4-16
(3) Replacement procedure
(2-3) Removal of mounting plate
Check the following table to see if the mounting plate should be removed. If the mounting plate must
be removed, remove the four screws and dismount the mounting plate.
Over current setting and removal of mounting plate
Model
Spare parts
LXE5C
LXE10C
LXE10D
LXE10D
LXE10E
Type
–––––
Dual 5HP
Dual 10HP
Single 10HP
Over current setting value
–––––
8.5A
15A
26A
Jumpers
J3
J2
J1
Mounting plate
Provided
Not to be
removed
Not to be
removed
To be
removed
To be removed
: Cut jumper
: Do not cut jumper
q
Disconnect the wires routed via CT1 and CT2
from the terminals.
※
At this time, take care to prevent CT1 and
CT2 from being damaged.
w
Disconnect the connector (CN1) for the
controller and the connector (CN2) for the
main circuit.
e
Remove four mounting nuts.
r
After replacing the PT and CT board, connect
the lead wired in reverse order of the above
removal procedure.
t
After checking the wiring once, test-run the
system to verify that no trouble is found.
CAUTION
Be sure that the main power is
disconnected.