
SiBE06-514A
Control Specification
Function and Control
47
3.15 Facility Setting Jumper (cooling at low outdoor
temperature)
Outline
This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
Detail
You can expand the operation range to –15°C by cutting jumper 8 (J8) on the PCB. If the
outdoor temperature falls to –20°C or lower, the operation will stop. If the outdoor temperature
rises, the operation will start again.
Caution
1. If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
provide a windbreak wall.
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4. Cutting jumper 8 (J8) sets the indoor fan tap to the highest position. Notify the user about
this.
1
2
3
PCB
J1
J3
J4
J5
J6
J7
J8
S80
S80
S90
S70
Cut J8 with nippers
or a similar tools.
Summary of Contents for FVKS25BVMB
Page 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Page 19: ...Specifications SiBE06 514A 10 Specifications ...
Page 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Page 85: ...Instruction SiBE06 514A 76 System Configuration ...
Page 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Page 171: ...Others SiBE06 514A 162 Others ...
Page 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Page 181: ...SiBE06 514A iv Index ...