SiBE041401E
Troubleshooting
Service Diagnosis
84
Troubleshooting
Check No.15
Refer to P.96
Check No.18
Refer to P.99
Check No.20
Refer to P.100
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the connection.
Check the power supply voltage.
Correct the power supply.
Voltage as rated?
(R19184)
NO
NO
NO
NO
YES
YES
YES
YES
Check No. 20
Check the short circuit of the diode
bridge.
Check No.15
Check with the inverter analyzer.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power.
Check the electrolytic capacitor
voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB.
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB.
∗
Inverter analyzer:
RSUK0917C
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
320 ± 50 VDC?
Any LED OFF?
Summary of Contents for FTXG20LV1BW
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition...