![background image](http://html1.mh-extra.com/html/daikin/fxhq32aveb9/fxhq32aveb9_installation-manual_4704281006.webp)
5
English
(3) Remove the parts of the indoor unit.
1)
Remove the suction grille.
•
Slide the suction grille fixing knobs (32 type: 2 places
for each, 63, 100 type: 3 places for each) toward
backward direction (as shown by an arrow) to open
the suction grille widely.
(Refer to Fig. 4)
•
Keeping the suction grille opened, hold the knob at
the back of the suction grille and at the same time,
pull the suction grille forward to remove.
(Refer to Fig. 5)
2)
Remove the decoration side panel (right, left).
•
Remove the fixture screw of the decoration side
panel (one for each), pull forward (arrow direction) to
remove.
(Refer to Fig. 6)
•
Take out accessories.
(Refer to Fig. 6)
•
Open the knock hole at the wiring inlet side at the
rear surface or top surface, and install the attached
resin bushing (10).
3)
Remove the hanger.
•
Loosen 2 bolts for installing the hanger at both sides
(M8) (4 places at left and right) within 10mm.
(Refer to Fig. 7 and 8)
•
Remove the fixture screw for hanger at the back side
(M5), pull the hanger backward (the arrow direction)
to remove.
(Refer to Fig. 8)
CAUTION
Do not remove the tape (milky white) applied to the outside
of the indoor unit. It may cause electric shocks or a fire.
(4) Install the hanging bolts.
•
Use M8 or M10 bolts for hanging the indoor unit.
•
Adjust the length of the hanging bolt from the ceiling in
advance.
(Refer to Fig. 9)
•
Use hole-in-anchors for the existing bolts and embedded
inserts or foundation bolts for new bolts, and fix the unit
firmly to the building so that it may withstand the mass of
the unit.
In addition, adjust the distance from the ceiling in
advance.
CAUTION
If the hanging bolt is too long, it may damage or break the
indoor unit or options.
NOTE
NOTE
NOTE
NOTE
•
Parts shown
Fig. 9
will be all field supply.
5.
INSTALLATION OF THE INDOOR UNIT
It is easy to attach the optional parts before installing the
indoor unit. Refer to also the installation manual attached
to the optional parts.
For installation, use the attached installation parts and
specified parts.
(1) Fix the hanger to the hanging bolt. (Refer to Fig. 10)
Fixing knob
Suction
grille
Fig. 4
Rear knob
Fig. 5
Decoration side panel
Accessories
Fixing screw for
decoration side panel
(M4)
Fig. 6
Resin bushing (10)
(accessory)
Resin bushing (10)
(accessory)
Removable part (for leading
in from the top-surface)
Removable part (for leading
in from the rear-face)
Bolt (M8)
Loosen within10mm
Indoor unit
Hanger
Fig. 7
Hanger fixing screw (M5)
Hanger installing
bolt (M8)
Hanger
Loosen
Fig. 8
Ceiling slab
Foundation bolt
Hanging bolt
Ceiling surface
25-55 mm
Fig. 9
01_EN_3P368557-2D.fm Page 5 Wednesday, February 13, 2019 2:46 PM