CAUTION

For safety, make sure to use a washer for hanger (3) 
(accessory) and fix by double nuts firmly.

(2) Lift up the indoor unit, slide from the front and put the 

hanger installing bolt (M8) into the securely for tempo-
rary hanging. (Refer to Fig. 11)

(3) Tighten the hanger fixing screws (M5) at 2 places, 

which were removed, as they were before. 
(Refer to Fig. 11)
It is necessary to prevent misalignment of the indoor 
unit.

(4) Tighten the hanger installing bolts (M8) at 4 places 

securely. (Refer to Fig. 11)

(5) When hanging the indoor unit, make sure to use the 

level to have better drainage and install it horizontally. 
Also, if it is possible at the installation site, install so 
that the drain piping side is slightly lower. 
(Refer to Fig. 12)

CAUTION

Setting the indoor unit at an angle opposite to the drain piping 
might cause a water leakage.

• Do not insert materials other than that specified into the 

clearance between the hanger and the washer for hanger 
(3).

Unless the washers are properly attached, the hanging bolts 
may come off from the hanger.

A. When the drain piping is tilted to the right, or to the right 

and back.

Place it level, or tilt it slightly to the right or the back. (Within 
1°)

B. When the drain piping is tilted to the left, or to the left 

and back.

Place it level, or tilt it slightly to the left or the back. (Within 1°)

WARNING

The indoor unit must be securely installed on a place that 
can withstand the mass. 

If the strength is insufficient, the indoor unit may fall down and 
cause injuries.

6.

REFRIGERANT PIPING WORK

For the outdoor unit refrigerant piping, refer to the installation 
manual attached to the outdoor unit.

Carry out insulation of both gas and liquid refrigerant piping 
securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 120°C. For use under high 
humidity, strengthen the insulation material for refrigerant 
piping. If not strengthened, the surface of insulation material 
may sweat.

Before installation work, make sure that the refrigerant is 
R410A. (Unless the refrigerant is R410A, the normal opera-
tion cannot be expected.)

CAUTION

This air conditioner is a dedicated model for new refrig-
erant R410A. Make sure to meet the requirements shown 
below and carry out installation work.
• Use dedicated piping cutters and flaring tools for 

R410A.

• When making a flare connection, coat the flared inner 

surface only with ether oil or ester oil.

• Use only the flare nuts attached to the air conditioner. 

If other flare nuts are used, it may cause refrigerant 
leakage.

• To prevent contamination or moisture from getting 

into the piping, take measures such as pinching or 
taping the pipings.

Hanger

Nut (field supply)

Hanging bolt

Washer for hanger (3) 
(accessory)

Double nuts

Fig. 10

Hanger 
fixing screw 
(M5)

Attachment 
part

Hanger

Reinforcing plate

When carrying the 
indoor unit, do not
hold the reinforcing 
plates.

Hanger installing 
bolt (M8) 

Fig. 11

A

A.B

B

≤1°

≤1°

≤1°

Fig. 12

01_EN_3P368557-2D.fm  Page 6  Wednesday, February 13, 2019  2:46 PM

Summary of Contents for FXHQ32AVEB9

Page 1: ...ONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO LEES DEZE INSTRUCTIES ZOG...

Page 2: ...parts may result in the air conditioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result...

Page 3: ...al attached to the outdoor unit Do not throw away the accessories until the installation work is completed After the indoor unit is carried into the room to avoid the indoor unit from getting damaged...

Page 4: ...d out Water leakage Does the drain flow out smoothly Water leakage Is the power supply volt age identical to that stated in the manufac turer s label on the air conditioner Does not operate burnout Ar...

Page 5: ...TION 1 For the locations of indoor unit hanging bolts piping outlet holes drain piping outlet hole and electric wiring inlet hole Refer to Fig 3 2 Make holes for hanging bolts piping outlet drain pip...

Page 6: ...Use M8 or M10 bolts for hanging the indoor unit Adjust the length of the hanging bolt from the ceiling in advance Refer to Fig 9 Use hole in anchors for the existing bolts and embedded inserts or foun...

Page 7: ...mass If the strength is insufficient the indoor unit may fall down and cause injuries 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to th...

Page 8: ...ck securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in malfunction such as does not cool or heat Table 2 CAUTION Insulation of...

Page 9: ...eave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material eld supply For prevention of sweating...

Page 10: ...left side refer to Fig 21 When conducting left rear left side drain piping remove the protection net Then remove the drain socket cap and insu lation material applied to left side drain socket and ap...

Page 11: ...nical document Connecting drain piping Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain piping and corrode the heat...

Page 12: ...the works are finished Carry out installation and wiring of the remote controller according to the installation manual attached to the remote controller Do not touch the Printed Circuit Board assembly...

Page 13: ...nnect the remote con troller wiring to P1 P2 and transmission wiring to F1 F2 no polarity Refer to Fig 32 Next tie into a bundle and fix by the included the wiring fixture 11 and clamp 4 so that no te...

Page 14: ...Remote controller wiring Clamp 4 accessory Power supply wiring and Earth wiring Wiring xture 11 accessory Screw for wiring xture 12 accessory Wiring xture 11 accessory Screw for wiring xture 12 acces...

Page 15: ...e remote controller 8 8 FOR REMOTE CONTROL FORCED OFF OR ON OFF OPERATION 1 Wiring method and specification Remote control is available by transmission the external input to the terminals T1 and T2 on...

Page 16: ...er with the operation manual Do not carry out setting other than those shown in the table 10 1 SETTING OF CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 3...

Page 17: ...est operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In addition explain the power supply sta...

Page 18: ...B SELECTOR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN A...

Page 19: ...1904 HT 3P368557 2D EM12A009D 00_CV_3P368557 2D fm Page 2 Tuesday February 12 2019 10 56 AM...

Reviews: