4-10
(2) Removal of compressor
Recover
refrigerant
Disconnect
cables and
mounting bolts
Disconnect
pipings
1. Recover the refrigerant from service port
r
on discharge line
and
t
at receiver/water cooled condenser outlet.
(Refer to the section 4.1.4 Refrigerant Recovery and charge)
2. Close the discharge and suction side stop valves on the
compressor.
3. Switch off the power.
4. Open the terminal box cover and disconnect the cables.
5. Remove the mounting bolts.
6. Remove the flare nuts for the injection piping on the compress
head and gauge piping on the body.
7. Remove the insulation tape fixed on suction flange and discha
flange.
8. Remove the bolts for suction and discharge flange.
Attention !
Use double wrenches
when the flare nuts
are removed.
Compressor
Injection
piping
Gauge
piping
https://daikin-p.ru