SiBE06-514A
Troubleshooting
Service Diagnosis
93
4.9
Outdoor
Unit PCB Abnormality
Remote
Controller
Display
E1
Method of
Malfunction
Detection
The system follows the microprocessor program to make sure it runs normally.
The system checks to see if the zero-cross signal comes in properly.
Malfunction
Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
The microcomputer is out of control due to external factors.
Noise
Momentary voltage drop
Momentary power failure, etc.
Outdoor unit PCB defective
Broken harness between PCBs
Troubleshooting
Check the indoor and outdoor unit
model numbers.
Match the compatible
models.
Change for the specified
PCB (1) or (2).
Replace the indoor unit
PCB (1) (or the outdoor unit
PCB).
(Q0347)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Indoor unit and outdoor unit
matched?
NO
YES
YES
Matched compatibly?
NO
Check the code numbers
(2P01234, for example) of the
indoor and outdoor unit PCB
with the Parts List.
Turn on the power again.
Replace the outdoor unit
PCB (1).
Ground the system.
Zero-cross signal
abnormality. Replace the
outdoor unit PCB (2).
Replace the harness.
(R4563)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is LED A flashing?
NO
YES
YES
YES
Grounded?
NO
NO
Is the harness
broken?
Check to see if the system is
grounded.
Summary of Contents for FVKS25BVMB
Page 10: ...SiBE06 514A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE06 514A 4 List of Functions ...
Page 19: ...Specifications SiBE06 514A 10 Specifications ...
Page 57: ...Control Specification SiBE06 514A 48 Function and Control ...
Page 85: ...Instruction SiBE06 514A 76 System Configuration ...
Page 133: ...Check SiBE06 514A 124 Service Diagnosis ...
Page 171: ...Others SiBE06 514A 162 Others ...
Page 177: ...Wiring Diagrams SiBE06 514A 168 Appendix ...
Page 181: ...SiBE06 514A iv Index ...