
4-9
(2) Removal of compressor
Recover
refrigerant
Disconnect
cables and
mounting bolts
Disconnect
pipings
1. Recover the refrigerant from service port
r
on discharge line
and
t
at receiver/water cooled condenser outlet.
(Refer to the clause 4.1.4 Refrigerant Recovery and charge)
2. Close the discharge and suction side stop valves on the
compressor.
3. Switch off the power.
4. Open the terminal box cover and disconnect the cables.
5. Remove the mounting bolts.
6. Remove the flare nuts for the injection piping on the compressor
head and gauge piping on the body.
7. Remove the insulation tape fixed on suction flange and discharge
flange.
8. Remove the bolts for suction and discharge flange.
Attention !
Use double wrenches
when the flare nuts
are removed.
Compressor
Injection
piping
Gauge
piping
(3) Installation of compressor
Connect
pipings and
fix mounting
bolts
1. Before connecting pipings, insert and
screw in the mounting bolts slightly.
2. Tighten the flare nuts for the injection
piping and gauge piping on the body.
3. Fix the suction and discharge flanges
using with the auxiliary gaskets and the
bolts.
4. Tighten the mounting bolts.
Tightening torque
257 Kgf.cm (25.2 N.m)
435 Kgf.cm (42.7 N.m)
Attention !
Use double wrenches
when the flare nuts
are tightened.
Tightening
torque:
370 Kgf.cm
(36.3 N.m)
160 Kgf.cm
(15.7 N.m)
Compressor
04̲LXE10E100以降(08-26)̲E.qx 08.8.27 5:04 PM ページ 4-9
https://daikin-p.ru