<< No. 3 system: When BS unit is used >>

WARNING

Be sure to install an earth leakage breaker.
Failure to do so may cause electric shocks and a fire.

8-6

FOR CONTROL WITH 2 REMOTE CONTROL-
LERS (TO CONTROL 1 INDOOR UNIT WITH
2 REMOTE CONTROLLERS)

For control with 2 remote controllers, set one remote control-
ler as Main and the other remote controller as Sub.

<Changeover method from Main to Sub and vice versa>

Refer to the installation manual attached to the remote 
controller.

<Wiring method>

(1) Remove the control box lid according to the wiring connec-

tion method.

(2) Carry out additional wiring from the remote controller 2 

(Sub) to the terminals (P

1

, P

2

) for remote controller wiring 

on the terminal block (X1M) in the control box.

< CAUTION >

When using the group control and the 2 remote controllers 
control at the same time, connect the remote controller 2 (Sub) 
to the indoor unit at the end of the crossover wiring (the largest 
No.). 

(Refer to Fig. 34)

8-7

FOR CENTRALIZED CONTROL

When centralized equipment (such as centralized controller) 
is used for control, it is required to set the group No. on the 
remote controller.
For details, refer to the manuals attached to the centralized 
equipment.

Connect the centralized equipment to the indoor unit con-
nected to the remote controller.

8-8

FOR REMOTE CONTROL (FORCED OFF OR 
ON/OFF OPERATION) 

(1) Wiring method and specification

Remote control is available by transmission the external 
input to the terminals T1 and T2 on the terminal block for 
remote controller and transmission wiring.

(2) Actuation

Input A of FORCED OFF and ON/OFF OPERATION will 
be as the table shown below.

(3) How to choose FORCED OFF or ON/OFF OPERATION

For choosing FORCED OFF or ON/OFF OPERATION, 
setting by remote controller is required.
(Refer to 

10. FIELD SETTING AND TEST OPERATION

)

Outdoor unit

BS unit

L

N

Indoor unit A

Remote controller
(option)

F2

F1

F2

F1

F2

F1

F2

F1

IN/D

IN/D

OUT/D

OUT/D

P2

P1

F2

N

F1

L

T1T2

P1P2

Power supply

220-240V/220V

1 ~

50Hz/60Hz

Remote controller 1
(Main)

Remote controller 2
(Sub)

Terminal for remote 
controller wiring

Fig. 33

P

1

P

2

Wiring specification

Sheathed vinyl cord or 2 core cable

Wiring size

0.75-1.25mm

2

Wiring length

Max. 100m

External contact spec

Contact that can make and break the min. 
load of DC15V · 1mA

In case of 

FORCED 

OFF

FORCED OFF by input A of 

“ON” 

(Remote controller prohibited)

Remote controller 

permitted by input A 

of “OFF”

In case of ON/

OFF OPERA-

TION

Operation by input A of “OFF” 

 “ON”

Stop by input A of 

“ON” 

 “OFF”

Remote controller 1 (Main)

Remote controller 2 (Sub)

Crossover wiring (Remote controller)

Indoor unit 1

Indoor unit 2

Indoor unit largest No.

Fig. 34

F2

T1

FORCED 
OFF

T2

Input A

01_EN_3P368557-2D.fm  Page 14  Wednesday, February 13, 2019  2:46 PM

Summary of Contents for FXHQ32AVEB9

Page 1: ...ONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO LEES DEZE INSTRUCTIES ZOG...

Page 2: ...parts may result in the air conditioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result...

Page 3: ...al attached to the outdoor unit Do not throw away the accessories until the installation work is completed After the indoor unit is carried into the room to avoid the indoor unit from getting damaged...

Page 4: ...d out Water leakage Does the drain flow out smoothly Water leakage Is the power supply volt age identical to that stated in the manufac turer s label on the air conditioner Does not operate burnout Ar...

Page 5: ...TION 1 For the locations of indoor unit hanging bolts piping outlet holes drain piping outlet hole and electric wiring inlet hole Refer to Fig 3 2 Make holes for hanging bolts piping outlet drain pip...

Page 6: ...Use M8 or M10 bolts for hanging the indoor unit Adjust the length of the hanging bolt from the ceiling in advance Refer to Fig 9 Use hole in anchors for the existing bolts and embedded inserts or foun...

Page 7: ...mass If the strength is insufficient the indoor unit may fall down and cause injuries 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to th...

Page 8: ...ck securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in malfunction such as does not cool or heat Table 2 CAUTION Insulation of...

Page 9: ...eave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material eld supply For prevention of sweating...

Page 10: ...left side refer to Fig 21 When conducting left rear left side drain piping remove the protection net Then remove the drain socket cap and insu lation material applied to left side drain socket and ap...

Page 11: ...nical document Connecting drain piping Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain piping and corrode the heat...

Page 12: ...the works are finished Carry out installation and wiring of the remote controller according to the installation manual attached to the remote controller Do not touch the Printed Circuit Board assembly...

Page 13: ...nnect the remote con troller wiring to P1 P2 and transmission wiring to F1 F2 no polarity Refer to Fig 32 Next tie into a bundle and fix by the included the wiring fixture 11 and clamp 4 so that no te...

Page 14: ...Remote controller wiring Clamp 4 accessory Power supply wiring and Earth wiring Wiring xture 11 accessory Screw for wiring xture 12 accessory Wiring xture 11 accessory Screw for wiring xture 12 acces...

Page 15: ...e remote controller 8 8 FOR REMOTE CONTROL FORCED OFF OR ON OFF OPERATION 1 Wiring method and specification Remote control is available by transmission the external input to the terminals T1 and T2 on...

Page 16: ...er with the operation manual Do not carry out setting other than those shown in the table 10 1 SETTING OF CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 3...

Page 17: ...est operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In addition explain the power supply sta...

Page 18: ...B SELECTOR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN A...

Page 19: ...1904 HT 3P368557 2D EM12A009D 00_CV_3P368557 2D fm Page 2 Tuesday February 12 2019 10 56 AM...

Reviews: