Control Specification
SiBE06-514A
38
Function and Control
3.5
Input Current Control
Outline
The microcomputer calculates the input current during the compressor is running, and set the
frequency upper limit from such input current.
In case of heat pump model, this control is the upper limit control function of the frequency
which takes priority of the lower limit of four way valve activating compensation.
Detail
Frequency control in each zone
Drooping zone
The maximum limit of the compressor frequency in this control is defined as operation
frequency – 2Hz.
After this, the output frequency is pulled down by 2Hz every second until it reaches the
steady zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is cancelled.
Stop zone
After 2.5 s in this zone, the compressor is stopped.
Limitation of current drooping and stop value according to the outdoor air temperature
1. In case the operation mode is cooling
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
2. In case the operation mode is heating (only for heat pump model)
The current droops when outdoor air temperature becomes higher than a certain level
(model by model).
Compressor Stop
Drooping Zone
Stop Zone
Keep Zone
Reset Zone
I4
I3
I3 –I
α
(R4304)
Cooling
Heating
25 class
35 class
25 class
35 class
I4
(A)
12
12
6.0
7.25
7.5
8.25
I3
(A)
5.25
6.5
6.75
7.5
I3-I
α
(A)
Summary of Contents for FVKS25BVMB
Page 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Page 19: ...Specifications SiBE06 514A 10 Specifications ...
Page 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Page 85: ...Instruction SiBE06 514A 76 System Configuration ...
Page 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Page 171: ...Others SiBE06 514A 162 Others ...
Page 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Page 181: ...SiBE06 514A iv Index ...