2-23
(4) Defrosting termination
Defrosting will be terminated when any one of the following three conditions is satisfied.
q
The below figure is satisfied during defrost.
※
Only out of range conditions in case of chilled operation
w
When the backup timer has counted up 90 minutes
e
Any one of protective devices is activated.
Operation mode Status before defrost
Termination
Out of RANGE
Chilled mode
INRANGE
Out of RANGE
INRANGE
Frozen mode
EOS
≧
30.0˚C
EOS
≧
30.0˚C
&
RS
≧
15˚C
&
DRS
≧
15˚C