Even in water-cooled operation, there may be cases
where the condenser fan operates.
CAUTION
※
1 If the shortage of cooling water is caused in water-cooled operation, the condensing pressure will
increase, thus activating the high pressure switch. In order to prevent this event, operate the
condenser fan so that the condensing pressure will not increase in excess of a high-pressure
(HPT) set point. When the high pressure falls below the set point, the condenser fan will stop
running.
※
2 If ambient temperature is high, a temperature in the control box will increase. If this temperature
exceeds a value set with the control box thermostat (CBS), the condenser fan will start running
to cool the control box.
HPT
>
2350 kPa or (EOS
−
EIS)
>
30
°
C except water-cooling operation
HPT
<
2150 kPa & EOS
−
EIS
<
20
°
C
ON
OFF
CBS
>
59
°
C
CBS
<
49
°
C
ON
OFF