[DESIGN PRESSURE]

Since design pressure is 478 psi, the wall thickness of pipes should be 
more carefully selected in accordance with the relevant local and 
national regulations.

1-3 Disposal requirements

Dismantling of the unit,  treatment of the refrigerant, oil and eventual 
other parts, should be done in accordance with the relevant local and 
national regulations.

2.

INTRODUCTION

REYQ-PA series are designed for outdoor installation and used for 
cooling and heating applications.

The BS units that combined with REYQ-PA system for changing the 
refrigerant flow to indoor units are BSVQ36 · 60 · 96P type only. To 
combine with other type BS unit will cause malfunction.

The indoor units that combined with REYQ-PA system for air condi-
tioning are Daikin VRV series indoor units that compatible with 
R410A. To learn which indoor units are compatible with R410A, refer 
to the product catalogs. To combine with other refrigerant indoor unit 
will cause malfunction.

2-1 Combination

The indoor units can be installed in the following range.

Outside unit

Total capacity index of indoor units

REYQ72PAYD/PATJ ............................43

~  93.5

REYQ96PAYD/PATJ ............................57.5 ~  124.5
REYQ120PAYD/PATJ ..........................72

~  156

If the total capacity of the connected indoor units exceeds the capac-
ity of the outside unit, cooling and heating performance may drop 
when running the indoor units. See the capacity table in the Engi-
neering Data Book for details.

2-2 Standard supplied accessories

Confirm the following accessories are included. The storage location of 
the accessories is shown in figure 1.

NOTE

Do not throw away any of the accessories until installation is complete. 
They are needed for installation work.

(Refer to figure 1)

1.

Clamps, Manuals, etc.

2.

Accessory pipes

2-3 Option accessory

To install the outside units, the following optional parts are also required. 
To select an optimum kit, refer to “

6. REFRIGERANT PIPING

”.

• Refrigerant branching kit

Make sure that any separately purchased accessories are designed for 
use with R410A.

2-4 Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of specifications.

2-5 Main components

For main components and function of the main components, refer to the 
Engineering Data Book.

3.

SELECTION OF LOCATION

Select a location for installation that meets the following conditions and 
get the customer’s permission.

1.

Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.

2.

The foundation is strong enough to support the weight of the unit and 
the floor is flat to prevent vibration and noise generation.

3.

The piping length between the outside unit and the indoor unit may 
not exceed the allowable piping length.
(Refer to

  “6. REFRIGERANT PIPING”

)

4.

Locations where the unit’s suction vent and outlet vent do not gener-
ally face the wind.
Wind blowing directly into the suction or outlet vents will interfere with 
the unit’s operation.
If necessary, install some kind of obstruction to block the wind.

5.

The space around the unit is adequate for servicing and the mini-
mum space for air inlet and air outlet is available.
(See the 

“Installation Space Examples”

 for the minimum space 

requirements.)

Installation Space Examples

The installation space requirement shown in figure 2 is a reference 
for cooling operation when the outdoor temperature is 95°F. 
If the design outdoor temperature exceeds 95°F or the heat load 
exceeds maximum capacity in all the outside unit, take an even large 
space on the intake shown in figure 2.

During installation, install the units using the most appropriate of the 
patterns shown in figure 2 for the location in question, taking into 
consideration human traffic and wind.

If the number of units installed is more than that shown in the pattern 
in figure 2, install the units so there are no short circuits.

As regards space in front of the unit, consider the space needed for 
the local refrigerant piping when installing the units.

If the work conditions in figure 2 do not apply, contact your dealer or 
Daikin directly.

(Refer to figure 2)

1.

Front side

2.

No limit to wall height

3.

Service space of front side

4.

Service space of suction side

For Patterns 1 and 2 in figure 2 :

Wall height for front side – no higher than 59 in.

Wall height on the suction side – no higher than 19-5/8 in.

Wall height for sides – no limit.

3 pcs.

1 pc. about each item

Clamp(1)

9 pcs.

Clamp(2)

4 pcs.

Vinyl tube

2 pcs.

2 pcs.

Quantity

Name

Manuals, etc.

Shape

 Operation manual

 Installation manual

 “REQUEST FOR THE 

INDICATON” label 
(Installation records)

Conduit mounting plate

Shape

Liquid side

accessory

pipe (1)

Liquid side

accessory

pipe (2)

Suction gas

side accessory

pipe (1)

Suction gas

side accessory

pipe (2)

1 pc.

1 pc.

72PA type

120PA type

Name

96PA type

Quantity

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

φ

7/8

φ

7/8

φ

1-1/8

φ

3/4

φ

7/8

φ

1-1/8

HP / LP gas

side accessory

pipe (1)

L type

accessory

joint (1)

L type

accessory

joint (2)

accessory

joint (2)

HP / LP gas

side accessory

pipe (2)

Shape

72PA type

120PA type

Name

96PA type

Quantity

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

φ

5/8

φ

3/4

φ

5/8

φ

3/4

φ

1

φ

3/4

for 3 piping

REFNET header

KHRP25M33H KHRP25M72H KHRP25M73HU

REFNET joint

KHRP25M22T KHRP25M33T KHRP25M72TU KHRP25M73TU

for 2 piping

REFNET header KHRP26M22H

KHRP26M33H

KHRP26M72H

REFNET joint

KHRP26M22T

KHRP26M33T

KHRP26M72TU

Summary of Contents for REYQ72PAYD

Page 1: ...INSTALLATION MANUAL System air conditioner English Fran ais Espa ol REYQ72PAYD REYQ96PAYD REYQ120PAYD REYQ72PATJ REYQ96PATJ REYQ120PATJ...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...2 B 1 2 1 2 3 4 5 6 1 1 2 3 4 3 4 7 8 2 9 6 5 1 4 3 2 1 2 3 TOIN DUNIT TOOUT DUNIT F1 F2 F1 F2 1 2 4 5 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 7 8 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F...

Page 4: ...ure 23 figure 26 figure 28 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 1 2 3 4 5 6 7 8 9 10 13 14 15 11 12 18 19 16 17 1 2 1 2 3 1 2 3 4 5 1 2 3 4 2 5 7 8 6 1 2 3 10 11 12 4 5 6 7...

Page 5: ...dicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or m...

Page 6: ...em will not work properly The indoor unit is for R 410A See the catalog for indoor mod els that can be connected Normal operation is not possible when connected to other units Remote controller wirele...

Page 7: ...nd the floor is flat to prevent vibration and noise generation 3 The piping length between the outside unit and the indoor unit may not exceed the allowable piping length Refer to 6 REFRIGERANT PIPING...

Page 8: ...to figure 6 The base should support the unit with the extent larger than hatched area in figure 7 If protective rubber is to be attached attach it to the whole face of the base The height of the base...

Page 9: ...e wiring 2 Removing Pinch Piping When connecting refrigerant piping to an outside unit remove the pinch piping using the procedure in the figure 11 Refer to figure 11 About handling of shutoff valves...

Page 10: ...ft Example 6 a b 540 ft 8 a m n p 540 ft Example 8 a o 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft that...

Page 11: ...it name BHFP26P90U 3 pipes KHRP25M33H KHRP25M72H 2 pipes KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C...

Page 12: ...2 Total length ft of liquid piping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ72 120PAYD REYQ72 120PATJ REYQ144 192PAYD REYQ144 1...

Page 13: ...terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and...

Page 14: ...BOX with the accessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as s...

Page 15: ...lve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop Needed tools The system for air tight test...

Page 16: ...etion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 29 Refer to figure 25 1 Insulation material 2 Caulking etc Refer to figure 26 1 Piping lead out hole lid 2 Open a knock ho...

Page 17: ...8 Lift the protruding part to open the inspection door Use an insulated rod to operate the push buttons via the EL COMPO BOX s inspection door There is a risk of electric shock if you touch any live p...

Page 18: ...he additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the figure 29 The valve A C and the liquid pipe suction gas pipe HP LP gas pipe equalizer pipe shutoff valve...

Page 19: ...f refrigerant state If the additional refrigerant is little and operation is started before getting stability the system can not judge the charging amount pre cisely and it cause over charge 4 If the...

Page 20: ...Use an insulated rod to operate the push buttons via the inspection door of EL COMPO BOX lid There is a risk of electric shock if you touch any live parts since this operation must be performed with t...

Page 21: ...ction of the refrigerant flow 2 room where refrigerant leak has occurred outflow of all the refrigerant from the system Pay a special attention to the place such as a basement etc where refrigerant ca...

Page 22: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 8M EM09A062A 1002 FS...

Reviews: