background image

14

English

CAUTION

Make sure to use the protect tool (protective groves and goggles) 
when charging the refrigerant.

Due to a danger of liquid hammer, the refrigerant must not be charged 
over the allowable maximum amount when charging the refrigerant.

Do not perform the refrigerant charging operation under working for 
the BS and indoor unit.

When opening the front panel, make sure to take caution to the fan rota-
tion during the working.
After the outside unit stops operating, the fan may keep rotation for a while.

NOTE

If operation is performed within 12 minutes after the BS, indoor and 
outside units are turned on, H2P will be lit on and the compressor will 
not operate.

Check the LED display indicate as shown below.

In order to ensure uniform refrigerant distribution, it may take up to 
around 10 minutes for the compressor to start up after the unit start-
ing operating. This is not a malfunction.

The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the unit’s internal piping is 
already charged with refrigerant, so be careful when connecting the 
charge hose.

After adding the refrigerant, make sure to close the lid of the refrig-
erant charging port.
The tightening torque for the lid is 8.48 to 10.3 ft · lbf.

See [Shutoff valve operation procedure] in chapter 11-1 for details 
on how to handle shutoff valves.

When done or when pausing the refrigerant charging operation, 
close the valve of the refrigerant tank immediately.
The refrigerant charge port of this product have electric expansion 
valve.
The valve will be closed at end of refrigerant charging. However the 
valve will be opened on operation after refrigerant charging (check 
operation, nomal operation, etc.).
If the tank is left with the valve open, the amount of refrigerant which 
is properly charged may be off the point.

Make sure to perform the check operation after installation. Other-
wise, the malfunction code “U3” will be displayed and normal opera-
tion cannot be performed.
And the failure of “Check of miswiring” may also cause abnormal 
operation. Performance may drop due to the failure of “Judgment of 
piping length”.

Check operation must be performed for each refrigerant piping system.
Checking is impossible if plural systems are being done at once.

The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation is 
completed. (See chapter 13)

The check operation cannot be performed in recovery or other ser-
vice modes.

11-2-1 Procedure of Adding Refrigerant charging
1.

Make sure the following works are complete in accordance with the 
installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Installation work for BS, indoor unit

2.

Calculate the “additional charging amount” using “How to calculate the 
additional refrigerant to be charged” in 

“6-5 Example of connection”

.

3.

Open the valve B (

See the figure 29

. The valve A,C and the liquid 

pipe, suction gas pipe, HP/LP gas pipe, equalizer pipe shutoff valves 
must be left closed), and charge the refrigerant of the “additional 
charging amount” from the liquid side shutout valve service port.

(Refer to figure 29)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

Refrigerant charge port

5.

HP/LP gas pipe shutoff valve

6.

Suction gas shutoff valve

7.

Liquid pipe shutoff valve

8.

Valve A

9.

Valve B

10.

Valve C

11.

Outside unit

12.

To BS, indoor unit

13.

Field pipings

14.

Refrigerant flow

15.

Shutoff valve

16.

Service port

4.

If the “additional charging amount” was charged fully, close the valve 
B and go to step 6.
If the “additional charging amount” was not charged fully, close the 
valve B and go to step 5.

5.

Perform the refrigerant charging following [Automatic refrigerant 
charging operation procedure] as shown below. And charge the 
remaining refrigerant of the “additional charging amount”.

NOTE

For performing the automatic refrigerant charging operation, the push 
button on the PC-bord (A1) of outside unit are used. (See figure 28.)
And the refrigerant are charged from the refrigerant charge port via 
the valve A. (See figure 30.) For operating the push button and open-
ing or closeing the valves, follow the procedure.

During Automatic refrigerant charging operation, the system will 
select charging mode (cooling mode or heating mode) by the tem-
perature condition as follows.

When charging in cooling mode, the system will stop operation when 
the required amount of refrigerant is charged.
During charging in heating mode, a person must manually close 
valve A and stop operation.
Beforehand, check the remaining refrigerant that is needed to 
charge based on the “additional charging amount” in step 2 and the 
charged amount in step 3.

The refrigerant will be charged about 66 lb in one  hour at outdoor 
temp. 86°F DB (about 26 lb at outdoor temp. 32°F DB).

During Automatic refrigerant charging operation, you can stop the 
operation forcedly by pushing MODE button (BS1).

(Refer to figure 30)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

Refrigerant charge port

5.

HP/LP gas pipe shutoff valve

6.

Suction pipe shutoff valve

7.

Liquid pipe shutoff valve

8.

Valve A

9.

Valve B

10.

Valve C

11.

Outside unit

12.

To BS, indoor unit

13.

Field pipings

14.

Refrigerant flow when charging

15.

Shutoff valve

16.

Service port

[Automatic refirgerant charging operation procedure]

NOTE

The marks of LED mean as follows.

h

 : OFF

i

 : ON

j

 : Blinking

 : OFF, ON or Brinking

(1) Open the liquid pipe, suction gas pipe and HP/LP gas pipe shutoff 

valves. (The valve A~C must be closed. See figure 30.)

(2)

Close the EL. COMPO. BOX (1) lid and all front panel except on the 
EL. COMPO. BOX (1) side. (*1) And turn the power to the outdoor 
unit and all connected BS, indoor units. (*2)

H1P H2P H3P H4P H5P H6P H7P

h

h

i

h

h

h

h

Outdoor temp. : 32˚F DB ~  109˚F DB
Indoor temp. :

50˚F DB ~  90˚F DB

Less than above range

Cooling mode

Heating mode

Summary of Contents for REYQ72PAYD

Page 1: ...INSTALLATION MANUAL System air conditioner English Fran ais Espa ol REYQ72PAYD REYQ96PAYD REYQ120PAYD REYQ72PATJ REYQ96PATJ REYQ120PATJ...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...2 B 1 2 1 2 3 4 5 6 1 1 2 3 4 3 4 7 8 2 9 6 5 1 4 3 2 1 2 3 TOIN DUNIT TOOUT DUNIT F1 F2 F1 F2 1 2 4 5 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 7 8 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F...

Page 4: ...ure 23 figure 26 figure 28 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 1 2 3 4 5 6 7 8 9 10 13 14 15 11 12 18 19 16 17 1 2 1 2 3 1 2 3 4 5 1 2 3 4 2 5 7 8 6 1 2 3 10 11 12 4 5 6 7...

Page 5: ...dicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or m...

Page 6: ...em will not work properly The indoor unit is for R 410A See the catalog for indoor mod els that can be connected Normal operation is not possible when connected to other units Remote controller wirele...

Page 7: ...nd the floor is flat to prevent vibration and noise generation 3 The piping length between the outside unit and the indoor unit may not exceed the allowable piping length Refer to 6 REFRIGERANT PIPING...

Page 8: ...to figure 6 The base should support the unit with the extent larger than hatched area in figure 7 If protective rubber is to be attached attach it to the whole face of the base The height of the base...

Page 9: ...e wiring 2 Removing Pinch Piping When connecting refrigerant piping to an outside unit remove the pinch piping using the procedure in the figure 11 Refer to figure 11 About handling of shutoff valves...

Page 10: ...ft Example 6 a b 540 ft 8 a m n p 540 ft Example 8 a o 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft that...

Page 11: ...it name BHFP26P90U 3 pipes KHRP25M33H KHRP25M72H 2 pipes KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C...

Page 12: ...2 Total length ft of liquid piping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ72 120PAYD REYQ72 120PATJ REYQ144 192PAYD REYQ144 1...

Page 13: ...terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and...

Page 14: ...BOX with the accessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as s...

Page 15: ...lve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop Needed tools The system for air tight test...

Page 16: ...etion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 29 Refer to figure 25 1 Insulation material 2 Caulking etc Refer to figure 26 1 Piping lead out hole lid 2 Open a knock ho...

Page 17: ...8 Lift the protruding part to open the inspection door Use an insulated rod to operate the push buttons via the EL COMPO BOX s inspection door There is a risk of electric shock if you touch any live p...

Page 18: ...he additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the figure 29 The valve A C and the liquid pipe suction gas pipe HP LP gas pipe equalizer pipe shutoff valve...

Page 19: ...f refrigerant state If the additional refrigerant is little and operation is started before getting stability the system can not judge the charging amount pre cisely and it cause over charge 4 If the...

Page 20: ...Use an insulated rod to operate the push buttons via the inspection door of EL COMPO BOX lid There is a risk of electric shock if you touch any live parts since this operation must be performed with t...

Page 21: ...ction of the refrigerant flow 2 room where refrigerant leak has occurred outflow of all the refrigerant from the system Pay a special attention to the place such as a basement etc where refrigerant ca...

Page 22: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 8M EM09A062A 1002 FS...

Reviews: