English
4
NOTE
NOTE
NOTE
NOTE
•
If there is extra space required for * part, servicing can be
conducted more easily if 200mm or more is secured.
CAUTION
•
Install the indoor and outdoor units, power supply wiring,
remote controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image inter-
ference or noise. (Depending on the radio waves, a distance
of 1 meter may not be sufficient to eliminate the noise.)
•
Install the indoor unit as far as possible from fluorescent
lamps. If a wireless remote controller kit is installed, the
transmission distance may be shorter in a room where an
electronic lighting type (inverter or rapid start type) fluores-
cent lamp is installed.
(2) Use hanging bolts for installation.
Investigate if the installation place can withstand the mass
of the indoor unit and, if necessary, hang the indoor unit
with bolts after it is reinforced by beams etc. (Refer to the
installation pattern paper (5) for the mounting pitch.)
(3) Ceiling height
This indoor unit can be installed up to 4.3m (for 32·63
model, 3.5m) of the ceiling.
4.
PREPARATION BEFORE INSTALLA-
TION
(1) For the locations of indoor unit hanging bolts, piping
outlet holes, drain piping outlet hole, and electric
wiring inlet hole. (Refer to Fig. 3)
(2) Make holes for hanging bolts, piping outlet, drain pip-
ing outlet and electric wiring inlet.
•
Use the installation pattern paper (5).
•
Determine the locations of hanging bolts, piping outlet,
drain piping outlet, and electric wiring inlet. And make the
hole.
*30 or more
*30 or more
Fig. 1
Discharge
300
or more
2500 or more
from floor level
Floor level
Obstacles
Suction
Required installation space (mm)
For high installation
Fig. 2
Model name
(FXHQ-)
A
B
C
D
E
F
G
H
J
Type 32
960 920
378 324 270 375
398 377 260
Type 63
1270 1230 533 479 425 530
553 532 415
Type 100
1590 1550 693 639 585 690
713 692 575
Fig. 3
F
690 Unit dimension
210
D
C
A Unit dimension
B Hanging bolt pitch
View from the ceiling
G
H
J
260
30
5
175
200
163
E
189
87
View from the front
Left back drain
piping outlet hole
Wall hole for back side
piping outlet
(
φ
100 hole)
Back side wiring
outlet location
Discharge
Unit : mm
Top panel drain
piping connection
position
Top panel gas side
piping connection
position
Top panel liquid side piping
connection positions
Top panel wiring outlet position
Hanging bolt (4 pieces)
Hanging bolt pitch
01_EN_3P368557-2D.fm Page 4 Wednesday, February 13, 2019 2:46 PM