background image

9

English

Before brazing refrigerant piping, have nitrogen flow through 
the refrigerant piping and substitute air with nitrogen. Then, 
carry out brazing (NOTE 2). 

(Refer to Fig. 20)

 After all the 

brazing works are finished, carry out flare connection with the 
indoor unit.

NOTE

NOTE

NOTE

NOTE

1.

The proper pressure for having nitrogen flow through the 
piping is approximately 0.02MPa, a pressure that makes 
one feel like breeze and can be obtained through a pressure 
reducing valve.

2.

Do not use flux when brazing refrigerant piping. Use phos-
phor copper brazing filler metal (BCuP-2: JIS Z 3264/B-
Cu93P-710/795: ISO 3677) that does not require flux. (If 
chlorinated flux is used, the piping will be corroded and, in 
addition if fluorine is contained, the refrigerant oil will be 
deteriorated and the refrigerant circuit will be affected 
badly.)

3.

When carrying out leakage test of refrigerant piping and the 
indoor unit after the installation of indoor unit is finished, 
confirm the connecting outdoor unit installation manual for 
test pressure.
Refer to also the outdoor unit installation manual or techni-
cal document for refrigerant piping.

4.

In case of refrigerant shortage due to forgetting additional 
refrigerant charge etc., it will result in malfunction such as 
does not cool or does not heat. Refer to the outdoor unit 
installation manual or technical document for refrigerant 
piping.

CAUTION

Do not use antioxidant when brazing piping.

 

It may result in malfunction of components and clogging of 
piping due to residue.

7.

DRAIN PIPING WORK

(1) Carry out drain piping.

Carry out drain piping so that drainage can ensured.

Drain piping can be connected from the following directions: 
For right rear/right side, refer to 

Fig. 18

 of 

“6. REFRIGERANT PIPING WORK”

, and for left rear/left 

side, refer to 

Fig. 21

.

When conducting left rear/left side drain piping, remove the 
protection net. Then, remove the drain socket cap and insu-
lation material applied to left side drain socket and apply 
them to the right side drain socket. 
When doing this, insert the drain socket cap all the way in to 
prevent a water leakage.
After the drain hose (1) (accessory) installing, attach the pro-
tection net by reversing the steps taken to remove it. 

(Refer to Fig. 22)

Select the piping diameter equal to or larger than that of the 
drain hose (1) (accessory) (polyvinyl chloride piping, nominal 
diameter 20mm, outside diameter 26mm). 

Install the drain piping as short as possible with downward 
inclination of 1/100 or more and without where air may stag-
nate. 

(Refer to Fig. 23 and 24)

(It may cause abnormal sound such as bubbling noise)

CAUTION

If drain stagnates in the drain piping, the piping may be 
clogged.

Make sure to use the attached drain hose (1) and metal 
clamp (2). Also, insert the drain hose (1) into the root of the 
drain socket, and tighten the metal clamp (2) at the root of the 
drain socket tightly. 

(Refer to Fig. 25 and 26)

(Install the metal clamp (2) so that the tightening part is in the 
range of about 45°as shown in the 

Fig. 26

.)

(Do not bond the drain socket and drain hose. If so, mainte-
nance and inspection for the heat exchanger and others can-
not be conducted.)

CAUTION

If an old drain hose or an elbow or a clamp is used, it may 
cause water leakage. 

Pressure reducing valve

Brazing place

Taping

Stop valve

Nitrogen

Nitrogen

Refrigerant piping

Fig. 20

Back side (sheet metal)
Detach parts

Putty or insulation
(field supply)

Left side
Drain piping

Left side
Detach parts

Left rear side
Drain piping

Fig. 21

Protection net

Fixing 
screw for
protection net

Fig. 22

Good

Wrong

Supports

1-1.5m

Downward inclination 
of 1/100 or more

Do not lift

Make sure there 
is no slack

Make sure it is 
not in the water

Fig. 23

Fig. 24

01_EN_3P368557-2D.fm  Page 9  Wednesday, February 13, 2019  2:46 PM

Summary of Contents for FXHQ32AVEB9

Page 1: ...ONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO LEES DEZE INSTRUCTIES ZOG...

Page 2: ...parts may result in the air conditioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result...

Page 3: ...al attached to the outdoor unit Do not throw away the accessories until the installation work is completed After the indoor unit is carried into the room to avoid the indoor unit from getting damaged...

Page 4: ...d out Water leakage Does the drain flow out smoothly Water leakage Is the power supply volt age identical to that stated in the manufac turer s label on the air conditioner Does not operate burnout Ar...

Page 5: ...TION 1 For the locations of indoor unit hanging bolts piping outlet holes drain piping outlet hole and electric wiring inlet hole Refer to Fig 3 2 Make holes for hanging bolts piping outlet drain pip...

Page 6: ...Use M8 or M10 bolts for hanging the indoor unit Adjust the length of the hanging bolt from the ceiling in advance Refer to Fig 9 Use hole in anchors for the existing bolts and embedded inserts or foun...

Page 7: ...mass If the strength is insufficient the indoor unit may fall down and cause injuries 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to th...

Page 8: ...ck securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in malfunction such as does not cool or heat Table 2 CAUTION Insulation of...

Page 9: ...eave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material eld supply For prevention of sweating...

Page 10: ...left side refer to Fig 21 When conducting left rear left side drain piping remove the protection net Then remove the drain socket cap and insu lation material applied to left side drain socket and ap...

Page 11: ...nical document Connecting drain piping Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain piping and corrode the heat...

Page 12: ...the works are finished Carry out installation and wiring of the remote controller according to the installation manual attached to the remote controller Do not touch the Printed Circuit Board assembly...

Page 13: ...nnect the remote con troller wiring to P1 P2 and transmission wiring to F1 F2 no polarity Refer to Fig 32 Next tie into a bundle and fix by the included the wiring fixture 11 and clamp 4 so that no te...

Page 14: ...Remote controller wiring Clamp 4 accessory Power supply wiring and Earth wiring Wiring xture 11 accessory Screw for wiring xture 12 accessory Wiring xture 11 accessory Screw for wiring xture 12 acces...

Page 15: ...e remote controller 8 8 FOR REMOTE CONTROL FORCED OFF OR ON OFF OPERATION 1 Wiring method and specification Remote control is available by transmission the external input to the terminals T1 and T2 on...

Page 16: ...er with the operation manual Do not carry out setting other than those shown in the table 10 1 SETTING OF CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 3...

Page 17: ...est operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In addition explain the power supply sta...

Page 18: ...B SELECTOR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN A...

Page 19: ...1904 HT 3P368557 2D EM12A009D 00_CV_3P368557 2D fm Page 2 Tuesday February 12 2019 10 56 AM...

Reviews: