selected in accordance with the 
relevant local, state, and national regulations.

Codes and Regulations

This product is designed and manufactured to comply with 
national codes. Installation in accordance with such codes and/or 
prevailing local codes/regulations is the responsibility of the 
installer. The manufacturer assumes no responsibility for equip-
ment installed in violation of any codes or regulations. Rated per-
formance is achieved after 72 hours of operation. 

2.

INTRODUCTION

1.

This series uses R410A  refrigerant. Be absolutely sure to comply 
with “

7. PRECAUTIONS ON REFRIGERANT PIPING

”, because 

even greater caution is needed to prevent impurities from entering 
R410A (mineral oils and water).

2.

The design pressure is 478psi (3.3MPa), which means that piping 
may be thicker than conventionally, so please refer to “

7. PRECAU-

TIONS ON REFRIGERANT PIPING

”.

3.

This is a mixed refrigerant, so charge as a liquid when adding refrig-
erant. 
(If charged as a gas, the composition of the refrigerant may change, 
preventing normal operation.)

4.

The indoor unit must use R410A. See the catalog for indoor unit 
models which can be connected. (Normal operation is not possible 
when connected to other units.)

5.

The power supply of this series is single-phase, 208/230V, 60Hz.

01_EN_3P591321-3B.fm  Page 2  Tuesday, December 24, 2019  10:28 AM

Summary of Contents for RXSQ60TAVJUA

Page 1: ...nual Residential VRV System air conditioner Manuel d installation Climatiseur syst me VRV r sidentiel Espa ol Manual de instalaci n Acondicionador residencial de aire sistema VRV Residential VRV INSTA...

Page 2: ...s inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or more 40 1000 or more...

Page 3: ...4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure...

Page 4: ...1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2 3 4 5 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 25 figure 26 figure 27 1 2 3 4 5 6 7 8 figure 28 figure 29 Maximum a...

Page 5: ...lt in serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or dea...

Page 6: ...scent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install the air conditioner...

Page 7: ...y accessories and parts which are of the designated specifica tion when installing 4 SELECTING INSTALLATION SITE 1 Select an installation site where the following conditions are satisfied and that mee...

Page 8: ...ance lev els especially in small rooms so steps need to be taken to prevent refrigerant leakage See the equipment design reference for details 6 Inverter type air conditioners sometimes cause static i...

Page 9: ...MULTIPLE ROW INSTALLATION FOR ROOF TOP USE ETC 1 In case of installing one unit per row Refer to figure 10 1 2 In case of installing multiple units 2 units or more in lateral connec tion per row Refe...

Page 10: ...n a wiring pipe or plastic tube to protect it Secure the wiring with the included clamp so that it does not come in contact with the piping or stop valve See 6 3 How to connect the power supply wiring...

Page 11: ...with no polarity 3 Indoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malf...

Page 12: ...performing nitrogen replacement or releasing nitro gen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrig...

Page 13: ...insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure that the interunit piping does not touch the mounting bolt of the compressor Refe...

Page 14: ...0 5m Pipe length from rst refrigerant branch kit either refnet joint or refnet header to indoor unit 100ft 30 5m Example unit 8 i 100ft 30 5m Example unit 6 b h 131ft 40m unit 8 i k 100ft 30 5m Refrig...

Page 15: ...94 Put connected indoor unit Qty based on table below 2 49 Indoor type table 3 44 A coil 3 75 FXMQ FXEQ FXUQ FXFQ FXZQ FXHQ FXLQ FXDQ FXTQ FXAQ CXTQ 4 78 A Total G2 G3 24 36 G4 B 2 40 G5 G6 A B G7 A B...

Page 16: ...p valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed t...

Page 17: ...All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to perform the check o...

Page 18: ...see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control ch...

Page 19: ...refrigerant temperature to match the required load which is also related to the outdoor ambient conditions E g when your system is operating in cooling you do not need as much cooling under low outdoo...

Page 20: ...ing on the situation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above To activate...

Page 21: ...Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout i...

Page 22: ...ilure related to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 H...

Page 23: ...damage due to sweating and cause compressor damage and void warranty Standard pipe connection Gas side Standard diameter Existing pipe connection Gas side Larger pipe Liquid side No inslated Existing...

Page 24: ...unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve defau...

Page 25: ...action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant sy...

Page 26: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 3B EM19A006A HT 00_CV_3P591321 3B fm Page 5 Friday December 20 2019 4 17 PM...

Reviews: