SiBE06-514A
Troubleshooting
Service Diagnosis
99
Troubleshooting
Check No.05
Refer to P.119
Check No.06
Refer to P.120
Check No.11
Refer to P.122
Correct.
Reconnect.
Replace the four way valve
coil.
Replace the outdoor unit
PCB.
Reconnect in position.
Replace a defective
thermistor.
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
(R4699)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Four way valve coil
disconnected (loose)?
YES
YES
NO
Functioning
NO
C
heck No.
11
Check the refrigerant line.
Malfunctioning
z
Insufficient gas
z
Water mixed
z
Stop valve defective
Harness out of connector?
NO
YES
Disconnect the
harness from
the connector.
Resistance between
harnesses about
3k
Ω
±0.5k
Ω
?
Malfunctioning
Functioning
C
heck No.
05
Check the four way valve
switching output.
YES
NO
Any thermistor disconnected?
Malfunctioning
Functioning
C
heck No.
06
Check the thermistors.
Check the continuity of the four
way valve coil and harness.
Summary of Contents for FVKS25BVMB
Page 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Page 19: ...Specifications SiBE06 514A 10 Specifications ...
Page 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Page 85: ...Instruction SiBE06 514A 76 System Configuration ...
Page 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Page 171: ...Others SiBE06 514A 162 Others ...
Page 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Page 181: ...SiBE06 514A iv Index ...