background image

English

3

2-1 Combination

The indoor units can be installed in the following range.

Be sure to connect a dedicated indoor unit. See the catalog for 
indoor unit models which can be connected.

• Total capacity/quantity of indoor units

Outdoor unit

Total capacity of indoor units

 

Total quantity of indoor units

RXSQ60 type ............... 8.35~21.7kW 

  9 units

                                      28.5~74.1 MBh

2-2 Standard operation limit

Normal operation

The figures below assume following operating conditions for indoor and 
outdoor units:

Equivalent pipe length .................................................... 25ft. (7.6m)
Level difference.................................................................... 0ft. (0m)

Cooling

Heating

Range for operation
Range for pull down operation
Range for warming up operation

2-3 Standard supplied accessories

Make sure that the accessories shown below are all present. 
(The accessories can be found behind the front panel.)

(Refer to figure 1)

1.

Accessories

2.

Screw for front panel

3.

Front panel

2-4 Option accessory

Refrigerant branching kit

* See “

7. PRECAUTIONS ON REFRIGERANT PIPING

” for details 

on how to connect refrigerant branch kits and how many are 
needed.

3.

BEFORE INSTALLATION

<Transporting the Unit>

As shown in figure 2, move the unit slowly. (Take care not to let hands or 
things come in contact with rear fins.)

(Refer to figure 2)

1.

Air outlet grille

2.

Intake hole

3.

Corner

4.

Outdoor unit

5.

Handle

6.

Front

7.

Rear

8.

Always hold the unit by the corners, as holding it by the side 
intake holes on the casing may cause them to deform.

Use only accessories and parts which are of the designated specifica-
tion when installing.

4.

SELECTING INSTALLATION SITE

(1) Select an installation site where the following conditions are 

satisfied and that meets with your customer’s approval.

• Places which are well-ventilated.
• Places where the unit does not bother next-door neighbors.
• A location where small animals will not make nests in the unit.
• Safe places which can withstand the unit’s weight and vibration and 

where the unit can be installed level.

• A locations where there is enough space to install the unit.

VRV ID units and G/F connection

Pair connection with G/F

System

Connection with multiple G/Fs

VRV Indoor units only

Required Option

Receiver Tank

Only one G/F can be combined 
with VRV ID units

· Combination with VRV ID units is not 

allowed.

· G/F heating only by the heat pump 

lockout function. (Heat pump heating 
is not available.)

It should set the field setting #2-57 
and indoor unit setting. If the setting 
is not set, heating malfunction may 
occur.

67

(19)

57.2
(14)

77

(25)

50

(10)

23(–5)

82.4
(28)

Outdoor temperature °FDB (°CDB)

95(35)

122(50)

Indoor temperature 

°FWB (°CWB)

Rated 
cooling 
capacity

41(5)

–4(–20)

50

(10)

68

(20)

43(6)

80.6

(27)

59

(15)

Outdoor temperature °FWB (°CWB)

60(15.5)

Rated 
heating 
capacity

Indoor temperature 

°FDB (°CDB)

Name

Operation 

manual

Clamp

Conduit mounting plate

Quantity

1

4 pcs.

2 pcs.

2 pcs.

Shape

Name

Gas side acces-

sory piping

Insulation tube

Installation 

manual

Quantity

1 pc.

1 pc.

1 pc.

1

Shape

REFNET joint

KHRP26A22T9

REFNET header

KHRP26M22H9

KHRP26M33H9

Vessel kit

BHL-02A

(Large)

(Small)

01_EN_3P591321-3B.fm  Page 3  Tuesday, December 24, 2019  10:28 AM

Summary of Contents for RXSQ60TAVJUA

Page 1: ...nual Residential VRV System air conditioner Manuel d installation Climatiseur syst me VRV r sidentiel Espa ol Manual de instalaci n Acondicionador residencial de aire sistema VRV Residential VRV INSTA...

Page 2: ...s inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or more 40 1000 or more...

Page 3: ...4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure...

Page 4: ...1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2 3 4 5 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 25 figure 26 figure 27 1 2 3 4 5 6 7 8 figure 28 figure 29 Maximum a...

Page 5: ...lt in serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or dea...

Page 6: ...scent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install the air conditioner...

Page 7: ...y accessories and parts which are of the designated specifica tion when installing 4 SELECTING INSTALLATION SITE 1 Select an installation site where the following conditions are satisfied and that mee...

Page 8: ...ance lev els especially in small rooms so steps need to be taken to prevent refrigerant leakage See the equipment design reference for details 6 Inverter type air conditioners sometimes cause static i...

Page 9: ...MULTIPLE ROW INSTALLATION FOR ROOF TOP USE ETC 1 In case of installing one unit per row Refer to figure 10 1 2 In case of installing multiple units 2 units or more in lateral connec tion per row Refe...

Page 10: ...n a wiring pipe or plastic tube to protect it Secure the wiring with the included clamp so that it does not come in contact with the piping or stop valve See 6 3 How to connect the power supply wiring...

Page 11: ...with no polarity 3 Indoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malf...

Page 12: ...performing nitrogen replacement or releasing nitro gen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrig...

Page 13: ...insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure that the interunit piping does not touch the mounting bolt of the compressor Refe...

Page 14: ...0 5m Pipe length from rst refrigerant branch kit either refnet joint or refnet header to indoor unit 100ft 30 5m Example unit 8 i 100ft 30 5m Example unit 6 b h 131ft 40m unit 8 i k 100ft 30 5m Refrig...

Page 15: ...94 Put connected indoor unit Qty based on table below 2 49 Indoor type table 3 44 A coil 3 75 FXMQ FXEQ FXUQ FXFQ FXZQ FXHQ FXLQ FXDQ FXTQ FXAQ CXTQ 4 78 A Total G2 G3 24 36 G4 B 2 40 G5 G6 A B G7 A B...

Page 16: ...p valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed t...

Page 17: ...All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to perform the check o...

Page 18: ...see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control ch...

Page 19: ...refrigerant temperature to match the required load which is also related to the outdoor ambient conditions E g when your system is operating in cooling you do not need as much cooling under low outdoo...

Page 20: ...ing on the situation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above To activate...

Page 21: ...Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout i...

Page 22: ...ilure related to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 H...

Page 23: ...damage due to sweating and cause compressor damage and void warranty Standard pipe connection Gas side Standard diameter Existing pipe connection Gas side Larger pipe Liquid side No inslated Existing...

Page 24: ...unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve defau...

Page 25: ...action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant sy...

Page 26: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 3B EM19A006A HT 00_CV_3P591321 3B fm Page 5 Friday December 20 2019 4 17 PM...

Reviews: