Options required for specific operating environments

High-efficiency filter

Available in two types: 65% and 90% colorimetry.

Using this kit, a 
duct can be fitted 
to increase the 
intake of outdoor 
air.

*Connecting ducts, insect nets, fire dampers, air filters, and other 

parts should, as required, be procured locally. 

**Outside Air fan interlocked with air conditioning unit is necessary. 

Optional PCB(KRP1C63)is required for interlocking.

***It is recommended that the volume of outdoor air introduced 

through the kit is limited to 10% of the maximum airflow rate of the 
indoor unit. Introducing higher quantities will increase the 
operating sound and may also influence temperature sending. 

Fresh air intake kit

Even in smoky environments where 
the air conditioning is on most of 
the time, the ultra long-life filter only 
has to be changed once a year.

Ultra long-life filter

Panel spacer

Use when only minimal space is available between drop 
ceilings and ceiling slabs.

Sealing material of air discharge outlet

Sealing material block air discharge openings not used in 
2-way or 3-way blow.

Branch duct

 (direct-connection round duct)

Outside

Note: Use of options will increase operating sound.

The units can be installed in the following different ways.

Note: Some ceiling constructions may hinder installation. 

Contact your Daikin Dealer before installing your unit.

Direct installation type

Flexible duct

T-joint pipe

Intake duct
(procured locally)
(duct length: 4 m max.)

Intake duct
(procured locally)
(duct length: 4 m max.)

Connection

chamber

Suction

chamber

 Duct flange
 (with insulation
  material)

 Intake duct
(procured locally)

Chamber type 

(with T-joint pipe and without fan)

Flexible duct
(procured locally)

T-joint pipe
(procured locally)

Chamber type 

(without T-joint pipe and fan)

KDDP55X160

KDDP55B160K

 

KDDP55B160

Easier to maintain

With Ultra long-life filters (option), maintenance is not required in normal shops or offices 
for up to four years. 

The condition of the drain pan and
drain water can be checked by
removing the drain plug and
intake grille.

Drain plug

Just open the 

intake grille!

40

mm

Panel spacer

A round duct can be attached without the need for a chamber.

A flanged port for direct connection of a round duct is 
provided. An existing branch duct chamber can also be fitted 
(square slit hole). 

Connection

chamber

Suction

chamber

Smoky atmosphere: annual filter change

Ordinary store or office: filter change every 4 years

*For dust concentration of 0.3 mg/m

3  

(Requires separately sold Air Cleaner.)

 1 year (Approx. 5,000 hr)    15 hr/day x 28 day/month x 12 month/year

*For dust concentration of 0.15 mg/m

 4 years (Approx. 10,000 hr)    8 hr/day x 25 day/month x 4 years

Note: 

Quick and easy to install

Just 256 mm high. Installable in tight 
ceiling spaces 

(13-26M)

Fine square panels

Compact body and quiet operation

*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. 
**Wireless remote controller does not have a temperature-sensor.

Note :  Anechoic chamber 
conversion value, measured 
according to JIS parameters 
and criteria. During 
operation these values are 
somewhat higher owing to 
ambient conditions.

Note: Air direction is set to the standard position when the unit is shipped from the factory. 
          The position can be changed from the remote controller.

Panel size is same for all models, FCNQ13-48M.
It is easy to maintain a neat appearance when 
multiple units are installed.

Optimal comfort and convenience 
assured by 2 air discharge modes

Both indoor unit and wired remote controller (option) contain temperature- 
sensors. Temperature sensing can be set at the unit or, to further improve 
comfort level, closer to the target area at the wired remote control. 

 

This 

feature must be set during commissioning by the technicians.

Two selectable temperature-sensors

Even in spaces with high ceilings, a comfortable airflow is carried down to 
the floor level.

Suitable for high ceilings

Operation starts when the preset time of the ON timer elapses and stops 
when the preset time of the OFF timer elapses.

On/Off timer

Indoor unit

High

Low

dB(A)

13/18M

31

28

21/26M

35

28

30/36M

43

32

42M

44

34

48M

44

36

Same for 

all models

Air direction

Auto air 
direction control

Settable to 5 different 
levels between 15° and 60°

Settable to 5 different 
levels between 25° and 60°

Auto-swing between
15° and 60°

Auto-swing between
25° and 60°

Recommended for shops with 

light coloured ceilings that 

must be kept spotless.

Standard position to 

prevent draft.

Standard setting

Setting to prevent soiling of ceiling

*

The air direction is set automatically to the 
memorised position of the previous air direction. 

Desired 
situation

Auto-swing

5-levels
air direction
setting 

*Closing of the corner discharge outlets is recommended.

Number of  air discharge outlets used

4-way

flow

3-way

flow

2-way

flow

4-way

flow

3-way

flow

2-way

flow

3.1 m
3.4 m
4.0 m

All round 

flow

2.7 m
3.0 m
3.5 m

3.0 m
3.3 m
3.5 m

3.5 m
3.8 m

-

3.4 m
3.9 m
4.5 m

All round 

flow

3.2 m
3.6 m
4.2 m

3.6 m
4.0 m
4.2 m

4.2 m
4.2 m

-

Standard

Ceiling 

height

High ceiling    

High ceiling    

Criteria for ceiling height and number of air discharge outlets

950 

mm

950 

mm

Note: Factory settings are for standard ceiling height and all-round flow. 
          High ceiling settings (1) and (2) are set with the remote controller by field setting.

256 mm 

*

1

266 mm 

*

2

*1 298 mm high with 30-48M
*2 308 mm high with 30-48M

All models can be installed without 
using lifter because of the light weight.

Drain pump is equipped as standard 
accessory with 850 mm lift.

Transparent drain socket

Each corner of the unit has an Adjuster Pocket that 
lets you easily adjust the unit's suspended height. 

Since the orientation of 
the intake grill can be 
adjusted after installing,
the direction of the intake 
grill lines can be unified 
when multiple units
are installed. 

Note: If the wireless remote control option is installed, a light receptor 

unit is housed in one of the adjuster pockets.

Easy height adjustment

Installable in 
any direction

Because the drain socket is 
transparent, after the drain piping 
has been installed, it is easy to 
check if the drain come out 
through the socket.

High setting provides maximum reach while low 
setting minimises drafts.

Switchable fan speed: High/Low

175 mm

850 mm

30-48M

13-26M

5

6

CEILING MOUNTED CASSETTE TYPE

Round Flow

(Ceiling height is reference value)

Connection to a centralised control 
system is available without option

Summary of Contents for PCSMT1420A

Page 1: ...ire or explosion Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and acces...

Page 2: ...YPE Round Flow Series Pair FCNQ18MV1 RNQ13MV1 FCNQ13MV1 FCNQ21MV1 FCNQ26MV1 RNQ26MY1 30 RNQ30MV1 FCNQ30MV1 RNQ30MY1 36 RNQ36MV1 RNQ26MV1 RNQ30MV1 RNQ36MV1 FCNQ36MV1 RNQ36MY1 42 RNQ42MY1 FCNQ42MV1 48 2...

Page 3: ...still obtain the same feeling temperature and comfort Operation sound increases when using 2 way or 3 way flow 1 4 6 Cleanliness Comfort Work Servicing Control features Others Options Features Access...

Page 4: ...t higher owing to ambient conditions Note Air direction is set to the standard position when the unit is shipped from the factory The position can be changed from the remote controller Panel size is s...

Page 5: ...ide as was formerly the case The unit fits more snugly into tight spaces Flexible installation Uniform height and depth Compact design for small capacity models to meet tighter dimensional constraints...

Page 6: ...e sensors Remote controller 2 2 2 2 3 Setpoint range set Weekly schedule timer Setpoint auto reset Off timer programmed On Off timer 1 6 Comfort Work Servicing Control features Others Features 1 Appli...

Page 7: ...s DCS301BA61 Option Schedule timer Unified control of weekly schedule for up to 1 024 indoor units DST301BA61 Option Schedule timer sets on off time in 1 minute units to be executed twice a day for a...

Page 8: ...set as holiday 3 independent schedules can be set e g summer winter mid season Display is available in 11 languages Dot matrix display Backlight display Convenience Weekly schedule Multilingual displ...

Page 9: ...te Others To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution coated Anti corrosion treated heat exchangers with special acryl pretreatment are used for...

Page 10: ...42 000 4 51 2 73 48 FHNQ48MV1 RNQ42MY1 RNQ48MY1 14 1 48 000 5 51 2 56 42 44 24 26 1 483 1 553 847 918 3 Phase 380 415 V 50 Hz Outdoor unit Outdoor unit Cooling capacity1 2 kW Y1 V1 Y1 V1 kW Power cons...

Page 11: ...air intake kit Chamber type 1 2 High efficiency filter2 High humidity operation kit Ultra long life filter2 19 20 Indoor unit Indoor unit OPTIONS Outdoor unit Kit name RNQ18MV1 RNQ21MV1 RNQ09MV1 RNQ13...

Page 12: ...e ceiling opening keep the clearance of 35mm or less between the indoor unit and the ceiling opening so that the panel overlap allowance can be ensured 5 Please do not place the thing been damp and tr...

Page 13: ...pension bracket 5 6 7 8 300 or more 7 P150 1050 263 151 20 M4 Holes 51 1350 1137 16 1121 8 10 305 All Around 16 150 74 280 1153 7 5 6 4 1114 1134 1 29 50 123 18 M4 Holes 152 206 274 175 2 305 All Arou...

Page 14: ...IMENSIONS Unit mm Gas pipe connection Liquid pipe connection Service port Grounding terminal Refrigerant piping intake Power supply wiring intake Control wiring intake Drain pipe connection 1 2 3 4 5...

Page 15: ...sed body embedded cord Conduit CONTROL BOX Through hole Size Specifications of cord 0 75 1 25 mm2 Total length 500 m Type Vinyl cord with sheath or cable Insulated thickness 1 mm or more Note 1 Remote...

Page 16: ...29 30 MEMO...