2-22
2.5.4 Dehumidification
※
If reheat coil and humidity sensor (Optional) is equipped:
The unit have dehumidification control by a reheat coil, which is under the evaporator coil. To execute
dehumidification, controller setting is required. (Refer to Page 3-12)
In dehumidification, the Reheat Solenoid Valve (RSV)/Capillary Solenoid Valve (CSV) opens to give
high pressurized refrigerant to reheat coil. The "DEHUMID" LED lamp will light up.
The following setting can be made:
1) Dehumidification range: 30%RH–95%RH