* Use “No indication” setting when cleaning indication is not 

necessary such as the case of periodical cleaning being 
carried out.

<Test operation>

After cleaning the indoor unit inside and the suction grille, 
carry out test run according to installation manual attached to 
the outdoor unit. 

When the remote controller operation lamp flashes, it shows 
that something is abnormal. Check the malfunction codes on 
the remote controller. The relation between the malfunction 
codes and abnormal details is described in the operation 
manual attached to the outdoor unit. Particularly, if the indi-
cation is one of those shown in the Table 6, it may be an error 
in the electrical wiring or the power supply is disconnected. 
Therefore, recheck Table 6.

Table 6

CAUTION

After test operation is completed, check the items mentioned in 
the clause 2 “

2. Items to be checked at delivery

” on page 3.

If the interior finish work is not completed when the test 
operation is finished, for protection of the system, ask the 
customer not operate the indoor unit until the interior finish work 
is completed. 
If the system is operated, the inside of the indoor units may be 
polluted by substances generated from the coating and 
adhesives used for the interior finish work and cause water 
splash and leakage. 

To the operator carrying out test operation

After test operation is completed, before delivering the air 
conditioner to the customer, confirm that the control box lid, the 
air filter and suction panel are attached.
In addition, explain the power supply status (power supply ON/
OFF) to the customer.

11. WIRING DIAGRAM

(Refer to Fig. 36)

Contamination

Filter hours

(long life type)

Mode No.

FIRST 

CODE No.

SECOND 

CODE No.

Normal

Approx. 

2500 hrs

10 (20)

0

01

More contami-
nated

Approx. 

1250 hrs

02

With indication

3

01

No indication*

02

Remote controller 

indication

Details

Though the central-
ized control is not 
carried out, the 

lamp “

” 

turns on. 

• The terminals (T1 · T2) for FORCED OFF 

on the indoor unit transmission terminal 
block is short circuited.

“U4” turns on
“UH” turns on

• The power supply to the outdoor unit is not 

made. 

• The power supply work to the outdoor unit 

is not carried out.

• The transmission wiring and the remote 

controller wiring and FORCED OFF wiring 
are connected wrongly.

• The transmission wiring is disconnected. 

No indication

• The power supply to the indoor unit is not 

made. 

• The power supply work to the indoor unit is 

not carried out.

• The remote controller wiring and the trans-

mission wiring and FORCED OFF wiring 
are connected wrongly.

• The remote controller wiring is discon-

nected.

1

(NOTE 6)

2

(NOTE 3)

3

WIRELESS REMOTE CON-
TROLLER 
(RECEIVER/DISPLAY UNIT)
(OPTIONAL ACCESSORY)

4

INPUT FROM OUTSIDE 
(NOTE 7)

5

TRANSMISSION WIRING 
(NOTE 2)
CENTRAL REMOTE CON-
TROLLER

6

(NOTE  4)

7

WIRED REMOTE CON-
TROLLER (OPTIONAL 
ACCESSORY)

8

CONTROL BOX

9

CLASS

01_EN_3P368557-2D.fm  Page 16  Wednesday, February 13, 2019  2:46 PM

Summary of Contents for FXHQ32AVEB9

Page 1: ...ONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO LEES DEZE INSTRUCTIES ZOG...

Page 2: ...parts may result in the air conditioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result...

Page 3: ...al attached to the outdoor unit Do not throw away the accessories until the installation work is completed After the indoor unit is carried into the room to avoid the indoor unit from getting damaged...

Page 4: ...d out Water leakage Does the drain flow out smoothly Water leakage Is the power supply volt age identical to that stated in the manufac turer s label on the air conditioner Does not operate burnout Ar...

Page 5: ...TION 1 For the locations of indoor unit hanging bolts piping outlet holes drain piping outlet hole and electric wiring inlet hole Refer to Fig 3 2 Make holes for hanging bolts piping outlet drain pip...

Page 6: ...Use M8 or M10 bolts for hanging the indoor unit Adjust the length of the hanging bolt from the ceiling in advance Refer to Fig 9 Use hole in anchors for the existing bolts and embedded inserts or foun...

Page 7: ...mass If the strength is insufficient the indoor unit may fall down and cause injuries 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to th...

Page 8: ...ck securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in malfunction such as does not cool or heat Table 2 CAUTION Insulation of...

Page 9: ...eave clearance Wrap from the root of the indoor unit Sealing material Small 9 accessory Bring the seam to the top Flare nut connection Piping insulating material eld supply For prevention of sweating...

Page 10: ...left side refer to Fig 21 When conducting left rear left side drain piping remove the protection net Then remove the drain socket cap and insu lation material applied to left side drain socket and ap...

Page 11: ...nical document Connecting drain piping Do not connect the drain piping directly to the sewage that gives off ammonia odor The ammonia in the sewage may go through the drain piping and corrode the heat...

Page 12: ...the works are finished Carry out installation and wiring of the remote controller according to the installation manual attached to the remote controller Do not touch the Printed Circuit Board assembly...

Page 13: ...nnect the remote con troller wiring to P1 P2 and transmission wiring to F1 F2 no polarity Refer to Fig 32 Next tie into a bundle and fix by the included the wiring fixture 11 and clamp 4 so that no te...

Page 14: ...Remote controller wiring Clamp 4 accessory Power supply wiring and Earth wiring Wiring xture 11 accessory Screw for wiring xture 12 accessory Wiring xture 11 accessory Screw for wiring xture 12 acces...

Page 15: ...e remote controller 8 8 FOR REMOTE CONTROL FORCED OFF OR ON OFF OPERATION 1 Wiring method and specification Remote control is available by transmission the external input to the terminals T1 and T2 on...

Page 16: ...er with the operation manual Do not carry out setting other than those shown in the table 10 1 SETTING OF CEILING HEIGHT Set the SECOND CODE No according to the ceiling height as shown in the Table 3...

Page 17: ...est operation is completed before delivering the air conditioner to the customer confirm that the control box lid the air filter and suction panel are attached In addition explain the power supply sta...

Page 18: ...B SELECTOR SWITCH WIRELESS ADDRESS SET A2P A3P BS1 H1P H2P H3P H4P SS1 SS2 WIRING DIAGRAM CONNECTOR FOR OPTIONAL PARTS INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN A...

Page 19: ...1904 HT 3P368557 2D EM12A009D 00_CV_3P368557 2D fm Page 2 Tuesday February 12 2019 10 56 AM...