Field Settings
SiBE041401E
107
Trial Operation and Field Settings
3. Field Settings
3.1
When 2 Units are installed in 1 Room
Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding
wireless remote controller can be set for different addresses.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB
Cut the address setting jumper JA on the control PCB.
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Wireless Remote
Controller
Cut the address setting jumper.
Replace the remote controller if you cut the jumper on the left side.
The heating operation will not be available when the jumper on the left side is cut.
3.2
Model Type Setting
This remote controller is common to the heat pump model and cooling only model.
Replace the remote controller if you cut the jumper on the left side.
The heating operation will not be available when the jumper on the left side is cut.
(R19936)
JA
ADDRESS : JA
EXIST : 1
CUT : 2
(R18416)
ADDRESS
EXIST
1
CUT
2
Jumper
∗
Do not cut the left jumper.
Never cut this jumper.
(R18451)
Summary of Contents for FTXG20LV1BW
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition...