background image

10

English

NOTE

Open the knock holes with a hammer or the like.

After knocking out the holes, we recommend you remove any burrs 
and paint them using the repair paint to prevent rusting. 

(Refer to figure 17-1, 2)

When passing wiring through the knock holes, remove burrs around 
the knock holes and protect the wiring with protective tape. 

(Refer to figure 17-1, 2)

If small animals might enter the unit, block off any gaps (hatching 
parts in figure 17-1, 2) with material (field supply).

7-4 Transmission Wiring Connection Procedure

Referring to figure 18 connect the transmission wiring between out-
side unit and indoor unit, outside unit and outside unit of other sys-
tem, outside unit and outside unit of same system.

(Refer to figure 18)

1.

EL. COMPO. BOX (1)

2.

EL. COMPO. BOX (2)

3.

Do not open the EL. COMPO. BOX (2) lid. 
(There are no work when installation)

4.

Never connect the power wire.

5.

To outside unit of other system

6.

Use duplex wires (No polarity)

7.

BS unit

8.

Indoor unit

9.

Indoor unit (Cooling only)

NOTE

Do not connect the power wiring to terminals for the transmission 
wiring. Doing so would destroy the entire system.

When connecting wires to the terminal block on the PC-board, too 
much heat or tightening could damage the PC-board. Attach with care.
See the table below for the tightening torque of the transmission wiring 
terminals.

Transmission wiring (About the symbol 

 ~ 

see figure 18

should be done within the following limitations.
If they are exceeded, transmission problems may occur.

 Between outside unit and BS (or indoor) unit

Between BS unit and indoor unit
Between outside unit and outside unit of other systems

Max. wiring length

: 3280 ft

Max. total wiring length

: 6560 ft

Max. no. of branches

: 16

[Note] 
No branch is allowed after branch (

See figure 19

)

Max. no. of outside units of other system 
that can be connected

: 10

(Refer to figure 19)

1.

Branch

2.

Branch after branch

 Between outside unit and outside unit of  same system

Max. wiring length

: 100 ft

The transmission wiring inside the EL.COMPO.BOX should be 
secured using the clamp (1) as shown in figure 20.

(Refer to figure 20)

1.

In the EL.COMPO.BOX

2.

Retain to the EL.COMPO.BOX with the accessory clamp (1).

3.

Vinyl tube (accessory)

Outside the units, the transmission wiring must be finished simulta-
neously with the local refrigerant piping, and wound with tape (field 
supply) as shown in figure 21.

(Refer to figure 21)

1.

Suction gas pipe

2.

HP/LP gas pipe

3.

Liquid pipe

4.

Insulation material

5.

Finishing tape

6.

Transmission wiring

Wiring to other systems should be connected to terminals F1 and F2 
(TO OUT/D UNIT) on the PC-board of the EL. COMPO. BOX(1).

7-5 Power Wiring Connection Procedure

Be sure to connect the power supply wiring to the power supply ter-
minal block and hold it in place using the included clamp as shown in 
the figure 22.

The L1, L2, L3 and N phases of the power wiring should be secured 
separately to the hook using the included clamp (1).

The ground wiring should be bound to the power wiring using the 
included clamp (1) to prevent outside force from being applied to the 
terminal area.

(Refer to figure 22)

1.

Power supply 
(MODEL PAYD:3~460V 60Hz)
(MODEL PATJ:3~208-230V 60Hz)

2.

Earth leakage circuit breaker

3.

Branch switch, earth leakage circuit breaker

4.

Ground wire

5.

EL. COMPO. BOX (1)

6.

EL. COMPO. BOX (2)

7.

Do not open the EL. COMPO. BOX (2) lid.
(There are no work when installation)

8.

Attach insulation sleeves

9.

Power supply terminal block

10.

Ground terminal

11.

Clamp (1) (accessory)

12.

Vinyl tube (accessory)

CAUTION

Be sure to use crimp-style terminal with insulating sleeves for con-
nections. (See the figure below.)

For wiring, use the designated power wire and connect firmly, then 
secure to prevent outside pressure being exerted on the terminal board.

Use an appropriate screwdriver for tightening the terminal screws. A 
screwdriver with a small head will strip the head and make proper 
tightening impossible.

Over-tightening the terminal screws may break them.
See the following table for the tightening torque of the terminal screws.

When pulling the ground wire out, wire it so that it comes through the 
cut out section of the cup washer. (See the figure below.) An improper 
ground connection may prevent a good ground from being achieved.

Screw size

Tightening torque (ft · lbf)

M3.5 (A1P)

0.59 ~ 0.71

1

2

1

2

Screw size

Tightening torque (ft · lbf)

M8 Power terminal, ground terminal

4.06 ~ 5.38

Power wire

Crimp-style terminal

Insulating sleeve

Crimp-style terminal

Cup washer

Cut out section

Summary of Contents for REYQ72PAYD

Page 1: ...INSTALLATION MANUAL System air conditioner English Fran ais Espa ol REYQ72PAYD REYQ96PAYD REYQ120PAYD REYQ72PATJ REYQ96PATJ REYQ120PATJ...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...2 B 1 2 1 2 3 4 5 6 1 1 2 3 4 3 4 7 8 2 9 6 5 1 4 3 2 1 2 3 TOIN DUNIT TOOUT DUNIT F1 F2 F1 F2 1 2 4 5 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 7 8 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F...

Page 4: ...ure 23 figure 26 figure 28 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 1 2 3 4 5 6 7 8 9 10 13 14 15 11 12 18 19 16 17 1 2 1 2 3 1 2 3 4 5 1 2 3 4 2 5 7 8 6 1 2 3 10 11 12 4 5 6 7...

Page 5: ...dicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or m...

Page 6: ...em will not work properly The indoor unit is for R 410A See the catalog for indoor mod els that can be connected Normal operation is not possible when connected to other units Remote controller wirele...

Page 7: ...nd the floor is flat to prevent vibration and noise generation 3 The piping length between the outside unit and the indoor unit may not exceed the allowable piping length Refer to 6 REFRIGERANT PIPING...

Page 8: ...to figure 6 The base should support the unit with the extent larger than hatched area in figure 7 If protective rubber is to be attached attach it to the whole face of the base The height of the base...

Page 9: ...e wiring 2 Removing Pinch Piping When connecting refrigerant piping to an outside unit remove the pinch piping using the procedure in the figure 11 Refer to figure 11 About handling of shutoff valves...

Page 10: ...ft Example 6 a b 540 ft 8 a m n p 540 ft Example 8 a o 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft that...

Page 11: ...it name BHFP26P90U 3 pipes KHRP25M33H KHRP25M72H 2 pipes KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C...

Page 12: ...2 Total length ft of liquid piping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ72 120PAYD REYQ72 120PATJ REYQ144 192PAYD REYQ144 1...

Page 13: ...terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and...

Page 14: ...BOX with the accessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as s...

Page 15: ...lve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop Needed tools The system for air tight test...

Page 16: ...etion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 29 Refer to figure 25 1 Insulation material 2 Caulking etc Refer to figure 26 1 Piping lead out hole lid 2 Open a knock ho...

Page 17: ...8 Lift the protruding part to open the inspection door Use an insulated rod to operate the push buttons via the EL COMPO BOX s inspection door There is a risk of electric shock if you touch any live p...

Page 18: ...he additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the figure 29 The valve A C and the liquid pipe suction gas pipe HP LP gas pipe equalizer pipe shutoff valve...

Page 19: ...f refrigerant state If the additional refrigerant is little and operation is started before getting stability the system can not judge the charging amount pre cisely and it cause over charge 4 If the...

Page 20: ...Use an insulated rod to operate the push buttons via the inspection door of EL COMPO BOX lid There is a risk of electric shock if you touch any live parts since this operation must be performed with t...

Page 21: ...ction of the refrigerant flow 2 room where refrigerant leak has occurred outflow of all the refrigerant from the system Pay a special attention to the place such as a basement etc where refrigerant ca...

Page 22: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 8M EM09A062A 1002 FS...

Reviews: