background image

English

15

After H2P stop blinking (about 12 minutes after turning on the 
power), check H2P is OFF.
If H2P is ON, check the malfunction code in the remote controller of 
indoor unit and correct the malfunction in accordance with [Remote 
controller display malfunction code] in chapter 11-2-2.

(3) Check the LED. And push the MODE button (BS1) once if the LED 

displays is not as below.

(4) Push the TEST button (BS4) once. (The LED displays will change as 

below.)

(5) Hold the TEST button (BS4) down for 5 seconds or more.

(The LED displays will change as below and fan of outside unit will 
start rotation.)

(6) When the compressor start working and the LED displays change 

any state in below (*3), go to “In case of cooling mode” or “In case of 
heating mode” in accordance with the LED displays.

In case of cooling mode

(7) Push the TEST button (BS4) once within 5 minutes after procedure 

(5) (*4) and close the all front panels (*5).
After that, open the valve A immediately (See figure 30) (*6) and 
watch the remote controller display of indoor unit.

(8) If the remote controller display shows “PE” code (*7), ready to close 

the valve A.
And go to procedure (9).
If the remote controller display shows other code, close the valve A 
immediately and refer to [Remote controller cooling mode malfunc-
tion code]

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(9) When the compressor stop working (the fan may continue rotation.), 

close the valve A immediately (*8).
And check the LED displays are as below and the remote controller 
display shows “P9” code.

After checking, push the MODE button (BS1) once and the charging 
is complete.

In case of heating mode

(7) Push the TEST button (BS4) once within 5 minutes after procedure 

(5) (*4) and close the all front panels.
After that, open the valve A immediately (See figure 30) (*6) and 
check the charged amount by meauring device.
During operation, if the remote controller display shows “P2” or “P8” 
code, close the valve A immediately and refer to [Remote controller 
heating mode malfunction code].

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(8) When the required amount of refrigerant is charged, close the valve 

A (See figure 30) (*8) and push the RETURN button (BS3) once. And 
then go to procedure (9).

(9) Push the MODE button (BS1) once, and the charging is complete.

Notes (*1)~(*9)

(*1) Lead the refrigerant charge hose etc from the pipe intake. 

All front panels must be closed at the procedure (7).

(*2)

If you perform the refrigerant charging operation within the refrig-
erant system that have the power off unit, the operation cannot fin-
ish properly.
Check the number of outside and indoor units that is powered.
For checking, see [How to check how many units are connected] 
in chapter 11-1.

To energize the crankcase heater, make sure to turn on for 
6 hours before starting operation.

(*3) It takes about 2~10 minutes for getting stability of refrigerant state.

If the additional refrigerant is little and operation is started before 
getting stability, the system can not judge the charging amount pre-
cisely and it cause over charge.

(*4) If the TEST button (BS4) is not pushed within 5 minutes, “P2” code 

will displayed in the remote controller. In this case, refer [Remote 
controller cooling (or heating) mode malfunction code].

(*5) If the front panel is opened during the operation, the system cannot 

operate properly.

(*6) If you leave the system without connecting the refrigerant tank or 

opening the valve A for 30 minutes or more, the system stop oper-
ation and “P2” code are displayed in remote controller.
In this case, refer [Remote controller cooling (or heating) mode mal-
function code].

(*7) Depending on the situation of operation such as the charging 

amount is little, the “PE” code may not be displayed and the “P9” 
code may be displayed.

(*8) Always close the valve A and take the tank off.

The refrigerant charge port of this unit have electric expansion valve 
and the valve are closed when charging is finished. However, the 
valve will opened when ather operation (Check operation, nomal 
operation, etc.). If you leave the tank connected, the refrigerant will 
charged and it cause over charge.

[Remote controller cooling mode malfunction code]

[Remote controller heating mode malfunction code]

H1P H2P H3P H4P H5P H6P H7P

h

h

i

h

h

h

h

H1P H2P H3P H4P H5P H6P H7P

i

i

i

i

i

i

i

H1P H2P H3P H4P H5P H6P H7P

h

j

h

h

h

H1P H2P H3P H4P H5P H6P H7P

j

j

j

h

i

h

i

Go to “In case of 
cooling mode”

j

j

h

h

i

h

i

Go to “In case of 
heating mode”

H1P H2P H3P H4P H5P H6P H7P

i

j

j

i

i

i

i

Code

The work contents

PE

Charging is almost finished. Ready to close the valve A.

PA

PH

The refrigerant tank is empty. Close the valve A and replace 
empty tank to the new tank. After changing the tank, open the 
valve A again.

Beware the fan running. The outside unit does not stop 
operation.

P8

Close the valve A immediately, and restart the operation from 
procedure (3).

P2

Operation is interrupted. Close the 
valve A immedeately and check the 
below items.

Check if HP/LP gas pipe, suction 
gas pipe or liquid pipe shutoff 
valve is opened.

Check the refrigerant tank is con-
nected and the valve A was opend.

Check if the air inlet and outlet of 
the indoor unit are not closed by 
an obstruction.

After correcting the 
abnormality, restart 
the operation from 
procedure (3).

Operation is stoped abnormally. Close 
the valve A immediately. Confirm the mal-
function code and correct the abnormality 
following the [Remote controller displays 
malfunction code] in chapter 11-2-2.

P9

Charging is finished. Close the valve A and take the refriger-
ant tank off.

Code

The work contents

P8

Close the valve A immediately and push the TEST button (BS4) 
once. And restart from procedure (7) of “In case of heating mode”.

P2

Operation is interrupted. Close the valve A immedeately and 
check the below items.

Check if HP/LP gas pipe, suction gas pipe or liquid pipe 
shutoff valve is opened.

Check the refrigerant tank is connected and the valve A 
was opend.

Check if the air inlet and outlet of the indoor unit are not 
closed by an obstruction.

Summary of Contents for REYQ72PAYD

Page 1: ...INSTALLATION MANUAL System air conditioner English Fran ais Espa ol REYQ72PAYD REYQ96PAYD REYQ120PAYD REYQ72PATJ REYQ96PATJ REYQ120PATJ...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...2 B 1 2 1 2 3 4 5 6 1 1 2 3 4 3 4 7 8 2 9 6 5 1 4 3 2 1 2 3 TOIN DUNIT TOOUT DUNIT F1 F2 F1 F2 1 2 4 5 A1P TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F1 F2 7 8 TOIN DUNIT F1 F2 F1 F2 TOOUT DUNIT F1 F2 F...

Page 4: ...ure 23 figure 26 figure 28 3 2 4 5 7 2 8 Part A Part B Part C 11 9 10 C A B 1 6 12 13 14 14 1 2 3 4 5 6 7 8 9 10 13 14 15 11 12 18 19 16 17 1 2 1 2 3 1 2 3 4 5 1 2 3 4 2 5 7 8 6 1 2 3 10 11 12 4 5 6 7...

Page 5: ...dicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or m...

Page 6: ...em will not work properly The indoor unit is for R 410A See the catalog for indoor mod els that can be connected Normal operation is not possible when connected to other units Remote controller wirele...

Page 7: ...nd the floor is flat to prevent vibration and noise generation 3 The piping length between the outside unit and the indoor unit may not exceed the allowable piping length Refer to 6 REFRIGERANT PIPING...

Page 8: ...to figure 6 The base should support the unit with the extent larger than hatched area in figure 7 If protective rubber is to be attached attach it to the whole face of the base The height of the base...

Page 9: ...e wiring 2 Removing Pinch Piping When connecting refrigerant piping to an outside unit remove the pinch piping using the procedure in the figure 11 Refer to figure 11 About handling of shutoff valves...

Page 10: ...ft Example 6 a b 540 ft 8 a m n p 540 ft Example 8 a o 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft that...

Page 11: ...it name BHFP26P90U 3 pipes KHRP25M33H KHRP25M72H 2 pipes KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Refrigerant branch kit name Example for indoor units connected downstream Example REFNET joint C...

Page 12: ...2 Total length ft of liquid piping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 1 02 HEAT RECOVER SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT REYQ72 120PAYD REYQ72 120PATJ REYQ144 192PAYD REYQ144 1...

Page 13: ...terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and...

Page 14: ...BOX with the accessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as s...

Page 15: ...lve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the insulation value to drop Needed tools The system for air tight test...

Page 16: ...etion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 29 Refer to figure 25 1 Insulation material 2 Caulking etc Refer to figure 26 1 Piping lead out hole lid 2 Open a knock ho...

Page 17: ...8 Lift the protruding part to open the inspection door Use an insulated rod to operate the push buttons via the EL COMPO BOX s inspection door There is a risk of electric shock if you touch any live p...

Page 18: ...he additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the figure 29 The valve A C and the liquid pipe suction gas pipe HP LP gas pipe equalizer pipe shutoff valve...

Page 19: ...f refrigerant state If the additional refrigerant is little and operation is started before getting stability the system can not judge the charging amount pre cisely and it cause over charge 4 If the...

Page 20: ...Use an insulated rod to operate the push buttons via the inspection door of EL COMPO BOX lid There is a risk of electric shock if you touch any live parts since this operation must be performed with t...

Page 21: ...ction of the refrigerant flow 2 room where refrigerant leak has occurred outflow of all the refrigerant from the system Pay a special attention to the place such as a basement etc where refrigerant ca...

Page 22: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 8M EM09A062A 1002 FS...

Reviews: