background image

12

English

<Vacuum drying>

Evacuate the system from the liquid pipe, suction gas pipe, HP/LP 
gas pipe and equalizer pipe shutoff valve service ports by using a 
vacuum pump for more than 2 hours and bring the system to
–14.6 psi or less. After keeping the system under that condition for 
more than 1 hour, check if the vacuum gauge rises or not. If it rises, 
the system may either contain moisture inside or have leaks.

NOTE

If moisture might enter the piping, follow belows.
(I.e., if doing work during the rainy season, if the actual work takes 
long enough that condensation may form on the inside of the 
pipes, if rain might enter the pipes during work, etc.)

After evacuating the system for 2 hours, pressurize the system to 7.25 
psi (vacuum break) with nitrogen gas and evacuate the system again 
using the vacuum pump for 1 hour to –14.6 psi or less (vacuum drying). 
If the system cannot be evacuated to –14.6 psi within 2 hours, repeat 
the operation of vacuum break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that the 
vacuum gauge does not rise.

9.

PIPE INSULATION

Insulation of pipes should be done after performing “

8. AIR TIGHT 

TEST AND VACUUM DRYING

”.

Always insulate the liquid piping, the HP/LP gas piping, the gas pip-
ing, and these pipe connections.
Failing to insulate the pipes may cause leaking or burns.
Especially, be sure to insulate the HP/LP gas piping as withstanding 
as the suction pipe because the suction gas follows in the HP/LP gas 
piping when the system is whole cooling mode.
And be sure to use the insulation which can withstand such temper-
atures of 248°F or more for the HP/LP gas piping, the equalizer pipe 
and the gas piping because the HP/LP gas follows in these pipings.

Reinforce the insulation on the refrigerant piping according to the 
installation environment. Condensation might form on the surface of 
the insulation. Refer to the below.

„

Ambient temperature : 86°F, humidity : 75% to 80% RH : min. 
thickness : 9/16 in..

„

If the ambient temperature exceeds 86°F and the humidity 80% 
RH, then the min. thickness is 3/4 in..
See the Engineering data book for detail.

If there is a possibility that condensation on the shutoff valve might 
drip down into the indoor unit through gaps in the insulation and pip-
ing because the outside unit is located higher than the indoor unit, 
etc., this must be prevented by caulking the connections, etc. 

(Refer to figure 25)

The piping lead-out hole lid should be attached after opening a 
knock hole. 

(Refer to figure 26)

If small animals and the like might enter the unit through the piping 
lead-out hole, close the hole with blocking material (procured on site) 
after completion of “

11. ADDITIONAL REFRIGERANT CHARGE 

AND CHECK OPERATION

”. 

(Refer to figure 29)

(Refer to figure 25)

1.

Insulation material

2.

Caulking, etc.

(Refer to figure 26)

1.

Piping lead-out hole lid

2.

Open a knock hole at “

”. 

3.

Block  “

”.

NOTE

After knocking out the holes, we recommend you remove burrs in the 
knock holes (

See figure 26

) and paint the edges and areas around 

the edges using the repair paint.

10. CHECKING OF DEVICE AND INSTALLA-

TION CONDITIONS

Be sure to check the followings.

For those doing electrical work

1.

Make sure there is no faulty transmission wiring or loosing of a nut.
See “

7-4 Transmission Wiring Connection Procedure

”.

2.

Make sure there is no faulty power wiring or loosing of a nut.
See “

7-5 Power Wiring Connection Procedure

”.

3.

Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular 
value in accordance with relevant local and national regulations.

For those doing pipe work

1.

Make sure piping size is correct. 
See “

6-1 Selection of piping material and Refrigerant branching kit

”.

2.

Make sure insulation work is done. 
See “

9. PIPE INSULATION”

.

3.

Make sure there is no faulty refrigerant piping.
See “

6. REFRIGERANT PIPING

”.

11. ADDITIONAL REFRIGERANT CHARGE 

AND CHECK OPERATION

The outside unit is charged with refrigerant when shipped from the factory, 
but depending on the size and length of the piping when installed, it may 
require additional charging.
For charging the additional refrigerant, follow the procedure in this chapter.
And then carry out the check operation.

11-1 Before working

[About the refrigerant tank]

Check whether the tank has a siphon pipe before charging and place 
the tank so that the refrigerant is charged in liquid form.
(See the figure below.)

NOTE

Always use the proper refrigerant (R410A). If charged with the refrig-
erant containing an improper material, it may cause an explosion or 
accident.

R410A is a mixed refrigerant, so charging it as a gas will cause the refrig-
erant composition to change, which may prevent normal operation.

[Shutoff valve operation procedure]

When operating the shutoff valve, follow the procedure instructed below.

NOTE

Do not open the shutoff valve until 

“10. CHECKING OF DEVICE 

AND INSTALLATION CONDITIONS”

 are completed. If the shutoff 

valve is left open without turning on the power, it may cause refriger-
ant to buildup in the compressor, leading insulation degradation.

Be sure to use the correct tools.
The shutoff valve is not a back-seat type. If forced it to open, it might 
break the valve body.

When using a service port, use the charge hose.

After tightening the cap, make sure no refrigerant gas is leaking.

With siphon pipe

Other tanks

Stand the tank upright and charge.
(The siphon pipe goes all the way inside, 
so the tank does not need be put 
upside-down charge in liquid form.)

Stand the tank upside-down and charge.

Summary of Contents for REYQ72PAYD

Page 1: ...INSTALLATION MANUAL System air conditioner English Fran ais Espa ol REYQ72PAYD REYQ96PAYD REYQ120PAYD REYQ72PATJ REYQ96PATJ REYQ120PATJ...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...2 B 1 2 1 2 3 4 5 6 1 1 2 3 4 3 4 7 8 2 9 6 5 1 4 3 2 1 2 3 TOIN DUNIT TOOUT DUNIT F1 F2 F1 F2 1 2 4 5 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 7 8 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F...

Page 4: ...ure 23 figure 26 figure 28 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 1 2 3 4 5 6 7 8 9 10 13 14 15 11 12 18 19 16 17 1 2 1 2 3 1 2 3 4 5 1 2 3 4 2 5 7 8 6 1 2 3 10 11 12 4 5 6 7...

Page 5: ...dicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or m...

Page 6: ...em will not work properly The indoor unit is for R 410A See the catalog for indoor mod els that can be connected Normal operation is not possible when connected to other units Remote controller wirele...

Page 7: ...nd the floor is flat to prevent vibration and noise generation 3 The piping length between the outside unit and the indoor unit may not exceed the allowable piping length Refer to 6 REFRIGERANT PIPING...

Page 8: ...to figure 6 The base should support the unit with the extent larger than hatched area in figure 7 If protective rubber is to be attached attach it to the whole face of the base The height of the base...

Page 9: ...e wiring 2 Removing Pinch Piping When connecting refrigerant piping to an outside unit remove the pinch piping using the procedure in the figure 11 Refer to figure 11 About handling of shutoff valves...

Page 10: ...ft Example 6 a b 540 ft 8 a m n p 540 ft Example 8 a o 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft that...

Page 11: ...it name BHFP26P90U 3 pipes KHRP25M33H KHRP25M72H 2 pipes KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C...

Page 12: ...2 Total length ft of liquid piping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ72 120PAYD REYQ72 120PATJ REYQ144 192PAYD REYQ144 1...

Page 13: ...terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and...

Page 14: ...BOX with the accessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as s...

Page 15: ...lve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop Needed tools The system for air tight test...

Page 16: ...etion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 29 Refer to figure 25 1 Insulation material 2 Caulking etc Refer to figure 26 1 Piping lead out hole lid 2 Open a knock ho...

Page 17: ...8 Lift the protruding part to open the inspection door Use an insulated rod to operate the push buttons via the EL COMPO BOX s inspection door There is a risk of electric shock if you touch any live p...

Page 18: ...he additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the figure 29 The valve A C and the liquid pipe suction gas pipe HP LP gas pipe equalizer pipe shutoff valve...

Page 19: ...f refrigerant state If the additional refrigerant is little and operation is started before getting stability the system can not judge the charging amount pre cisely and it cause over charge 4 If the...

Page 20: ...Use an insulated rod to operate the push buttons via the inspection door of EL COMPO BOX lid There is a risk of electric shock if you touch any live parts since this operation must be performed with t...

Page 21: ...ction of the refrigerant flow 2 room where refrigerant leak has occurred outflow of all the refrigerant from the system Pay a special attention to the place such as a basement etc where refrigerant ca...

Page 22: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 8M EM09A062A 1002 FS...

Reviews: