background image

7

English

Do not mix substance other than the specified refriger-
ant such as air into the refrigeration circuit.
If the refrigerant leaks during the work, ventilate the 
room.

• Remove the stay for packing and delivering (reinforcing 

plate) before refrigerant piping work. 

(Refer to Fig. 18)

• The refrigerant is pre-charged in the outdoor unit.
• When connecting the pipings to the air conditioner, make 

sure to use a spanner and a torque wrench as shown in 

Fig. 

13

.

For the dimension of flared part, refer to the Table 1.

When making a flare connection, coat the flared inner sur-
face only with ether oil or ester oil. 

(Refer to Fig. 14)

 

Then, turn the flare nut 3 to 4 times with your hand and screw 
in the nut.

For the tightening torque, refer to the Table 1.

Table 1

CAUTION

Do not have oil adhere to the screw fixing part of resin 
parts.

If oil adheres, it may weaken the strength of screwed part.

Do not tighten flare nuts too tight.

If a flare nut cracks, the refrigerant may leak.

If there is no torque wrench, use Table 2 as a rule of thumb. 
When tightening a flare nut with a spanner harder and 
harder, there is a point where the tightening torque suddenly 
increases. From that position, tighten the nut additionally the 
angle shown in Table 2. After the work is finished, check 
securely that there is no gas leak. If the nut is not tightened 
as instructed, it may cause slow refrigerant leak and result in 
malfunction (such as does not cool or heat).

Table 2

CAUTION

Insulation of field piping must be carried out up to the 
connection inside the casing.

If the piping is exposed to the atmosphere, it may cause 
sweating, burn due to touching the piping, electric shocks or 
a fire due to the wiring touching the piping.

 

After leak test, referring to 

Fig. 15

, insulate both the gas and 

liquid piping connection with the attached joint insulating 
material (6) and (7) to prevent the pipings from getting 
exposed.
Then, tighten the both ends of insulating material with the 
clamp (4).

Wrap the sealing material (Small) (9) around the joint insulat-
ing material (6) (flare nut section), only the gas piping side. 

Make sure to bring the seam of joint insulating material (6) 
and (7) to the top.

Piping size 

(mm)

Tightening 

torque (N·m)

Dimension for 

processing 

flare A (mm)

Flare shape

 6.4

15.7 ± 1.5

8.9 ± 0.2

 9.5

36.3 ± 3.6

13.0 ± 0.2

 12.7

54.9 ± 5.4

16.4 ± 0.2

 15.9

68.6 ± 6.8

19.5 ± 0.2

 

Torque wrench

Spanner

Flare nut

Union joint

Fig. 13

Coat the flared inner surface
only with ether oil or ester oil

Fig. 14

R0. 4-0.8

90°±2°

A

45°±2°

Piping size 

(mm)

Tightening angle

Recommended arm length of 

tool used

 6.4

60° – 90°

Approximately 150mm



9.5

60° – 90°

Approximately 200mm

 12.7

30° – 60°

Approximately 250mm

 15.9

30° – 60°

Approximately 300mm

01_EN_3P368557-2D.fm  Page 7  Wednesday, February 13, 2019  2:46 PM

Summary of Contents for FXHQ32AVEB9

Page 1: ...ONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO LEES DEZE INSTRUCTIES ZOG...

Page 2: ...parts may result in the air conditioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result...

Page 3: ...al attached to the outdoor unit Do not throw away the accessories until the installation work is completed After the indoor unit is carried into the room to avoid the indoor unit from getting damaged...

Page 4: ...d out Water leakage Does the drain flow out smoothly Water leakage Is the power supply volt age identical to that stated in the manufac turer s label on the air conditioner Does not operate burnout Ar...

Page 5: ...TION 1 For the locations of indoor unit hanging bolts piping outlet holes drain piping outlet hole and electric wiring inlet hole Refer to Fig 3 2 Make holes for hanging bolts piping outlet drain pip...

Page 6: ...Use M8 or M10 bolts for hanging the indoor unit Adjust the length of the hanging bolt from the ceiling in advance Refer to Fig 9 Use hole in anchors for the existing bolts and embedded inserts or foun...

Page 7: ...mass If the strength is insufficient the indoor unit may fall down and cause injuries 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to th...

Page 8: ...ck securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in malfunction such as does not cool or heat Table 2 CAUTION Insulation of...

Page 9: ...eave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material eld supply For prevention of sweating...

Page 10: ...left side refer to Fig 21 When conducting left rear left side drain piping remove the protection net Then remove the drain socket cap and insu lation material applied to left side drain socket and ap...

Page 11: ...nical document Connecting drain piping Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain piping and corrode the heat...

Page 12: ...the works are finished Carry out installation and wiring of the remote controller according to the installation manual attached to the remote controller Do not touch the Printed Circuit Board assembly...

Page 13: ...nnect the remote con troller wiring to P1 P2 and transmission wiring to F1 F2 no polarity Refer to Fig 32 Next tie into a bundle and fix by the included the wiring fixture 11 and clamp 4 so that no te...

Page 14: ...Remote controller wiring Clamp 4 accessory Power supply wiring and Earth wiring Wiring xture 11 accessory Screw for wiring xture 12 accessory Wiring xture 11 accessory Screw for wiring xture 12 acces...

Page 15: ...e remote controller 8 8 FOR REMOTE CONTROL FORCED OFF OR ON OFF OPERATION 1 Wiring method and specification Remote control is available by transmission the external input to the terminals T1 and T2 on...

Page 16: ...er with the operation manual Do not carry out setting other than those shown in the table 10 1 SETTING OF CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 3...

Page 17: ...est operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In addition explain the power supply sta...

Page 18: ...B SELECTOR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN A...

Page 19: ...1904 HT 3P368557 2D EM12A009D 00_CV_3P368557 2D fm Page 2 Tuesday February 12 2019 10 56 AM...

Reviews: