
SiBE06-514A
Troubleshooting
Service Diagnosis
105
4.19
DC Voltage / Current Sensor Abnormality
Remote
Controller
Display
H8
Method of
Malfunction
Detection
Detecting abnormality of the DC sensor by the running frequency of compressor and by the
input current multiplied DC voltage and current.
Malfunction
Decision
Conditions
The compressor running frequency is below 52 Hz.
(The input current is also below 0.5 A.)
If this error repeats 4 times, the system will be shut down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Outdoor unit PCB defective
Troubleshooting
Replace the outdoor unit PCB.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for FVKS25BVMB
Page 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Page 19: ...Specifications SiBE06 514A 10 Specifications ...
Page 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Page 85: ...Instruction SiBE06 514A 76 System Configuration ...
Page 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Page 171: ...Others SiBE06 514A 162 Others ...
Page 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Page 181: ...SiBE06 514A iv Index ...