(Abnormal heating may occur if the wirings are not tightened 
securely.)

Use the required wirings, connect them securely and fix 
these wirings so that external force may not apply to the ter-
minals.

Use a proper screw driver for tightening the terminal screws. 
If an improper screw driver is used, it may damage the screw 
head and a proper tightening cannot be carried out. 

If a terminal is over tightened, it may be damaged. Refer to 
the table shown below for tightening torque of terminals.

Conduct wiring so that the earth lead comes out from the 
notched part of the cup washer. (Otherwise, earth lead con-
tact will be insufficient and grounding effect may be lost.)    

Do not carry out soldering finish when stranded wirings are 
used.

<Power supply wiring • earth wiring • remote controller wir-
ing • transmission wiring connecting method>

(1) Hold the control box, loosen the fixing screws (2 pieces) 

and remove the control box lid 

(Refer to Fig. 31)

.

(2) Open the knockout hole and put the resin bushing (10) 

(accessory) on the rear or top side (sheet metal).

(3) Pull the power supply wiring through the penetration hole 

and connect to the terminal block for power supply (X2M; 
dipoles) 

(Refer to Fig. 31)

. Connect the earth wiring to the 

earth terminal. Next, tie into a bundle and fix by the 
attached the wiring fixture (11) and clamp (4) so that no ten-
sion will be given to the wiring. 

(Refer to Fig. 32)

(4) Pull the remote controller wiring and transmission wiring 

through the penetration hole, and connect the remote con-
troller wiring to [P1·P2] and transmission wiring to [F1·F2] 
(no polarity) 

(Refer to Fig. 32)

. Next, tie into a bundle and 

fix by the included the wiring fixture (11) and clamp (4) so 
that no tension will be given to the wiring transmission part. 

(Refer to Fig. 32)

WARNING

When wiring, form the wirings orderly so that the control 
box lid can be securely fastened. If the control box lid is not 
in place, the wirings may float up or be sandwiched by the 
box and the lid and cause electric shocks or a fire.

Tightening torque 

(N·m)

Terminal block for remote controller and trans-
mission wirings

0.88±0.08

Terminal block for power supply

1.47±0.14

Earth terminal

1.69±0.25

Connection of 2 
wirings of same size 
must be carried out 
on both sides.

Connection of 
wirings of different 
sizes is prohibited.

Connection of 2 
wirings on one side 
is prohibited.

Notched part

Ring type crimp style terminal

Cup washer

L

N

Terminal block for remote 
controller / transmission 
wiring (X1M)

R10 or more

R10 
or more

Remote controller wiring
(no polarity)

<Low voltage wiring connection method>

Printed Circuit Board

• Do not carry out 
 soldering finish.

• Do not carry out soldering finish.

Terminal block for power supply (X2M)

Earth terminal

Earth wiring

Power supply wiring

<High voltage wiring connection method>

Wiring penetration 
hole

Rear piping 
penetration cover

Remote controller 
and transmission 
wiring

Wiring diagram Label

Control box lid

Control box lid
fixing screws (2 pieces)

Power supply 
wiring and earth wiring

Transmission wiring 
(no polarity)

Control 
box

Forbidden

Never connect the 
power supply wiring.

(Refer to Fig. 32)

Fig. 31

01_EN_3P368557-2D.fm  Page 12  Wednesday, February 13, 2019  2:46 PM

Summary of Contents for FXHQ32AVEB9

Page 1: ...ONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO LEES DEZE INSTRUCTIES ZOG...

Page 2: ...parts may result in the air conditioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result...

Page 3: ...al attached to the outdoor unit Do not throw away the accessories until the installation work is completed After the indoor unit is carried into the room to avoid the indoor unit from getting damaged...

Page 4: ...d out Water leakage Does the drain flow out smoothly Water leakage Is the power supply volt age identical to that stated in the manufac turer s label on the air conditioner Does not operate burnout Ar...

Page 5: ...TION 1 For the locations of indoor unit hanging bolts piping outlet holes drain piping outlet hole and electric wiring inlet hole Refer to Fig 3 2 Make holes for hanging bolts piping outlet drain pip...

Page 6: ...Use M8 or M10 bolts for hanging the indoor unit Adjust the length of the hanging bolt from the ceiling in advance Refer to Fig 9 Use hole in anchors for the existing bolts and embedded inserts or foun...

Page 7: ...mass If the strength is insufficient the indoor unit may fall down and cause injuries 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to th...

Page 8: ...ck securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in malfunction such as does not cool or heat Table 2 CAUTION Insulation of...

Page 9: ...eave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material eld supply For prevention of sweating...

Page 10: ...left side refer to Fig 21 When conducting left rear left side drain piping remove the protection net Then remove the drain socket cap and insu lation material applied to left side drain socket and ap...

Page 11: ...nical document Connecting drain piping Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain piping and corrode the heat...

Page 12: ...the works are finished Carry out installation and wiring of the remote controller according to the installation manual attached to the remote controller Do not touch the Printed Circuit Board assembly...

Page 13: ...nnect the remote con troller wiring to P1 P2 and transmission wiring to F1 F2 no polarity Refer to Fig 32 Next tie into a bundle and fix by the included the wiring fixture 11 and clamp 4 so that no te...

Page 14: ...Remote controller wiring Clamp 4 accessory Power supply wiring and Earth wiring Wiring xture 11 accessory Screw for wiring xture 12 accessory Wiring xture 11 accessory Screw for wiring xture 12 acces...

Page 15: ...e remote controller 8 8 FOR REMOTE CONTROL FORCED OFF OR ON OFF OPERATION 1 Wiring method and specification Remote control is available by transmission the external input to the terminals T1 and T2 on...

Page 16: ...er with the operation manual Do not carry out setting other than those shown in the table 10 1 SETTING OF CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 3...

Page 17: ...est operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In addition explain the power supply sta...

Page 18: ...B SELECTOR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN A...

Page 19: ...1904 HT 3P368557 2D EM12A009D 00_CV_3P368557 2D fm Page 2 Tuesday February 12 2019 10 56 AM...

Reviews: