Indoor Unit
SiBE06-514A
134
Removal Procedure
3
The figure shows the
power supply PCB
(indoor unit).
SW2
SW2-1 : unused
SW2-2 : unused
SW2-3 : unused
SW2-4 :
OFF - initial set
ON - limit upward air flow
4
The figure shows the
service PCB
.
Select
to discharge air
only from top discharge port.
Select
to discharge air
with automatic pattern
decided in accordance with
operation mode and
operation conditions.
It is recommendable to
select
.
has been selected
before factory shipment.
Step
Procedure
Points