background image

English

5

Outside unit multi connection piping kit and refrigerant branching kit 
(sold separately) are needed for connection of piping between out-
side units (in case of multi system) and piping branches.
Use only separately sold items selected specifically according to the 
outside unit multi connection piping kit, the refrigerant branching kit 
selection in the “

6-5 Example of connection

”.

6-2 Protection against contamination 

when installing pipes

Protect the piping to prevent moisture, dirt, dust, etc. from enter-
ing the piping.

NOTE

Exercise special caution to prevent dirt or dust when passing piping 
through holes in walls and when passing pipe edges to the exterior.

6-3 Pipe connection

Be sure to perform nitrogen permutation or nitrogen blow when 
brazing. 

(Refer to figure 8)

Brazing without performing nitrogen permutation or nitrogen blow 
into the piping will create large quantities of oxidized film on the 
inside of the pipes, adversely affecting valves and compressors in 
the refrigerating system and preventing normal operation.

(Refer to figure 8)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Nitrogen

4.

Taping

5.

Handy valve

6.

Regulator

The pressure regulator for the nitrogen released when doing the 
brazing should be set to about 2.9 psi (Enough to feel a slight 
breeze on your cheek).

NOTE

Do not use anti-oxidants when brazing the pipe joints.
Residue can clog pipes and break equipment.

6-4 Connecting the refrigerant piping
1.

Direction to bring out the pipes
The local inter unit piping can be connected either forward or to the 
sides (taken out through the bottom) as shown in the figure 9.
When passing out through the bottom, use the knock hole in the bot-
tom frame.

(Refer to figure 9)

1.

Left-side connection

2.

Front connection

3.

Right-side connection

Precautions when knocking out knock holes

Open knock hole (large, small) in the base frame by drilling the 4 
concave around it with a 

φ 

-1/4”-bit. 

(Refer to figure 10)

(Refer to figure 10)

1.

Knock hole 
(large : for liquid pipe, suction gas pipe and HP/LP gas pipe)

2.

Knock hole (small : for equalizer pipe)

3.

Drill

4.

Concave section (4 points)

Be sure to avoid damaging the casing.

After knocking out the holes, we recommend you remove any burrs 
and paint them using the repair paint to prevent rusting.

When passing electrical wiring through the knock holes, protect the wir-
ing with a conduit or bushings, making sure not to damage the wiring.

2.

Removing Pinch Piping

When connecting refrigerant piping to an outside unit, remove the 
pinch piping using the procedure in the figure 11.

(Refer to figure 11)

About handling of shutoff valves, refer to [Shutoff valve operation 
procedure] in 

“11-1 Before working”

.

CAUTION

After removing the gass, remove the pinch piping.
Any gas remaining inside may blow off the pinch piping when you 
dissolve the brazing, causing damage.

(Refer to figure 11)

1.

Pich piping (3 pieces)

2.

Do not remove the relay piping.

3.

Pinch piping

4.

Procedure 1 : Confirm the shutoff valve is closed.

5.

Procedure 2 : Connect a charge hose to the service port of 
shutoff valve and remove the gas in the pinch piping.

6.

Procedure 3 : After removing the gas in the pinch piping, dis-
solve the brazing using a burner and remove the pinch piping.

3.

Connecting refrigerant piping to outside units

Figure 12 shows the example of connecting refrigerant piping to out-
side units.

The local inter unit piping next accesorry pipes are field supplyed.

(Refer to figure 12)

1.

When connected to the front

2.

When connected at lateral side (bottom)

3.

Remove the shutoff valve cover to connect.

4.

Remove the knock hole on the bottom frame and route the 
piping under the bottom frame.

5.

Liquid pipe shutoff valve

6.

Suction gas pipe shutoff valve

7.

HP/LP gas pipe shutoff valve

8.

Brazing

9.

Liquid side accessory pipe (1)

10.

Suction gas side accessory pipe (1)

11.

HP/LP gas side accessory pipe (1)

12.

L type accessory joint (1)

13.

L type accessory joint (2)

14.

Liquid side accessory pipe (2)

15.

Suction gas side accessory pipe (2)

16.

HP/LP gas side accessory pipe (2)

17.

In case of 72PA type use the Accessory joint for connecting 
the Suction gas side accessory pipe (2) to Suction gas side 
shutoff valve.

18.

Accessory joint

NOTE

Make sure the onsite piping does not come into contact with other 
piping or the bottom frame or side panels of the unit.

4.

Branching the refrigerant piping
Heed the restrictions below when installing the refrigerant branching 
kit and read the installation instruction manual with the kit.
(Improper installation could lead to malfunctioning or breakdown of 
the outside unit.)

<REFNET joint>

Install the REFNET joint so it splits horizontally or vertically.

(Refer to figure 13)

1.

Horizontal

2.

A-arrow view

3.

Horizontal surface

4.

±30° or less

5.

Vertical

<REFNET header>

Install the REFNET header so it splits horizontally.

(Refer to figure 14)

1.

Horizontal surface

2.

B-arrow view

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the period

Summary of Contents for REYQ72PAYD

Page 1: ...INSTALLATION MANUAL System air conditioner English Fran ais Espa ol REYQ72PAYD REYQ96PAYD REYQ120PAYD REYQ72PATJ REYQ96PATJ REYQ120PATJ...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...2 B 1 2 1 2 3 4 5 6 1 1 2 3 4 3 4 7 8 2 9 6 5 1 4 3 2 1 2 3 TOIN DUNIT TOOUT DUNIT F1 F2 F1 F2 1 2 4 5 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 7 8 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F...

Page 4: ...ure 23 figure 26 figure 28 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 1 2 3 4 5 6 7 8 9 10 13 14 15 11 12 18 19 16 17 1 2 1 2 3 1 2 3 4 5 1 2 3 4 2 5 7 8 6 1 2 3 10 11 12 4 5 6 7...

Page 5: ...dicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or m...

Page 6: ...em will not work properly The indoor unit is for R 410A See the catalog for indoor mod els that can be connected Normal operation is not possible when connected to other units Remote controller wirele...

Page 7: ...nd the floor is flat to prevent vibration and noise generation 3 The piping length between the outside unit and the indoor unit may not exceed the allowable piping length Refer to 6 REFRIGERANT PIPING...

Page 8: ...to figure 6 The base should support the unit with the extent larger than hatched area in figure 7 If protective rubber is to be attached attach it to the whole face of the base The height of the base...

Page 9: ...e wiring 2 Removing Pinch Piping When connecting refrigerant piping to an outside unit remove the pinch piping using the procedure in the figure 11 Refer to figure 11 About handling of shutoff valves...

Page 10: ...ft Example 6 a b 540 ft 8 a m n p 540 ft Example 8 a o 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft that...

Page 11: ...it name BHFP26P90U 3 pipes KHRP25M33H KHRP25M72H 2 pipes KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C...

Page 12: ...2 Total length ft of liquid piping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ72 120PAYD REYQ72 120PATJ REYQ144 192PAYD REYQ144 1...

Page 13: ...terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and...

Page 14: ...BOX with the accessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as s...

Page 15: ...lve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop Needed tools The system for air tight test...

Page 16: ...etion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 29 Refer to figure 25 1 Insulation material 2 Caulking etc Refer to figure 26 1 Piping lead out hole lid 2 Open a knock ho...

Page 17: ...8 Lift the protruding part to open the inspection door Use an insulated rod to operate the push buttons via the EL COMPO BOX s inspection door There is a risk of electric shock if you touch any live p...

Page 18: ...he additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the figure 29 The valve A C and the liquid pipe suction gas pipe HP LP gas pipe equalizer pipe shutoff valve...

Page 19: ...f refrigerant state If the additional refrigerant is little and operation is started before getting stability the system can not judge the charging amount pre cisely and it cause over charge 4 If the...

Page 20: ...Use an insulated rod to operate the push buttons via the inspection door of EL COMPO BOX lid There is a risk of electric shock if you touch any live parts since this operation must be performed with t...

Page 21: ...ction of the refrigerant flow 2 room where refrigerant leak has occurred outflow of all the refrigerant from the system Pay a special attention to the place such as a basement etc where refrigerant ca...

Page 22: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 8M EM09A062A 1002 FS...

Reviews: