2.5 Operation modes and control
There are two main types of operation modes: the cargo cooling control mode and the unit
inspection mode.
The cargo cooling control mode is explained in this section.
※
For the unit inspection mode, refer to section 3.9.
The relationship between the operation mode and setting temperature is as follows.
※
For details, refer to clause 2.5.1 to 2.5.4
Mode selection Operation mode Setting temperature
Control sensor
Inside fan
Operation description
Mode selection
Chilled mode
–9.9˚C to +30.0˚C
(–14.1˚F to +86.0˚F)
Supply air
temperature
sensor
High speed
Capacity control
operation with suction
modulating valve and
hot-gas bypass control
Frozen mode
–30.0˚C to –10.0˚C
(–22.0˚F to +14.0˚F)
Return air
temperature
sensor
Low speed
Compressor
ON/OFF control
Defrosting mode
-
-
OFF
Hot-gas defrosting with
refrigerant quantity
control