background image

8

English

7-1 Selecting piping material

CAUTION

Piping and other pressure containing parts shall comply with the 
applicable legislation and shall be suitable for refrigerant. Use phos-
phoric acid deoxidized seamless copper for refrigerant.

CAUTION

• All field piping must be installed by a licensed refrigeration techni-

cian and must comply with relevant local and national regulations.

• After piping work is complete, do not under any circumstances 

open the stop valve until 

6. FIELD WIRING

 on page 6 and 

9. POST-WORK CHECKS

 on page 13 are complete.

• Do not use flux when brazing the refrigerant piping. Use the phos-

phor copper brazing filler metal(B-Cu93P-710/795:ISO 3677) 
which does not require flux. Flux has extremely negative effect on 
refrigerant piping systems. For instance, if the chlorine based flux 
is used, it will cause pipe corrosion or, in particular, if the flux con-
tains fluorine, it will damage the refrigerant oil.

• Use only pipes which are clean inside and outside and which do not 

accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or 
other contamination. (Foreign materials inside pipes including oils 
for fabrication must be 0.14 gr/10 ft. (30 mg/10 m) or less.)

• Use the following items for the refrigerant piping.

Material :

Jointless phosphor-deoxidized copper pipe.

Size :

See 

7-6 Example of connection

.

Thickness :

Select a thickness for the refrigerant piping which com-

plies with national and local laws.

• Install the refrigerant branch kit while observing the following condi-

tion and referring to the installation manual offered as an accessory 
of the kit.

(Refer to figure 20)

1.

Install the REFNET joint so it splits horizontally or vertically.

2.

Horizontal surface

3.

A-arrow view

4.

±30° or less

5.

Level

6.

Vertical is also OK

7.

Install the REFNET header so that it splits horizontally.

8.

B-arrow view

7-2 Protection against contamination when install-

ing pipes

• Wrap the piping to prevent moisture, dirt, dust, etc. from entering the 

piping.

• Exercise caution when passing copper piping through the through-

holes and when passing them out to the outside.

• In case existing refrigerant pipes between outdoor and indoor are 

being re-used, the line set must be flushed with R410A to avoid 
residual oil from previous system contaminating the new system.
Remember to consult and follow all limitations for using existing pipe.

7-3 Pipe connection

• See “Stop valve operation procedure” in “

7-8 Air tight test and vac-

uum drying

” regarding handling of the stop valve.

• Only use the flare nuts included with the unit. Using different flare 

nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.

(Brazing without performing nitrogen replacement or releasing nitro-
gen into the piping will create large quantities of oxidized film on the 
inside of the pipes, adversely affecting valves and compressors in the 
refrigerating system and preventing normal operation.)

(Refer to figure 21)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Regulator

4.

Nitrogen

5.

Manual valve

6.

Taping

7-4 Connecting the refrigerant piping

• Connection to larger pipe sizes.

In certain configurations this system is designed to be connected to 
larger diameter pipe sizes than the standard factory service valves. 
If the installation requires use of larger pipe diameters, a field setting 
change is required for the system to operate smoothly.

• A filter dryer should not be attached to piping.
• The local inter-unit piping is connectable in four directions.

(Refer to figure 22)

1.

Front panel

2.

Pipe outlet panel

3.

Backward

4.

Sideways

5.

Downward

6.

Pipe outlet panel screw

7.

Forward

8.

Screw for front panel

When connecting the pipings downward, remove the knockout 
by making four holes in the middle on the each side of the 
knockout with a drill.

(Refer to figure 23)

1.

Drill

2.

Center area around knockout hole

3.

Knockout hole

4.

Slit

• After knocking out the knock-out, it is recommended to apply repair 

paint to the edge and the surrounding end surfaces to prevent rusting.

(Refer to figure 24)

1.

Bottom frame

2.

Interunit piping

3.

piping (accessory)

Limitations when using existing pipes.

When installing residential VRV you should use the specified pipe diam-
eter sizes and insulate both gas and liquid pipes.
An exception to this would be in a system replacement application where 
existing piping can be used if the limitations listed below are followed.

1.

Limitations when using existing liquid pipes.
• Observe the piping size of 7-6.
• Using existing liquid pipes is allowed for the main pipe only. Ther-

mal insulation is required to branch pipes.

• Insulation is required to accessible liquid pipe exposed outdoors 

and indoors.

• Liquid pipes which located under outdoor ambient condition should 

to be insulated as much as possible.

• Condensation at non-insulation liquid pipe may cause a problem, 

field pipe setting (Mode2-4) have to set “1” or “3”.

• If there is a place where insulation can not be installed, add the 

amount of refrigerant according to “

7-7 Additional refrigerant 

charge amount

”.

• Insulation on liquid pipe is required if there is possibility to operate 

at reversed ambient temperatures between outdoor and indoor 
(cooling: outdoor<indoor, heating: outdoor>indoor)

2.

Limitations when using existing gas pipes.
• Observe the piping size of 7-6.
• Using existing liquid pipes is allowed for the main pipe only.

Place

Installation Protection 

method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Regardless of the period

01_EN_3P591321-3B.fm  Page 8  Tuesday, December 24, 2019  10:28 AM

Summary of Contents for RXSQ60TAVJUA

Page 1: ...nual Residential VRV System air conditioner Manuel d installation Climatiseur syst me VRV r sidentiel Espa ol Manual de instalaci n Acondicionador residencial de aire sistema VRV Residential VRV INSTA...

Page 2: ...s inch mm 40 1000 or more 40 1000 or more 20 500 or less 12 300 or more 8 200 or more 4 100 or more 4 100 or more figure 5 figure 6 1 2 3 4 20 500 or more 20 500 or less 20 500 or more 40 1000 or more...

Page 3: ...4 100 or more inch mm 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more 4 100 or more L H A 60 1500 or more 24 600 or more 120 3000 or more 1 13 16 20 inch mm 1 2 7 3 4 6 5 figure...

Page 4: ...1 2 3 4 4 5 6 1 2 3 5 6 8 4 7 1 2 3 4 4 1 3 2 figure 21 figure 22 figure 23 figure 24 1 2 3 4 5 1 2 1 2 3 4 5 6 7 11 8 9 10 figure 25 figure 26 figure 27 1 2 3 4 5 6 7 8 figure 28 figure 29 Maximum a...

Page 5: ...lt in serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding will result a severe shock hazard resulting in severe injury or dea...

Page 6: ...scent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for outdoor use Do not install the air conditioner...

Page 7: ...y accessories and parts which are of the designated specifica tion when installing 4 SELECTING INSTALLATION SITE 1 Select an installation site where the following conditions are satisfied and that mee...

Page 8: ...ance lev els especially in small rooms so steps need to be taken to prevent refrigerant leakage See the equipment design reference for details 6 Inverter type air conditioners sometimes cause static i...

Page 9: ...MULTIPLE ROW INSTALLATION FOR ROOF TOP USE ETC 1 In case of installing one unit per row Refer to figure 10 1 2 In case of installing multiple units 2 units or more in lateral connec tion per row Refe...

Page 10: ...n a wiring pipe or plastic tube to protect it Secure the wiring with the included clamp so that it does not come in contact with the piping or stop valve See 6 3 How to connect the power supply wiring...

Page 11: ...with no polarity 3 Indoor unit 4 Under no circumstances should 208 230V be connected Precautions regarding the length of wiring between units Exceeding the following limits may cause transmission malf...

Page 12: ...performing nitrogen replacement or releasing nitro gen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrig...

Page 13: ...insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure that the interunit piping does not touch the mounting bolt of the compressor Refe...

Page 14: ...0 5m Pipe length from rst refrigerant branch kit either refnet joint or refnet header to indoor unit 100ft 30 5m Example unit 8 i 100ft 30 5m Example unit 6 b h 131ft 40m unit 8 i k 100ft 30 5m Refrig...

Page 15: ...94 Put connected indoor unit Qty based on table below 2 49 Indoor type table 3 44 A coil 3 75 FXMQ FXEQ FXUQ FXFQ FXZQ FXHQ FXLQ FXDQ FXTQ FXAQ CXTQ 4 78 A Total G2 G3 24 36 G4 B 2 40 G5 G6 A B G7 A B...

Page 16: ...p valve Close 10 Indicates local procurement 11 Outdoor unit NOTE The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed t...

Page 17: ...All indoor units connected to the outdoor unit operate automatically Complete work on the indoor units in order to ensure maximum safety 10 1 Power On Check Operation Make sure to perform the check o...

Page 18: ...see if cold or hot air is coming out of the indoor unit 4 Press the fan direction and fan strength buttons on the indoor unit to see if they operate properly Precautions during temperature control ch...

Page 19: ...refrigerant temperature to match the required load which is also related to the outdoor ambient conditions E g when your system is operating in cooling you do not need as much cooling under low outdoo...

Page 20: ...ing on the situation When the request from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above To activate...

Page 21: ...Type Description Actions Field setting Shorted between Heating Thermo on Heating Thermo off Heater Fan Heater Fan I Heat pump heating is always locked out 2 16 ON ON ON H L OFF LL II Mode 1 Lockout i...

Page 22: ...ilure related to outdoor units No Setting item display Setting condition display Setting item MODE H1P TEST H2P C H selection Low noise H6P Demand H7P IND H3P Master H4P Slave H5P Factory setting 57 H...

Page 23: ...damage due to sweating and cause compressor damage and void warranty Standard pipe connection Gas side Standard diameter Existing pipe connection Gas side Larger pipe Liquid side No inslated Existing...

Page 24: ...unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during heating A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual load curve defau...

Page 25: ...action is necessary to comply 1 Calculate the amount of refrigerant lb charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant sy...

Page 26: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 2001 3P591321 3B EM19A006A HT 00_CV_3P591321 3B fm Page 5 Friday December 20 2019 4 17 PM...

Reviews: