State
Malfunction occurrence
Abnormal point
Possible cause
C. Condenser fan rotates,
q
Activation of
Short circuit of condenser fan motor
but evaporator fan and
high-pressure switch
Wrong installation of condenser fan
compressor do not
(Water cooled
Reverse rotation of condenser fan
rotate.
condenser type)
Insufficient cooling water flow rate
Water-cooled condenser blocked with scale
w
Overcurrent due to overload operation, etc.
e
Abnormal low
Electronic expansion valve: poor contact of connector
pressure drop
Electronic expansion valve: incorrect opening
Electronic expansion valve: blocked
Suction modulating valve: blocked
Dryer: blocked
r
Abnormal discharge
Hot gas solenoid valve: coil wire broken
gas temperature
Injection solenoid valve: closed
Injection capillary tube: blocked
High pressure increasing due to overload
A. Suction pressure is
q
Poor compression of compressor
Abrasion of scroll slide section
high
w
Hot gas solenoid valve Valve leakage
e
Defrosting solenoid valve
Valve leakage
r
Discharge gas
Valve leakage
by-pass solenoid valve
t
Electronic expansion valve Electronic expansion valve malfunction
Poor contact of connector
y
Injection solenoid valve Valve leakage
B. Suction pressure is
q
Liquid solenoid valve (Not opened) Solenoid valve coil malfunction
excessively low
w
Shortage of refrigerant charge Refrigerant leakage
e
Drier
Drier blocked with contamination
r
Suction modulating valve Coil wire breakage
Disconnection of connector
t
Electronic expansion valve Valve blocked with moisture
Valve blocked with contamination
Breakage of coil lead wire or disconnection of connector
Lead wire breakage or miss-mounting of evaporator inlet or outlet sensor
Electronic expansion valve malfunction
y
Evaporator
Abnormal frosting
Insufficient air flow rate in the evaporator
Air passage blocked by foreign material
Evaporator fan motor malfunction
Evaporator fan damage or fall out
Air short circuit around the evaporator
Reverse rotation of evaporator fan motor
C. Economizer circuit
Economizer solenoid valve
Solenoid valve coil malfunction
does not function
Valve blocked with contamination
Thermostatic expansion valve is choked with moisture
Thermostatic expansion valve is clogged with contamination
Gas in the feeler bulb of thermostatic expansion valve is leaked
D. Defrosting is not
q
Manual defrost key
Poor contact of connector
initiated.
w
Evaporator outlet sensor Incorrect installation of sensor
e
Defrosting solenoid valve Valve blocked with contamination
Valve coil malfunction
r
No trouble with unit
Defrost interval is set to 99 H
(Demand/defrost setting)