11-5 Setting of larger pipe connection and no insulation on liquid line
When using existing piping, make the following settings.
In case of “Not insulated” (Setting# 1 or 3), the field settings for indoor units below are also required.
· Selection of thermistor
“Only remote controller thermistor”.
If the above setting is not set, thermo-off indoor unit might exert heating capacity.
Caution: Failure to follow the instruction may lead to damage due to sweating and cause compressor damage and void warranty.
Standard pipe connection
Gas side: Standard
diameter
Existing pipe connection
· Gas side: Larger pipe
· Liquid side: No inslated
Existing pipe connection
· Gas side: Larger pipe
·
Liquid side: Inslated
Existing pipe connection
· Gas side: Standard
diameter