background image

English

7

Outside unit multi connection piping kit and

Refrigerant branch kit selection

Pipe size selection

 Refrigerant branch kits can only be used with R410A.

 When multi outdoor system are installed, be sure to use the 

special separately sold Outside unit multi connection piping 

kit. (BHFP26P90U).

(For how to select the proper kit, follow the table at right.)

 Never use BHFP26M90U, BHFP22M90U for M type of this 

series or T joint (field supplyed).

How to select the REFNET joint

Piping between outside unit(*2 and refrigerant branch kit (partA)

How to select the REFNET header

When using REFNET joint at the first branch counted from the outside unit side,

choose from the following table in accordance with the outside unit capacity type.

(Example : REFNET joint A)

Choose from the following table in accordance with the outdoor

units system capacity type.

Piping between outside unit multi connection piping kit and outside unit (part B)

Choose from the following table in accordance with the capacity type of

the outside unit connected.

Choose from the following table in accordance with the total capacity index of all

the indoor units connected below the REFNET header.

How to select the outside unit multi connection piping kit

(This is required when the system is multi outside unit system.)

Choose from the following table in accordance with the number of outside units.

Choose the REFNET joints other than the first branch from the following table in accordance

with the total capacity index of all the indoor units connected below the REFNET joint.

Outside unit capacity type

REYQ72 · 96PA type

REYQ120~192PA type

Indoor unit total capacity index

× < 72

72 

 × < 111

111 

 ×

Refrigerant branch kit name

KHRP25M33T

KHRP25M72TU

3 pipes

KHRP25M22T

KHRP25M33T

KHRP25M72TU

2 pipes

KHRP26M22T

KHRP26M33T

KHRP26M72TU

Refrigerant branch kit name

Indoor unit total capacity index

× < 72

72 

 × < 111

111 

Number of outside unit

2 units

Connecting piping kit name

BHFP26P90U

3 pipes

KHRP25M33H 

  KHRP25M72H

2 pipes

KHRP26M22H or KHRP26M33H

KHRP26M33H

KHRP26M72H

Refrigerant branch kit name

Example for indoor units

connected downstream

Example REFNET joint C : Indoor units  5  +  6  +  7  +  8

Example REFNET joint B : Indoor units  7  +  8

Example REFNET header : Indoor units  1  +  2  +  3  +  4  +  5  +  6

Example REFNET header :

Indoor units  1  +  2  +  3  +  4  +  5  +  6  +  7  +  8

The thickness and material shall be selected in 

accordance with local code.

For an outside unit installation, make

the settings in accordance with the

following figure.

Outside unit

Equalizer pipe

(part C)

Piping between outside unit

multi connection piping kit

and outside unit (part B)

Piping between outside unit multi

connection piping kits

Piping between outside unit and

refrigerant branch kit (part A)

Outside unit

capacity type

REYQ72PA type

REYQ96PA type

REYQ120PA type

REYQ144PA type

REYQ168PA type

REYQ192PA type

Piping size (O. D.)

Piping size (O. D.)

Suction gas pipe

φ

3/4

φ

7/8

φ

1-1/8

HP/LP gas pipe

φ

5/8

φ

3/4

φ

7/8

φ

1-1/8

Liquid pipe

φ

3/8

φ

1/2

φ

5/8

Outside unit

capacity type

REMQ72 · 96PA type

Suction gas pipe

φ

7/8

HP/LP gas pipe

φ

3/4

Liquid pipe

φ

3/8

Piping between refrigerant branch kits

Piping between refrigerant branch kit and BS unit

Piping between BS unit and refrigerant branch kit

Choose from the following table in accordance with the total capacity type of all the

indoor units connected downstream.

Piping between refrigerant branch kit, BS unit and indoor unit.

Equalizer pipe (part C) (outside multi system only)

Match to the size of the connection pipng on the indoor unit.

*1 Connection piping must not exceed the refrigerant Piping size between outside

unit and refrigerant branch kit (part A) 

*2 When selecting 2 pipes line(gas pipe and liquid pipe), use Suction gas pipe

column for gas pipe and Liquid pipe column for liquid pipe.

Indoor capacity index

× < 54

54 

 × < 72

72 

 × < 111

111 

 × < 162

162 

 ×

Indoor unit capacity type

07

 · 

09

 · 

12

 · 

18

24

 · 

30

 · 

36

 · 

48

gas pipe

φ

1/2

φ

5/8

Liquid pipe

φ

1/4

φ

3/8

Piping size (O. D.)

φ

3/4

 (unit : in.)

 (unit : in.)

Piping size (O. D.)

 (unit : in.)

Piping size (O. D.)

 (unit : in.)

 (unit : in.)

Suction gas pipe

φ

5/8

φ

3/4

φ

7/8

φ

1-1/8

HP/LP gas pipe

φ

1/2

φ

5/8

φ

3/4

φ

1-1/8

Liquid pipe

φ

3/8

φ

1/2

φ

5/8

Summary of Contents for REYQ72PAYD

Page 1: ...INSTALLATION MANUAL System air conditioner English Fran ais Espa ol REYQ72PAYD REYQ96PAYD REYQ120PAYD REYQ72PATJ REYQ96PATJ REYQ120PATJ...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...2 B 1 2 1 2 3 4 5 6 1 1 2 3 4 3 4 7 8 2 9 6 5 1 4 3 2 1 2 3 TOIN DUNIT TOOUT DUNIT F1 F2 F1 F2 1 2 4 5 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 7 8 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F...

Page 4: ...ure 23 figure 26 figure 28 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 1 2 3 4 5 6 7 8 9 10 13 14 15 11 12 18 19 16 17 1 2 1 2 3 1 2 3 4 5 1 2 3 4 2 5 7 8 6 1 2 3 10 11 12 4 5 6 7...

Page 5: ...dicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or m...

Page 6: ...em will not work properly The indoor unit is for R 410A See the catalog for indoor mod els that can be connected Normal operation is not possible when connected to other units Remote controller wirele...

Page 7: ...nd the floor is flat to prevent vibration and noise generation 3 The piping length between the outside unit and the indoor unit may not exceed the allowable piping length Refer to 6 REFRIGERANT PIPING...

Page 8: ...to figure 6 The base should support the unit with the extent larger than hatched area in figure 7 If protective rubber is to be attached attach it to the whole face of the base The height of the base...

Page 9: ...e wiring 2 Removing Pinch Piping When connecting refrigerant piping to an outside unit remove the pinch piping using the procedure in the figure 11 Refer to figure 11 About handling of shutoff valves...

Page 10: ...ft Example 6 a b 540 ft 8 a m n p 540 ft Example 8 a o 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft that...

Page 11: ...it name BHFP26P90U 3 pipes KHRP25M33H KHRP25M72H 2 pipes KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C...

Page 12: ...2 Total length ft of liquid piping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ72 120PAYD REYQ72 120PATJ REYQ144 192PAYD REYQ144 1...

Page 13: ...terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and...

Page 14: ...BOX with the accessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as s...

Page 15: ...lve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop Needed tools The system for air tight test...

Page 16: ...etion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 29 Refer to figure 25 1 Insulation material 2 Caulking etc Refer to figure 26 1 Piping lead out hole lid 2 Open a knock ho...

Page 17: ...8 Lift the protruding part to open the inspection door Use an insulated rod to operate the push buttons via the EL COMPO BOX s inspection door There is a risk of electric shock if you touch any live p...

Page 18: ...he additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the figure 29 The valve A C and the liquid pipe suction gas pipe HP LP gas pipe equalizer pipe shutoff valve...

Page 19: ...f refrigerant state If the additional refrigerant is little and operation is started before getting stability the system can not judge the charging amount pre cisely and it cause over charge 4 If the...

Page 20: ...Use an insulated rod to operate the push buttons via the inspection door of EL COMPO BOX lid There is a risk of electric shock if you touch any live parts since this operation must be performed with t...

Page 21: ...ction of the refrigerant flow 2 room where refrigerant leak has occurred outflow of all the refrigerant from the system Pay a special attention to the place such as a basement etc where refrigerant ca...

Page 22: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 8M EM09A062A 1002 FS...

Reviews: