Check
SiBE041401E
101
Service Diagnosis
5.13 Power Module Check
Check No.22
Note:
Check to make sure that the voltage between (+) and (–) of the diode bridge or the power
module is approximately 0 V before checking.
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the (+) or (–) terminal of the
diode bridge or the power module, and the U, V, or W terminal of the compressor with a
multimeter. Evaluate the measurement results referring to the following table.
20/25/35 class
Negative (–) terminal of multimeter
(positive terminal (+) for digital
multimeter)
Diode
bridge (+)
or
Power module
(+)
UVW
Diode
bridge (–)
or
Power module
(–)
UVW
Positive (+) terminal of multimeter
(negative terminal (–) for digital
multimeter)
UVW
Power module (+)
or
Diode
bridge (+)
UVW
Power module
(–)
or
Diode
bridge (–)
Resistance is OK.
several k
Ω
~ several M
Ω
Resistance is NG.
0
Ω
or
∞
(R19947)
Diode bridge
Summary of Contents for FTXG20LV1BW
Page 12: ...SiBE041401E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 14: ...SiBE041401E 3 Specifications Part 2 Specifications 1 Specifications 4...
Page 60: ...SiBE041401E 49 Remote Controller Part 5 Remote Controller 1 Remote controller 50...
Page 113: ...SiBE041401E Check Service Diagnosis 102 50 class Diode bridge R19944...
Page 127: ...Revision History Month Year Version Revised contents 03 2014 SiBE041401E First edition...